12 Technical data
Installer reference guide
37
RZAG71~140L7V1B
Split system air conditioners
4P418663-1 – 2016.02
RZAG71
RZAG100
RZAG125
RZAG140
Drain
Quantity
5
Type
Hole
Diameter (OD)
Ø26 mm
Piping length
Minimum
3 m
Maximum
55 m
85 m
Equivalent
75 m
100 m
Chargeless
30 m
Additional refrigerant charge
See "To determine the additional refrigerant amount"
Maximum height difference between outdoor
unit and indoor unit
30 m
Heat insulation
Both liquid and gas pipes
Defrost method
Reverse cycle
Defrost control
Sensor for outdoor heat exchanger temperature
Capacity control method
Inverter-controlled
Safety devices
Manual high pressure switch / Automatic high pressure switch / low pressure switch / fan driver
overload protector / fuse
Electrical specifications
RZAG71
RZAG100
RZAG125
RZAG140
Power supply
Name
V1
Phase
1~
Frequency
50 Hz
Voltage
220-240 V
Voltage range
Minimum
198 V
Maximum
264 V
Current
Minimum S
sc
value
Equipment complying with EN 61000‑3‑12
(a)
Recommended fuses
20 A
32 A
Wiring connections
For power supply
See "Connecting the electrical wiring"
For connection with indoor
Power supply intake
Outdoor unit only
(a)
European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.