background image

5

English

Outdoor Unit Installation

4.

Refrigerant piping.

1) Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully with the torque 

wrenches.
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas.

2) To prevent gas leakage, apply refrigeration oil on both inner and outer surfaces of the flare. (Use refrigeration oil for 

R410A.) 

5.

Purging air and checking gas leakage.

• When piping work is completed, it is necessary to purge the air and check for gas leakage.

 WARNING

1) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
2) When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
3) R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
4) Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum 

pump or the unit.

• If using additional refrigerant, perform air purging from the refrigerant pipes and 

indoor unit using a vacuum pump, then charge additional refrigerant.

• Use a hexagonal wrench (4mm) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified 

tightening torque.

Coat here with refrigeration oil 

Torque wrench

Piping union

Flare nut

Spanner

Flare nut tightening torque

 

Gas side

Liquid side

 

3/8 inch

1/4 inch

 32.7-39.9N 

l

 m 

14.2-17.2N 

l

 m

 

(333-407kgf 

l

 cm) 

(144-175kgf 

l

 cm)

Valve cap tightening torque

 

Gas side

Liquid side

 

3/8 inch

1/4 inch

 21.6-27.4N 

l

 m 

21.6-27.4N 

l

 m

  (220-280kgf 

l

 cm) 

(220-280kgf 

l

 cm)

Service port cap 

10.8-14.7N 

l

 m

tightening torque 

(110-150kgf 

l

 cm)

Compound 
pressure gauge

Pressure 
meter

High-
pressure 
valve

Low-pressure 
valve

Vacuum pump 
adapter

Vacuum pump

Service port

Gas stop 
valve

Valve caps

Liquid stop valve

Charging 
hoses

Gauge 
manifold

01_EN_3P190651-2C.fm  Page 5  Tuesday, March 13, 2007  4:35 PM

Содержание RXR28EV1B9

Страница 1: ...V1B9 Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split syst...

Страница 2: ...TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ E...

Страница 3: ...e on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire If any refrigerant has leaked out during the in...

Страница 4: ...s to prevent interference to images and sounds Noises may be heard even if they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere o...

Страница 5: ...e from entering it until it is connected to the indoor unit and outdoor unit ducts Do not bend the humidifying hose more than 90 C C C C C D E F C C C No refrigerant needs to be added if the piping do...

Страница 6: ...drain water may freeze impairing heating performance 3 Flaring the pipe end 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the...

Страница 7: ...onment 4 Use a vacuum pump for R410A exclusively Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit If using additional refrigerant perform air purging from t...

Страница 8: ...tion 3 Do vacuum pumping and make sure that the compound pressure gauge reads 0 1MPa 76cmHg The vacuum pump should run for at least 10 min 4 Close gauge manifold s low pressure valve Lo and stop vacuu...

Страница 9: ...t n 2 the additional refrigerant amount charged in the field and n 1 2 the total refrigerant charge on the refrigerant charge label supplied with the product Important information regarding the refrig...

Страница 10: ...o the outdoor humidifying duct 2 Apply a binding band to prevent the humidifying hose from coming off 2 Connecting the cut humidifying hoses When installing the cut humidifying hoses follow the instru...

Страница 11: ...m the wire 20mm 2 Connect the connection wires between the indoor and outdoor units so that the termi nal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used...

Страница 12: ...ooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are ther mally insulated Water leakage Draining line is properly installed Water leakage System is properly ear...

Страница 13: ...0704 HT 3P190651 2C M06B104C Two dimensional bar code is a code for manufacturing...

Отзывы: