5 Preparation
Installer reference guide
9
RZAG71~140L7V1B
Split system air conditioners
4P418663-1 – 2016.02
b
Prevailing wind direction
c
Air outlet
The outdoor unit is designed for outdoor installation only, and for
ambient temperatures ranging:
Model
Cooling
Heating
RZAG
–15~50°C DB
–20~15.5°C WB
5.2.2
Additional installation site requirements
of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.
a
b
c
c
d
a
Snow cover or shed
b
Pedestal (minimum height = 150 mm)
c
Prevailing wind direction
d
Air outlet
5.2.3
About the minimum floor area
WARNING
If appliances contain R32 refrigerant, then the floor area of
the room in which the appliances are installed, operated
and stored must be larger than the minimum floor area.
This applies to:
▪ Indoor units
▪ Outdoor units installed or stored indoors (example:
winter garden, garage, machinery room)
▪ Field piping in unventilated spaces
To determine the minimum floor area
1
Determine the total refrigerant charge in the system (= factory
refrigerant additional refrigerant amount charged).
2
Determine which graph or table to use.
▪ For indoor units: Is the unit ceiling-mounted, wall-mounted or
floor-standing?
▪ For outdoor units installed or stored indoors, and field piping
in unventilated spaces, this depends on the installation
height:
If the installation height
is…
Then use the graph or
table for…
<1.8 m
Floor-standing units
≥1.8 m
Wall-mounted units
3
Use the graph or table to determine the minimum floor area.
m [kg]
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
1
1.2
1.4
1.6
1.8
2
2.2
2.4
2.6
2.8
3
3.2
3.4
3.6
3.8
4
4.2
4.4
4.6
4.8
5
5.2
5.4
5.6
5.8
6
6.2
6.4
6.6
6.8
7
7.2
7.4
7.6
7.8
8
A
min
[m
2
]
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
Ceiling-mounted
unit
(a)
—
4.6
13.5
<1.224
<1.224
—
4.6
182
1.224
0.956
4.8
14.7
1.224
12.9
4.8
198
1.4
1.25
5.0
16.0
1.4
16.8
5.0
215
1.6
1.63
5.2
17.3
1.6
22.0
5.2
232
1.8
2.07
5.4
18.6
1.8
27.8
5.4
250
2.0
2.55
5.6
20.0
2.0
34.3
5.6
269
2.2
3.09
5.8
21.5
2.2
41.5
5.8
289
2.4
3.68
6.0
23.0
2.4
49.4
6.0
309
2.6
4.31
6.2
24.5
2.6
58.0
6.2
330
2.8
5.00
6.4
26.1
2.8
67.3
6.4
351
3.0
5.74
6.6
27.8
3.0
77.2
6.6
374
3.2
6.54
6.8
29.5
3.2
87.9
6.8
397
3.4
7.38
7.0
31.3
3.4
99.2
7.0
420
3.6
8.27
7.2
33.1
3.6
111
7.2
445
3.8
9.22
7.4
34.9
3.8
124
7.4
470
4.0
10.2
7.6
36.9
4.0
137
7.6
496
4.2
11.3
7.8
38.8
4.2
151
7.8
522
4.4
12.4
8.0
40.8
4.4
166
8.0
549
m [kg]
A
min
[m
2
]
<1.224
—
4.6
20.2
1.224
1.43
4.8
22.0
1.4
1.87
5.0
23.8
1.6
2.44
5.2
25.8
1.8
3.09
5.4
27.8
2.0
3.81
5.6
29.9
2.2
4.61
5.8
32.1
2.4
5.49
6.0
34.3
2.6
6.44
6.2
36.6
2.8
7.47
6.4
39.1
3.0
8.58
6.6
41.5
3.2
9.76
6.8
44.1
3.4
11.0
7.0
46.7
3.6
12.4
7.2
49.4
3.8
13.8
7.4
52.2
4.0
15.3
7.6
55.1
4.2
16.8
7.8
58.0
4.4
18.5
8.0
61.0
Wall-mounted
unit
(b)
m [kg]
A
min
[m
2
]
Floor-standing
unit
(c)
m [kg]
A
min
[m
2
]