RXYSQ4~6M7V3B
VRVII-S system air conditioner
4PW17806-1C
Installation manual
13
Field line connection: Control wiring and cool/heat selection
See
Sequential start
Make the outdoor unit cable connections shown below.
The outdoor unit PC board (A1P) is factory set at "Sequential start
available".
Setting the cool/heat operation (heat pump unit only)
1
Performing cool/heat setting with the remote controller
connected to the indoor unit.
Keep the cool/heat selector switch (DS1) on the outdoor unit PC
board at the factory setting position IN/D UNIT.
2
Performing cool/heat setting with the cool/heat selector.
Connect the cool/heat selector remote controller (optional) to the
A/B/C terminals and set the cool/heat selector switch (DS1) on
the outdoor unit PC board (A1P) to OUT/D UNIT.
■
The wiring from the indoor units must be connected to the F1/F2
(In-Out) terminals on the PC board in the outdoor unit.
■
After installing the interconnecting wires inside the unit, wrap
them along with the on-site refrigerant pipes using finishing
tape, as shown in
For the above wiring, always use vinyl cords with 0.75 to 1.25 mm
2
sheath or cables (2 core wires). (3 core wire cables are allowable for
the cooler/heater changeover remote controller only.)
Precautions when laying power wiring
Use round pressure terminals for connections to the power
terminal block.
When none are available, follow the instructions below.
■
Do not connect wiring of different thicknesses to the
power terminal block. (Slack in the power wiring may
cause abnormal heat.)
■
When connecting wiring which is the same thickness,
do as shown in the figure below.
■
For wiring, use the designated power wire and
connect firmly, then secure to prevent outside
pressure being exerted on the terminal board.
■
Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
strip the head and make proper tightening impossible.
■
Over-tightening the terminal screws may break them.
■
See the table below for tightening torque for the
terminal screws.
If an excessive force is applied while connecting a cable to
the terminal block on the PC board, the PC board may be
damaged.
1
Cool/heat selector (not required for cooling only units)
2
Outdoor unit PC board (A1P)
3
Take care of the polarity (not required for cooling only units)
4
Use the conductor of sheathed wire (2 wire) (no polarity)
5
Terminal board (field supply)
1
2
1
Round pressure terminal
2
Power wire
Tightening torque (N•m)
M5 (Power terminal block/ground wire)
2.39~2.92
M4 (Shielded ground)
1.18~1.44
M3.5 (Control wiring block)
0.79~0.97
1
Remote controller
1
Cool/heat selector
For low-noise operation, it is necessary to get the optional
'External control adaptor for outdoor unit' (DTA104A61/62).
For details, see the installation manual attached to the
adaptor.
■
Be sure to follow the limits below. If the unit-to-unit
cables are beyond these limits, it may result in
malfunction of transmission.
Maximum wiring length: 1000 m
Total wiring length: 2000 m
Maximum No. of branches: 9
■
Up to 9 branches are possible for unit-to unit cabling.
No branching is allowed after branching.
■
Never connect the power supply to unit-to-unit cabling
terminal block. Otherwise the entire system may
break down.
1
Liquid pipe
2
Gas pipe
3
Interconnecting wiring
4
Insulator
5
Finishing tape
1
Branch
2
Subbranching