Outdoor Unit Installation Drawings
CAUTION
Set the piping length from
4.92ft (1.5m) to 49.2ft (15m).
Wrap the insulation pipe with
the finishing tape from bottom
to top.
In sites with poor drainage, use
block bases for outdoor unit.
Adjust foot height until the unit
is leveled. Otherwise, water
leakage or pooling of water may
occur.
Where there is a danger of the unit
falling, use foot bolts, or wires.
Allow space for piping
and electrical servicing.
9-27/32 (250) from wall
unit: inch (mm)
O.D. 3/8 inch (9.5mm)
Gas pipe
Liquid pipe
O.D. 1/4 inch (6.4mm)
0.22oz/ft
Max. allowable length
39.3ft (12m)
49.2ft (15m)
Max. allowable height
Additional refrigerant
required for refrigerant
pipe exceeding
33ft (10m) in length.
*
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced perfomance.
*
The suggested shortest pipe length is 4.92ft (1.5m), in order to
avoid noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how
the unit is installed and the environment in which it is used.)
4.92ft (1.5m)
Min. allowable length
18-1/2 (470)
(Foot bolt-hole centers)
(From unit’s side)
3-25/32 (96)
(Foot bolt-hole
centers)
11-13/16 (300)
How to remove the stop
valve cover
Remove the screw on the
stop valve cover.
Slide the lid downward
to remove it.
How to attach the stop
valve cover
Insert the upper part of
the stop valve cover into the
outdoor unit to install.
Tighten the screws.
Stop valve cover
*