RX(Y)Q5-10-1 RXQ RXYQ
RXYHQ1 RX(Y)Q14~18P7W1BA
VRVIII System air conditioner
4PW48461-1
Installation manual
22
In range:
The unit will restart from the charging mode judgement onwards
and the cooling mode will be selected. However, if in the mean
time the temperature has become out of range, heating mode
will be selected again, this is required to increase the indoor
temperature.
■
Charging in cooling mode
6.
Start up
Wait while the unit is preparing for charging in cooling mode.
7.
Ready
Press the
button once within 5 minutes.
If the
button is not pushed within 5 minutes,
P2
will be
displayed on the remote controller. Refer to
"4 Remote controller
malfunction code display" on page 24
.
8.
Operation
When the following LED display is shown, open valve A and
close the frontpanel. If the frontpanel is left open, the system
can not operate properly during the refrigerant charging.
*
= The state of this LED is not important.
9.
Complete
If the display on the remote controller shows a flashing
PE
code,
charging is almost finished.
When the unit stops operating, close valve A immediately and
check the LEDs and check if the
P9
code is displayed on the
remote controller. When the charging amount is little, the
PE
code may not be displayed, but instead the
P9
code will be
displayed immediately.
If it is not as shown above, correct the malfunction (as indicated
in the display of the remote controller) and restart the complete
charging procedure.
10. Press the
button to perform the temperature range
check
Out of range:
In these cases, press the
button once and follow the
procedure as described in
"5 Final adjustment of the amount of
refrigerant" on page 24
.
In range:
The state of the LEDs will show:
Press the
button once. The procedure is completed.
Record the amount that was added on the additional refrigerant
charge label provided with the unit and attach it on the back side
of the front panel.
Perform the test procedure as described in
"In case refrigerant
was added by using the leak detection function" on page 28
.
2
Adding refrigerant without using leak detection function
■
Charge with the outdoor unit at standstill
1.
Calculate how much refrigerant to be added using the formula
explained in the chapter
"How to calculate the additional
refrigerant to be charged" on page 10
.
2.
Open valve C (valves A and B and the stop valves must be left
closed) and charge the required amount of refrigerant through
the liquid side stop valve service port.
■
When the required amount of refrigerant is fully charged,
close valve C. Record the amount of refrigerant that was
added on the additional refrigerant charge label provided
with the unit and attach it on the back side of the front panel.
Perform the test procedure as described in
"In case
refrigerant was added without using the leak detection
function (pre-charging, charging in heating mode)" on
page 28
.
■
When the additional charging is not complete, perform the
procedure explained in the chapter
"Charge with operating
outdoor unit" on page 22
.
■
Charge with operating outdoor unit
Charge the refrigerant through valve A.
1.
Start of charging refrigerant manually
-
Open the liquid and gas side stop valves and the service port
stop valve. (Valves A, B and C must be closed.)
-
Close all frontpanels except the electric box frontpanel and
turn the power ON.
-
Make sure all indoor units are connected, refer to
"11.4. How
to check how many units are connected" on page 19
.
-
If the H2P LED is not flashing (in 12 minutes time after
turning on the power), make sure it is displayed as shown
below.
If the H2P LED is flashing, check the malfunction code on the
remote controller
"4 Remote controller malfunction code
display" on page 24
.
2.
Press the
button once if the LEDs combination is not
as in the figure below.
3.
Press the
button once.
4.
Hold the
button down for 5 seconds or more.
5.
Charging mode judgement
If the indoor temperature is 20°C DB or lower, charging in
cooling mode is not possible in some cases. The unit will
automatically select the cooling mode or heating mode for
charging.
H1P
H2P
H3P
H4P
H5P
H6P
H7P
Pressure control
(for the first minute)
x c x
x
x
x w
Start up control
(for the next 2 minutes)
x c x
x
x w x
Waiting for stable
heating conditions
(for the next ±15
minutes (according to
the system))
x c x
x
x w w
H1P
H2P
H3P
H4P
H5P
H6P
H7P
c c c x w x w
H1P
H2P
H3P
H4P
H5P
H6P
H7P
w c
*
*
*
*
*
When a malfunction occurs, check the display of the
remote controller and refer to
"4 Remote controller
malfunction code display" on page 24
.
H1P
H2P
H3P
H4P
H5P
H6P
H7P
w c c w w w w
H1P
H2P
H3P
H4P
H5P
H6P
H7P
Out of outdoor
temperture range
w c c c w x
x
Out of indoor
temperture range
w c c c x w x
BS4 TEST
BS4 TEST
BS4 TEST
BS1 MODE
H1P
H2P
H3P
H4P
H5P
H6P
H7P
w c c w w w w
H1P
H2P
H3P
H4P
H5P
H6P
H7P
x
x w x
x
x
x
H1P
H2P
H3P
H4P
H5P
H6P
H7P
w w w w w w w
BS1 MODE
BS1 MODE
BS4 TEST
BS4 TEST