Si39-407
Test Operation
Test Operation
119
Malfunction code
In case of an alarm code displayed on remote controller:
1.1.4 Confirmation on normal operation
•
Conduct normal unit operation after the check operation has been completed.
(When outdoor air temperature is 24°C or higher, the unit can not be operated with heating
mode. See the instruction manual attached.)
Confirm that the indoor/outdoor units can be operated normally.
(When an abnormal noise due to liquid compression by the compressor can be heard, stop
the unit immediately, and turn on the crankcase heater to heat up it sufficiently, then start
operation again.)
•
Operate indoor unit one by one to check that the corresponding outdoor unit operates.
•
Confirm that the indoor unit discharges cold air (or warm air).
•
Operate the air direction control button and flow rate control button to check the function of
the devices.
<Precautions for checking normal operation>
•
For a period of approximately 5 minutes after the compressor stops, even if the ON/OFF
button for the indoor units in one and the same system is pressed, the compressor will not
operate.
•
After stopping the compressor operation using the remote controller, the outdoor unit may
conduct the residual operation for a period of 5 minutes at maximum.
•
If the system is set to "nighttime automatic low noise operation setting" or "external low noise
level setting", the outdoor unit fan may operate at a low speed, which, however, is not a
malfunction.
•
When the check operation is not conducted using the TEST OPERATION button at the first
test operation after installation, the malfunction code "U3" will be displayed.
Be sure to conduct the check operation according to 2. Check Operation (for details, refer to
information on the previous page.)
Cause of trouble due to faulty
installation work
Alarm
code
Countermeasure
The stop valve of an outdoor unit is left
closed.
E3
E4
F3
F6
UF
Open the stop valve.
The phases of the power to the outdoor
units are reversed.
U1
Exchange two of the three phases (L1, L2, L3) to make a positive
phase connection.
No power is supplied to an outdoor or
indoor unit (including phase interruption).
U1
U4
Check if the power wiring for the outdoor units are connected
correctly.
(If the power wire is not connected to L2 phase, no malfunction display
will appear and the compressor will not work.)
Incorrect transmission between units
UF
Check if the refrigerant piping line and the unit transmission wiring are
consistent with each other.
Refrigerant overcharge
E3
F6
UF
Recalculate the required amount of refrigerant from the piping length
and correct the refrigerant charge level by recovering any excessive
refrigerant with a refrigerant recovery machine.
Insufficient refrigerant
E4
F3
•
Check if the additional refrigerant charge has been finished
correctly.
•
Recalculate the required amount of refrigerant from the piping
length and add an adequate amount of refrigerant.
If an outdoor multi terminal is connected
when there is one outdoor unit installed
U7
UF
Remove the line from the outdoor multi terminals (Q1 and Q2).
The operation mode on the remote
controller was changed before the check
operation.
UF
E4
Set the operation mode on all indoor unit remote controllers to
"cooling".
Содержание RXYQ5-48MAY1
Страница 1: ...RXYQ5 48MAY1 R410A Heat Pump 50Hz Si39 407...
Страница 20: ...Si39 407 Specifications 9 Part 2 Specifications 1 Specifications 10 1 1 Outdoor Units 10 1 2 Indoor Units 21...
Страница 59: ...Specifications Si39 407 48 Specifications...
Страница 62: ...Si39 407 Refrigerant Circuit Refirgerant Circuit 51 RXYQ5MA 3D048203 2 4 3 5 K J S E D M T N P A G O 1 W V...
Страница 83: ...Refrigerant Flow for Each Operation Mode Si39 407 72 Refirgerant Circuit...
Страница 173: ...Field Setting Si39 407 162 Test Operation...
Страница 184: ...Si39 407 Troubleshooting by Remote Controller Troubleshooting 173...
Страница 277: ...Troubleshooting OP Unified ON OFF Controller Si39 407 266 Troubleshooting...
Страница 279: ...Piping Diagrams Si39 407 268 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ5MAY1 3D048203...
Страница 280: ...Si39 407 Piping Diagrams Appendix 269 RXYQ8MAY1 RXYQ10MAY1 RXYQ12MAY1 3D048033A...
Страница 281: ...Piping Diagrams Si39 407 270 Appendix RXYQ14MAY1 RXYQ16MAY1 3D048034A...
Страница 285: ...Piping Diagrams Si39 407 274 Appendix FXUQ BEVQ Indoor unit Connection Unit 4D037995E 4D034127B...
Страница 286: ...Si39 407 Piping Diagrams Appendix 275 FXAQ BEVQ Indoor unit Connection Unit 4D047084 4D034127B...
Страница 287: ...Piping Diagrams Si39 407 276 Appendix FXLQ BEVQ Indoor unit Connection Unit 4D047084 4D034127B...
Страница 288: ...Si39 407 Wiring Diagrams for Reference Appendix 277 2 Wiring Diagrams for Reference 2 1 Outdoor Unit RXYQ5MAY1 3D047087C...
Страница 289: ...Wiring Diagrams for Reference Si39 407 278 Appendix RXYQ8MAY1 RXYQ10MAY1 RXYQ12MAY1 3D047088C...
Страница 290: ...Si39 407 Wiring Diagrams for Reference Appendix 279 RXYQ14MAY1 RXYQ16MAY1 3D047089C...
Страница 294: ...Si39 407 Wiring Diagrams for Reference Appendix 283 2 3 Indoor Unit FXCQ20M 25M 32M 63MVE 3D039556A...
Страница 295: ...Wiring Diagrams for Reference Si39 407 284 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Страница 296: ...Si39 407 Wiring Diagrams for Reference Appendix 285 FXZQ20M 25M 32M 40M 50MVE 3D038359...
Страница 297: ...Wiring Diagrams for Reference Si39 407 286 Appendix FXFQ25M 32M 40M 50M 63M 80M 100M 125MVE 3D039600A...
Страница 298: ...Si39 407 Wiring Diagrams for Reference Appendix 287 FXKQ25M 32M 40M 63MVE 3D039564A...
Страница 299: ...Wiring Diagrams for Reference Si39 407 288 Appendix FXDQ20N 25N 32N 40N 50N 63NVE 3D045500A...
Страница 300: ...Si39 407 Wiring Diagrams for Reference Appendix 289 FXSQ20M 25M 32M 40M 50M 63M 80M 100M 125MVE 3D039561A...
Страница 301: ...Wiring Diagrams for Reference Si39 407 290 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Страница 302: ...Si39 407 Wiring Diagrams for Reference Appendix 291 FXMQ200M 250MVE 3D039621A...
Страница 303: ...Wiring Diagrams for Reference Si39 407 292 Appendix FXHQ32M 63M 100MVE 3D039801C...
Страница 304: ...Si39 407 Wiring Diagrams for Reference Appendix 293 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206A...
Страница 306: ...Si39 407 Wiring Diagrams for Reference Appendix 295 FXUQ71M 100M 125MV1 3D044973...
Страница 307: ...Wiring Diagrams for Reference Si39 407 296 Appendix FXAQ20MH 25MH 32MH 40MH 50MHV1 3D046348A...
Страница 308: ...Si39 407 Wiring Diagrams for Reference Appendix 297 FXLQ20MH 25MH 32MH 40MH 50MHV1 3D046787A...
Страница 309: ...Wiring Diagrams for Reference Si39 407 298 Appendix FXMQ125MF 200MF 250MFV1 3D044996B...
Страница 310: ...Si39 407 Wiring Diagrams for Reference Appendix 299 BEVQ50MVE 3D046579A Notes...
Страница 311: ...Wiring Diagrams for Reference Si39 407 300 Appendix BEVQ71M 100M 125MVE 3D044901A Notes...
Страница 335: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 407 324 Appendix...
Страница 349: ...Si39 407 iv Index...
Страница 352: ...Printed in Singapore 03 2005 COS...