MAINTENANCE
Malfunction display: E5 Compressor Overheat
Abnormal overheat
Yes
Adjust compressor's
connection line
No
Replace main
board
Replace overheat protector
Refer to “E1”
Contact the power supplier
Check if
compressor’s connection line is
properly connected
Check if current
value is higher than the protector’s
setting
If unit’s high pressure is normal
If voltage is normal
No
No
No
Yes
Yes
Yes
Yes