SiEN34-705
Installation
General Information
67
Ceiling
Suspended
Cassette Type
(FXUQ-MA)
Drain Piping Work
1. Rig drain piping (Refer to Fig. 26)
As for drain work, perform piping in such a manner that water can be drained properly.
As for drain piping, the connection can be made from three different directions.
!
Employ a pipe with either the same diameter or with the diameter larger (excluding the
raising section) than that of the connecting pipe (PVC pipe, nominal diameter 20 mm,
outside diameter 26 mm).
!
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent
air pockets from forming.
(Refer to Fig. 27)
Caution
Water pooling in the drainage piping can cause the drain to clog.
!
To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m.
(Refer to Fig. 26)
!
Use only the included drain hose (1), (for rightward running drain hose) or elbow (10) (for
upward running drain hose) and clamp (2).
!
Fit the drain hose (1) or elbow (10) over the drain pipe up to the neck and fasten tight with
the clamp (2).
!
Insulate the clamp (2) and drain hose or elbow (10) with the included sealing pad (8).
(Refer to Fig. 28)
!
Make sure that heat insulation work is executed on the following 2 spots to prevent any
possible water leakage due to dew condensation.
!
Insulate the drain hose inside the building.
!
Drain socket
Caution
!
Do not twist or bend the drain hose (1), so that excessive force is not applied to it, as this
could cause leaks.
!
If converging multiple drain piping, install according to the procedure shown below.
(Refer to Fig. 29)
Select converging drain piping whose gauge is suitable for the operating capacity of the unit.
1 - 1.5 m
VP20
VP20
500
Elbow (10)
Drain piping
(field supplied)
Drain hose (1) (For VP20 connection)
(Accessory)
Ceiling slab
Hanger
bracket
Large sealing pad (8) (accessory)
Clamp (2) (accessory)
Notes on upward running drain hose
Fig. 26
Rearward running piping
Min. 1/100 gradient
Rightward running drain hose
GOOD
WRONG
Fig. 27
(V2327)
Fig. 28
Short end
Long
end
Metal clamp (2) (accessory)
Metal clamp (2) (accessory)
Large sealing pad (8) (accessory)
Elbow (10) (accessory)
Drain hose (1)
(accessory)
Large sealing pad (8)
(accessory)
Upward
running
piping
Metal clamp (2)
(accessory)
Elbow (10)
(accessory)
Large sealing pad (8) (accessory)
Large
sealing pad (8)
(accessory)
Metal clamp (2)
(accessor
Metal clamp (2)
(accessory)
Tape
Drain hose (1)
(accessory)
≤
4mm
≥
100mm
T-joint converging drain piping
Fig. 29