Access mode 2
Push BS1 for at least 5 seconds. Segment indication changes to:
INFORMATION
If you get confused in the middle of the process, push BS1.
Then it returns to idle situation (no indication on segment displays:
blank, refer to Functions of the push button switches which are located
on the outdoor printed circuit board (A1P) on page 24.).
Mode 1
Mode 1 is used to set basic settings and to monitor the status of the
unit (15.2. Monitoring function and field settings on page 32).
•
Changing and access the setting in mode 1:
Once mode 1 is selected (push BS1 one time), you can select the
wanted setting. It is done by pushing BS2. Accessing the selected
setting’s value is done by pushing BS3 one time.
•
To quit and return to the initial status, press BS1.
Example
:
Checking the content of parameter [1-10] (to know how many indoor
units are connected to the system).
[A-B]=C in this case defined as: A=1; B=10; C=the value we want to
know/monitor:
•
Make sure the segment indication is displayed in operational default
mode as shipped from factory.
•
Push BS1 one time; result segment display:
Result: mode 1 is accessed.
•
Push BS2 10 times; result segment display:
Result: mode 1 setting 10 is addressed.
•
Push BS3 one time; the value which is returned (depending on the
actual field situation), is the amount of indoor units which are con
-
nected to the system.
Result: mode 1 setting 10 is addressed and selected, return value is
monitored information
•
To leave the monitoring function, push BS1 one time, you will return
to the default situation when shipped from factory.
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
•
Changing and access the setting in mode 2:
Once mode 2 is selected (push BS1 for more than 5 seconds), you
can select the wanted setting. It is done by pushing BS2.
Accessing the selected setting’s value is done by pushing BS3 one
time.
•
To quit and return to the initial status, press BS1.
•
Changing the value of the selected setting in mode 2:
- Once mode 2 is selected (push BS1 for more than 5 seconds)
you can select the wanted setting. It is done by pushing BS2.
- Accessing the selected setting’s value is done by pushing BS3
one time.
- Now BS2 is used to select the required value of the selected
setting.
-
When the required value is selected, you can define the change
of value by pushing BS3 one time.
- Press BS3 again to start operation according to the chosen value.
Example:
Checking the content of parameter [2-18] (to define the high static
pressure setting of the outdoor unit’s fan).
[A-B]=C in this case defined as: A=2; B=10; C=the value we want to
know/change
Make sure the segment indication is as during normal operation (de-
fault situation when shipped from factory).
•
Push BS1 for over 5 seconds; result segment display:
Result: mode 2 is accessed.
•
Push BS2 18 times; result segment display:
Result: mode 2 setting 18 is addressed.
•
Push BS3 one time; the value which is returned (depending on the
actual field situation), is the status of the setting. In the case of [2-
18], default value is 0, which means the function is not active.
Result: mode 2 setting 18 is addressed and selected, return value is
the current setting situation.
•
To change the value of the setting, push BS2 till the required value
appears on the segment indication. When achieved, define the set
-
ting value by pushing BS3 one time. To start operation according to
the chosen setting, confirm again by pushing BS3.
•
To leave the monitoring function, push BS1 two times, you will
return to the default situation when shipped from factory.
13 .2 .2 . Operating the DIP switches
By operating the DIP switches it is possible to:
What to do with DIP switch DS1
1
Cool/Heat selector (refer to the manual of the Cool/
Heat selector switch)
OFF=not installed=factor setting
2-4
NOT USED
DO NOT CHANGE THE FACTORY SETTING
What to do with DIP switch DS2
1-4
NOT USED
DO NOT CHANGE THE FACTORY SETTING
13 .3 .
Connecting the PC configurator to the outdoor unit
Connection of the optional PC configurator cable to the outdoor unit
has to be done on A1P. Connect the EKPCCAB* cable to the 5-pin
blue connector X27A.
CAUTION
Works executed on the outdoor unit are best done under dry weather
conditions to avoid water ingress.