12 Technical data
Installer and user reference guide
59
RXYTQ8~16T7YF
VRV IV system air conditioner
4P388989-1B – 2016.02
Specification
8 HP
10 HP
12 HP
14 HP
16 HP
▪ Sound power
(f)
78 dBA
81 dBA
86 dBA
▪ Sound pressure
(g)
58 dBA
61 dBA
64 dBA
Refrigerant
▪ Type
R410A
▪ Charge
6.7 kg
10.3 kg
10.4 kg
11.7 kg
11.8 kg
Refrigerant oil
Synthetic (ether) oil
Safety devices
▪ High pressure switch
▪ Fan driver overload protector
▪ Inverter overload protector
▪ PCB fuse
(a)
Nominal cooling capacities are based on T1 (indoor temperature: 26.7°C DB, 19.4°C WB, outdoor temperature: 35°C DB, AHRI 1230:2010,
power input indoor units (duct type) included), T2 (indoor temperature: 26.6°C DB, 19.4°C WB, outdoor temperature: 48°C DB, AHRI 1230:2010,
power input indoor units (duct type) included), T3 (indoor temperature: 29.0°C DB, 19.0°C WB, outdoor temperature: 46°C DB, ISO15042:2011,
power input indoor units (duct type) included), Eurovent (indoor temperature 27.0°C DB, 19.0°C WB, outdoor temperature: 35°C DB,
Eurovent 2015, power input indoor units (duct type) excluded).
(b)
Nominal heating capacities are based on indoor temperature 20°C DB, outdoor temperature 7°C DB and 6°C WB, Eurovent 2015, equivalent
refrigerant piping: 5 m, level difference: 0 m.
(c)
Actual number of units depends on the indoor unit type (VRV DX,...) and the connection ratio restriction for the system (50%≤CR≤130%).
(d)
Nominal at 230 V.
(e)
Sound values are measured in a semi-anechoic room.
(f)
Sound power level is an absolute value that a sound generates.
(g)
Sound pressure level is a relative value depending on the distance and acoustic environment. For more details, refer to sound level drawings in
the technical data book.
Electrical specifications
Specification
8 HP
10 HP
12 HP
14 HP
16 HP
Power supply
▪ Name
Y1
▪ Phase
3N~
▪ Frequency
50 Hz/60 Hz
▪ Voltage at 50 Hz
▪ Voltage at 60 Hz
380-415 V
400 V
Current
▪ Nominal running current (RLA)
(a)
8 A
9.3 A
12.7 A
15.8 A
19.3 A
▪ Starting current (MSC)
(b)
≤MCA
▪ Minimum circuit amps (MCA)
(c)
16.1 A
22 A
24.0 A
27.0 A
31.0 A
▪ Maximum fuse amps (MFA)
(d)
20 A
25 A
32 A
40 A
▪ Total overcurrent amps (TOCA)
(e)
17.3 A
28 A
35.4 A
▪ Full load amps (FLA)
(f)
1.2 A
1.8 A
2.6 A
Voltage range at 50 Hz
380-415 V ±10% V
Voltage range at 60 Hz
400 V ±10% V
Wiring connections
▪ For power supply
5G
▪ For connection to indoor unit
2 (F1/F2)
Power supply intake
both indoor and outdoor unit
(a)
RLA is based on indoor unit temperature 27°C DB and 19°C WB, outdoor temperature 35°C DB.
(b)
MSC=the maximum current during startup of the compressor. VRV IV uses only inverter compressors. MCA must be used to select the correct
field wiring size. The MCA can be regarded as the maximum running current.
(c)
MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
(d)
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
(e)
TOCA means the total value of each OC set.
(f)
FLA=nominal running current fan. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not
below or above listed range limits. Maximum allowable voltage range variation between phases is 2%.