8 Finishing the outdoor unit installation

Installation manual

12

(A)RXP20~35N5V1B

R32 split series

3P650253-10H – 2022.10

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

7.1

Specifications of standard wiring
components

NOTICE

We recommend using solid (single-core) wires. If stranded
wires are used, twist the conductor to consolidate the end
or  twist  the  conductor  to  consolidate  the  end  in
combination with the usage of a round crimp-style terminal
on  the  end  of  the  conductor.  Details  are  described  in
"Guidelines  when  connecting  the  electrical  wiring"  in  the
installer reference guide.

Component

Power supply cable Voltage

220~240 V

Phase

1~

Frequency

50 Hz

Wire sizes

MUST comply with

applicable legislation

Interconnection cable
(indoor↔outdoor)

4-core cable ≥1.5 mm² and

applicable for 220~240 V

Recommended field fuse

16 A

Earth leakage circuit breaker

MUST comply with

applicable legislation

7.2

To connect the electrical wiring to
the outdoor unit

1

Remove the service cover.

2

Open the wire clamp.

3

Connect the interconnection cable and power supply as follows:

f

50 Hz

220-240 V

a

b

c

d

e

a

Interconnection cable

b

Power supply cable

c

Circuit breaker

d

Residual current device

e

Power supply

f

Earth

4

Tighten  the  terminal  screws  securely.  We  recommend  using  a
Phillips screwdriver.

8

Finishing the outdoor unit
installation

8.1

To finish the outdoor unit
installation

1

Insulate and fix the refrigerant piping and cables as follows:

g

b

a

f

e

c

d

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Field wiring (if applicable)

e

Liquid pipe

f

Liquid pipe insulation

g

Finishing tape

2

Install the service cover.

8.2

To close the outdoor unit

NOTICE

When  closing  the  outdoor  unit  cover,  make  sure  that  the
tightening torque does NOT exceed 1.3 N•m.

2

1

1

9

Commissioning

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

9.1

Checklist before commissioning

1

After the installation of the unit, check the items listed below.

2

Close the unit.

Содержание RXP20N5V1B

Страница 1: ...Installation manual R32 split series English Installation manual R32 split series RXP20N5V1B RXP25N5V1B RXP35N5V1B ARXP20N5V1B ARXP25N5V1B ARXP35N5V1B...

Страница 2: ...sploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi z...

Страница 3: ...accordance with our instructions as amended S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 S I 2008 1597 Supply of Machinery Sa...

Страница 4: ...cal data 14 12 1 Wiring diagram 14 12 1 1 Unified wiring diagram legend 14 12 2 Piping diagram 16 12 2 1 Piping diagram Outdoor unit 16 1 About the documentation 1 1 About this document WARNING Make s...

Страница 5: ...n This will cause abnormal pressure in the refrigeration cycle which may result in equipment damage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Us...

Страница 6: ...l insulation as such pipes will be very hot DANGER RISK OF ELECTROCUTION All electrical parts including thermistors are powered by the power supply Do NOT touch them with bare hands DANGER RISK OF ELE...

Страница 7: ...installation servicing maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons 4 1 1 Installation site requirements of t...

Страница 8: ...a 100 mm above expected level of snow 4 2 2 To install the outdoor unit 4 M8 M10 4 2 3 To provide drainage NOTICE If the unit is installed in a cold climate take adequate measures so that the evacuat...

Страница 9: ...sure the outdoor and indoor unit are mounted Typical workflow Connecting the refrigerant piping involves Connecting the refrigerant piping to the indoor unit Connecting the refrigerant piping to the...

Страница 10: ...harging additional refrigerant make sure the outdoor unit s external refrigerant piping is checked leak test vacuum drying INFORMATION Depending on the units and or the installation conditions it migh...

Страница 11: ...ying 1 Connect the refrigerant cylinder to the service port 2 Charge the additional refrigerant amount 3 Open the gas stop valve 6 6 To fix the fluorinated greenhouse gases label 1 Fill in the label a...

Страница 12: ...220 240 V Recommended field fuse 16 A Earth leakage circuit breaker MUST comply with applicable legislation 7 2 To connect the electrical wiring to the outdoor unit 1 Remove the service cover 2 Open...

Страница 13: ...run is finished set the temperature to a normal level In cooling mode 26 28 C in heating mode 20 24 C 3 The system stops operating 3 minutes after the unit is turned OFF INFORMATION Even if the unit i...

Страница 14: ...tor D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting diode S...

Страница 15: ...llation manual 15 A RXP20 35N5V1B R32 split series 3P650253 10H 2022 10 Symbol Meaning X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferrite co...

Страница 16: ...T 7 0CuT 9 5CuT M 6 4CuT 6 4CuT 4 8CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT Propeller fan 9 5CuT 9 5CuT 7 0CuT g2 g1 f f c a b d j l k g3 i e RXP20N RXP25N ARXP20N ARXP25N h 7 0CuT 7 0CuT...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P650253 10H 2022 10 Copyright 2...

Отзывы: