Daikin RZQ20KCVJK Скачать руководство пользователя страница 3

English

2

1. SAFETY PRECAUTIONS

Please instruct the customer on how to operate the unit and keep it maintained.
Also, inform customers that they should store this installation manual along with the operation manual for
future reference.

Meaning of WARNING and CAUTION notices.
Both are important notices for safety. Be sure to follow them.

WARNING

  ........Failure to follow these instructions properly may result in personal injury or loss of life.

CAUTION

 ..........Failure to observe these instructions properly may result in property damage or 

personal injury, which may be serious depending on the circumstances.

After completing installation, conduct a trial operation to check for faults and explain to the customer how to 
operate the air conditioner and take care of it with the aid of the operation manual. Ask the customer to store 
the installation manual along with the operation manual for future reference.

This air conditioner comes under the term “appliances not accessible to the general public”.

WARNING

Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, 
electric shocks or fire.

Install the air conditioner in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shocks or fire.

When installing the unit in a small room, take measures against to keep refrigerant concentration from 
exceeding allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to 
oxygen deficiency

Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.

Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
A foundation of insufficient strength may result in the equipment falling and causing injury.

Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit falling and causing accidents.

Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried 
out by qualified personnel according to local laws and regulations and this installation manual.
An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.

Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead.
Imperfect earthing may result in electric shocks or fire.
A high surge current from lightning or other sources may cause damage to the air conditioner.

Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks or fire.

Be sure to switch off the unit before touching any electrical parts.
Touching a live part may result in electric shock.

Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal 
connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or fire.

When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the 
wires so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric shocks, fire or overheating terminals.

If refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into contact with fire.

After completing installation, check for refrigerant gas leakage.
Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source 
of fire, such as a fan heater, stove or cooker.

Do not touch any refrigerant that leaks out of refrigerant piping joints or connections.
Touching it may cause frostbite.

01_EN_3P281953-1B.fm  Page 2  Tuesday, January 25, 2011  3:35 PM

 Please read the these "SAFETY CONSIDERATIONS" carefully before installing air conditioning unit and 

 be sure to install it correctly. After completing the installation, make sure that the unit operates properly 

 during the start-up operation.

Содержание RZQ20KCVJK

Страница 1: ...ODELS RZQ20KCVJK RZQ24KCVJK RZQ45LUYAK RZQ48LUYAK RZQ36KCVJK RZQ45KCVJK READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE English 00_CV_3P281...

Страница 2: ...onics This unit has an inverter so an interrupter capable of handling harmonics is needed to prevent malfunction of the interrupter itself 1 This unit uses R410A as a refrigerant For R410A refrigerant...

Страница 3: ...fter taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circ...

Страница 4: ...wing locations 1 Where there is a high concentration of mineral oil spray or vapour e g a kitchen Plastic parts will deteriorate parts may fall off and water leakage could result 2 Where corrosive gas...

Страница 5: ...ds or objects come in contact with rear fins Work in a team of at least two people when carrying the unit Only hold the unit at the specified positions when carrying it using PP bands or other items S...

Страница 6: ...from radios PCs and stereos Especially in the areas where the incoming signal strength is weak keep the indoor remote controller 3 m or more from electrical appliances Put the power cord and connecti...

Страница 7: ...installing the unit in a place frequently exposed to snow pay special attention to the following In regions where buildups of snow can be expected the air inlet and outlet as well as lower section of...

Страница 8: ...the air outlet is lower than the unit 1 When nothing is obstructing the top There is no height limit for obstructions on the intake side A L L H 0 L 1 2H 750 or more 1 2H L H 1000 or more L H Set the...

Страница 9: ...des of the unit 200 or more 300 200 or more 1000 or more 100 or more 100 or more 1000 or more 100 or more 100 or more 1000 or more 1000 or more 500 or less 100 or more 100 or more 200 or more 300 200...

Страница 10: ...o be installed even when H is lower than L 4 3 IN CASE OF STACKED INSTALLATION Units mm 1 In case obstacles exist in front of the outlet side A L L H 0 L 1 2H 1000 or more 1 2H L H 1250 or more L H Se...

Страница 11: ...ble below 5 PRECAUTIONS ON INSTALLATION Drain pipe disposal Potentially problematic locations for outdoor unit drainage In locations where for example drainage may fall on passersby or frozen drainage...

Страница 12: ...cap 2 correctly It will become the cause of the leak they are not attached correctly 3 Connect vinyl hose on the market internal diameter of 25mm to drain socket 1 If the house is too long and hangs...

Страница 13: ...Installation method of fitting for prevention of overturning If steps need to be taken to prevent the unit from tipping over use the tipping prevention clasps option 6 REFRIGERANT PIPING WORK 6 1 PRE...

Страница 14: ...pipe Thickness and size Decide based on section 6 5 REFRIGERANT PIPE SIZE AND ALLOWABLE PIPE LENGTH For the handling of the stop valves refer to Precautions when the handling piping stop valves in se...

Страница 15: ...table in four directions Refer to Fig 7 Do not let anything other than the designated refrigerant such as air or water enter the refrigerant system When connecting in a downward direction make four ro...

Страница 16: ...ghtening flare nuts always lock the shut off valve with a wrench and then use a torque wrench When tightening the flare of the stop valve do not exceed the rated torque The rated torque is shown on pa...

Страница 17: ...d and turn counter clockwise 2 Stop when the valve rod no longer turns It is now open To close 1 Insert one hex wrench onto the valve rod and turn clockwise 2 Stop when the valve rod no longer turns I...

Страница 18: ...g material of the refrigerant piping according to the installation conditions If this is not done condensation may form on the surface of the insulation material Please refer to the target values show...

Страница 19: ...ng has been connected use nitrogen to perform a refrigerant leak check Table 1 Pipe size Tightening torque A dimensions for processing flares mm Flare shape 9 5 32 7 39 9 N m 12 8 13 2 15 9 61 8 75 4...

Страница 20: ...n your cheek CAUTION Do not use anti oxidants when brazing the pipe joints Residue can clog pipes and break equipment 7 EVACUATING Perform a refrigerant leak check using nitrogen gas airtightness test...

Страница 21: ...amount that is suitable for a piping length exceeding the length for which charging is actually needed Then add the refrigerant from the service port of the liquid side stop valve Select the amount o...

Страница 22: ...ressure resistance always use the special tools dedicated for R410A The refrigerant should be charged from the service port of the liquid side stop valve CAUTION To plumbing persons After completing i...

Страница 23: ...are used Telephone earth and lightning rods the earth potential when struck by lightning gets extremely high The earth is needed in order to reduce the noise generated by the unit s inverter and infl...

Страница 24: ...ulating sleeves Secure the power supply wiring and the transmission wiring to the stop valve attachment plate using the clamping material so that it does not move How to connect the power supply wirin...

Страница 25: ...ver for tightening the terminal screws A screwdriver of small size hurts its screw head and cannot perform proper bolting Over tightening the terminal screw may break it See the table below for the ti...

Страница 26: ...type breaker of 30mA 0 1S 4 Use an earth leakage breaker that can also be used as earth leakage overload short circuit protection Be sure to use earth leakage breakers dedicated for earth leakage prot...

Страница 27: ...erant piping Is the piping size correct Is the piping insulation applied correctly Is the liquid and gas side piping all insulated Are the stop valves for both the liquid and gas sides open completely...

Страница 28: ...parentheses For group batch control the display will always read 01 even though the settings have been changed Furthermore when performing control with two remote controllers on site settings using a...

Страница 29: ...piping path is closed off by the outdoor unit electronic expansion valve etc There are no problems if the unit is run 2 Turn the power on at least 6 hours before operating the unit to protect the com...

Страница 30: ...or unit s installation manual Some malfunction codes are not displayed depending on the indoor and outdoor units CAUTION To plumbing persons To the electrician After the test run when handing the unit...

Страница 31: ...English 30 MEMO...

Страница 32: ...31 English MEMO...

Страница 33: ...R410A R410A SUNISO R410A R410A RZQ45KCVJK RZQ20KCVJK RZQ45LUYAK RZQ24KCVJK RZQ48LUYAK RZQ36KCVJK...

Страница 34: ...2 1...

Страница 35: ...3 1 1 1 2 3 4 5 R410A SUNISO R410A R410A 33 3 3 R407C 40 4 0 R410A R410A...

Страница 36: ...4 2 1 2 48 2 2 1 1 2 1 2 3 1 3 3 71 PP 2 1...

Страница 37: ...5 3 1 4 6 3 2 5 5 4 1 1 1 5 1 5...

Страница 38: ...6 R410A 3 4 500 500 4 DB C 35 C 35 RZQ48 RZQ20 24 RZQ48 RZQ45 RZQ36 1 4 1 2 3 50 100 100 100 500 100...

Страница 39: ...7 1 2 3 1 1 2 L A H 2 1 500 1000 100 500 1000 500 500 1000 150 150 150 50 100 500 500 1000 150 250 50 100 500 L A L H 0 L 1 2H 750 1 2H L H 1000 L H L H A L H...

Страница 40: ...8 2 L A H L A L H 0 L 1 2H 100 50 1 2H L H 200 100 L H L H A L H 2 2 4 1 2 1 2 1000 1000 200 200 300 500 100 100 1000 1000 500 100 100 1000 100 100 100 100 1000 200 200 300 500 1000 500 1000...

Страница 41: ...0 500 1000 L H 100 100 200 300 1000 100 500 200 300 1000 100 100 1000 1500 100 500 1000 1500 1000 L A 0 L 1 2H 250 150 1 2H L H 300 200 L A L H 0 L 1 2H 250 150 1 2H L H 300 200 L H L H A L H L A L H...

Страница 42: ...10 A 500 100 4 4 1 2 2 L A H 5 6 4 2 100 500 200 300 100 100 100 100 100 100 2000 3000 400 600 1000 1500 50 100 1000 2000 100 200 500 1000 L A L H 0 L 1 2H 250 150 1 2H L H 300 200 L H...

Страница 43: ...11 4 2 1 3 1 B 1 2 40 D C 2 2 1 3 1 25 3 A 4 4 A D 5 4 4 4 1 3 2...

Страница 44: ...12 100 M12 6 20 6 1 6 R410A BCuP 11 8 6...

Страница 45: ...13 2 6 3 6 5 6 6 6 5 6 4 6 Suniso R407C R410A R410A 755 0 1...

Страница 46: ...14 9 5 0 8 30 15 9 1 0 50 48 45 36 24 20 9 5 t0 8 15 9 t1 0 24 20 70 50 30 48 45 36 90 70 30 7 8 9 5 6 1 2 R410A 6 6 7 6 8 9...

Страница 47: ...15 10 7 11 16 10 11...

Страница 48: ...16 12 13 6 4 1 2 1 2 14 13 12 16 5 13 5 27 5 22 5...

Страница 49: ...17 15 15 75 C 30 20 80 C 30 C 120 13 9 11 5 14...

Страница 50: ...18 1 4 3 1 1 15 9 5 39 9 32 7 13 2 12 8 15 9 75 4 61 8 19 7 19 3...

Страница 51: ...19 Daikin 0 02 7 4 0 9 5 90 60 200 15 9 60 30 300...

Страница 52: ...8 R410A 1 8 2 8 3 8 48 45 36 24 20 30 10 20 30 40 R410A 24 20 0 50 1 00 48 45 36 0 50 1 00 1 50 2 00 10 20 30 40 50 60 70 R410A 24 20 1 75 2 25 2 75 3 25 3 75 48 45 36 2 70 3 20 3 70 4 20 4 70 5 20 5...

Страница 53: ...21 0 011 0 09 1 2 3 R410A 4 8 R410A RZQ 20 24 RZQ 36 45 48...

Страница 54: ...22 9 230 500...

Страница 55: ...23 VJK L N 3 2 1 YAK...

Страница 56: ...24 M4 1 8 1 2 M5 3 0 2 0 M4 1 9 1 4 M5 2 9 2 4...

Страница 57: ...25 140 125 1 2 0 1 30 3 4 230 60 400 3 60 VJK YAK RZQ VJK YAK 20 24 36 45 45 48 MCA 18 8 28 2 16 7 A 20 30 20...

Страница 58: ...26 10 1 10 1 500 220...

Страница 59: ...27 11 1 01 2 88 3 4 10 03 04 05 6 10 8 10 8 8 01 02 26 16 0 1...

Страница 60: ...28 12 R3T R2T 1 12 1 6 2 3 INSPECTION TEST OPERATION 4 3 RUN STOP 10 3 HEAT operation C 24 INSPECTION TEST OPERATION 5 6 7...

Страница 61: ...29 RUN STOP 5 INSPECTION TEST OPERATION 00 INSPECTION TEST OPERATION 2 12 4 10 E3 E4 L8 U0 E3 E4 L4 U8 U1 U2 U4 UF UA...

Страница 62: ...30...

Страница 63: ......

Страница 64: ...3P369976 1 M14N009 HT 00_CV_3P281953 1B fm Page 2 Frid ay December 24 2010 6 37 PM http www daikin com global_ac...

Отзывы: