12 - 2 Refrigerant Pipe Selection
RXYSCQ-TV1
RXYSQ-TV1
RXYSQ-TY1
System pattern
Excluding ·BP· units and including ·EXV· kits.
·VRV DX· indoor units only
50~130%
Maximum ·64·
50~130%
-
-
·RA DX· indoor units only
80~130%
Maximum ·32·
-
80~130%
-
·VRV DX· indoor unit + ·AHU·
Mix
·AHU· only
Pair + multi
Notes
1. There is no restriction on the number of connectable ·BP· boxes.
2. ·EKEXV· kits are also considered indoor units.
3. Restrictions regarding the air handling unit capacity
4. Pair AHU = system with 1 air handling unit connected to one outdoor unit
Multi AHU = system with multiple air handling units connected to one outdoor unit
About ventilation applications
I. ·FXMQ_MF· units are considered air handling units, following air handling unit limitations.
- Maximum connection ratio when combined with ·VRV DX· indoor units: ·CR
ч
30·%.
- Maximum connection ratio when only air handling units are connected: ·CR
ч
100·%.
- Minimum connection ratio when only ·FXMQ_MF· units are connected: ·CR
ш
50·%
For information on the operation range, refer to the documentation of the ·FXMQ_MF· unit.
II. ·Biddle· air curtains are considered air handling units, following air handling unit limitations:
For information on the operation range, refer to the documentation of the ·Biddle· unit.
III. ·EKEXV + EKEQ· units combined with an air handling unit are considered air handling units, following air handling unit limitations.
For information on the operation range, refer to the documentation of the ·EKEXV-EKEQ· unit.
IV. ·VKM· units are considered to be regular ·VRV DX· indoor units.
For information on the operation range, refer to the documentation of the ·VKM· unit.
V. Because there is no refrigerant connection with the outdoor unit (only communication F1/F2), ·VAM· units do not have connection limitations.
However, since there is communication via F1/F2, count them as regular indoor unit when calculating the maximum allowed number of connectable indoor units.
50~110%
Maximum ·64·
50~110%
-
0~110%
90~110%
Maximum ·64·
-
-
90~110%
Total
Allowed capacity
Allowed connection ratio (CR)
Capacity
Maximum allowed amount of connectable indoor units (·VRV,
RA, AHU·)
VRV DX indoor unit
·RA DX· indoor unit
Air handling unit (AHU)
Other combinations are not allowed.
(1)
(2)
(3)
(3)
(4)
(2)
3D097984
Содержание RXYSCQ-TV1 Series
Страница 1: ...Air Conditioning Technical Data RXYSCQ TV1 RXYSCQ4TMV1B RXYSCQ5TMV1B...
Страница 2: ......
Страница 17: ...3 9 VRV Systems RXYSCQ TV1 15 Outdoor Unit RXYSCQ TV1 9 Wiring diagrams 9 1 Wiring Diagrams Single Phase...
Страница 21: ...3 12 VRV Systems RXYSCQ TV1 19 Outdoor Unit RXYSCQ TV1 12 Installation 12 1 Installation Method...
Страница 22: ...Outdoor Unit RXYSCQ TV1 12 VRV Systems RXYSCQ TV1 20 12 Installation 12 1 Installation Method...
Страница 26: ......