Si341211
Procedure to Remove Electronic Expansion Valve and Peripheral Equipment
Removal Procedure
15
5. Procedure to Remove Electronic Expansion Valve
and Peripheral Equipment
Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work..
Step
Procedure
Points
1
Pull out the coils of
electronic expansion
valve (2 places).
2
Remove the pressure
sensors (2 places).
When removing the sensor,
be sure to use 2 spanners as
the left figure shows.
The pressure sensor is
equipped with a gauge joint
having a check valve.
Therefore, when loosing the
fixing nut of sensor, a
refrigerant leak is stopped.
Coil of main
electronic
expansion
valve (Y1E)
Coil of
subcooling
electronic
expansion
valve (Y3E)