Si34-603
Test Operation
Test Operation
75
1.1.3
Check Operation
* During check operation, mount front panel to avoid the misjudging.
* Check operation is mandatory for normal unit operation.
(When the check operation is not executed, alarm code "U3" will be displayed.)
On completion of test operation, LED on outdoor unit PC board displays the following.
H3P ON: Normal completion
H2P and H3P ON: Abnormal completion
→
Check the indoor unit remote controller for
abnormal display and correct it.
Malfunction code
In case of an alarm code displayed on remote controller:
Check on operation
(V3057)
Press and hold the TEST
OPERATION button (BS4) on
outdoor unit PC board for 5
seconds.
¡
The test operation is started automatically.
The following judgements are conducted within 15 minutes(about 30
minutes at the maximum).
2
“Check for wrong wiring”
2
“Check stop valve for not open”
2
“Pipe length automatic judgement”
The following indications are conducted while in test operation.
2
LED lamp on outdoor unit PC board H2P flickers (test operation)
2
Remote controller Indicates “UNDER CENTRALIZED CONTROL”
on upper right.
Indicates “TEST OPERATION” on lower left.
Malfunction
code
Nonconformity during installation
Remedial action
E3
The shutoff valve of an outdoor unit is left
closed.
Open the gas-side shutoff valve and the liquid-side shutoff valve.
Refrigerant overcharge.
Recalculate the required amount of refrigerant from the piping
length and correct the refrigerant charge level by recovering any
excessive refrigerant with a refrigerant recovery machine.
E4
The shutoff valve of an outdoor unit is left
closed.
Open the gas-side shutoff valve and the liquid-side shutoff valve.
Insufficient refrigerant.
Check if the additional refrigerant charge has been finished
correctly.
Recalculate the required amount of refrigerant from the piping
length and add an adequate amount of refrigerant.
F3
Refrigerant overcharge.
Recalculate the required amount of refrigerant from the piping
length and correct the refrigerant charge level by recovering any
excessive refrigerant with a refrigerant recovery machine.
The shutoff valve of an outdoor unit is left
closed.
Open the gas-side shutoff valve and the liquid-side shutoff valve.
Insufficient refrigerant.
Check if the additional refrigerant charge has been finished
correctly.
Recalculate the required amount of refrigerant from the piping
length and add an adequate amount of refrigerant.
F6
Refrigerant overcharge
Recalculate the required amount of refrigerant from the piping
length and correct the refrigerant charge level by recovering any
excessive refrigerant with a refrigerant recovery machine.
U2
Insufficient supply voltage
Check to see if the supply voltage is supplied properly.
U3
If a check operation has not been
performed.
Perform a check operation.
U4
No power is supplied to an outdoor unit.
Turn the power on for the outdoor unit.
UA
If no dedicated indoor unit is being used.
Check the indoor unit. If it is not a dedicated unit, replace the
indoor unit.
UF
The shutoff valve of an outdoor unit is left
closed.
Open the gas-side shutoff valve and the liquid-side shutoff valve.
If the right indoor unit piping and wiring are
not properly connected to the outdoor unit.
Make sure that the right indoor unit piping and wiring are properly
connected to the outdoor unit.
UH
If the interunit wiring has not be connected
or it has shorted.
Make sure the interunit wiring is correctly attached to terminals
(X2M) F1/F2 (TO IN/D UNIT) on the outdoor unit circuit board.
Содержание RXMQ4 5 6PVE
Страница 11: ...Introduction Si34 603 x...
Страница 16: ...Si34 603 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 10...
Страница 45: ...Specifications Si34 603 34 Specifications...
Страница 56: ...Si34 603 Refrigerant Circuit Refrigerant Circuit 45 C 3D052627A A P G N M D D O H F S E T...
Страница 121: ...Field Setting Si34 603 110 Test Operation...
Страница 217: ...Piping Diagrams Si34 603 206 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RX Y MQ4 5 6PVE 3D052628...
Страница 220: ...Si34 603 Piping Diagrams Appendix 209 FXUQ BEVQ Indoor Unit Connection Unit 4D037995F 4D034127B...
Страница 221: ...Wiring Diagrams Si34 603 210 Appendix 2 Wiring Diagrams 2 1 Outdoor Unit 2 1 1 Heat Pump RXYMQ4 5 6PVE 3D051730D...
Страница 222: ...Si34 603 Wiring Diagrams Appendix 211 2 1 2 Cooling Only RXMQ4 5 6PVE 3D051731C...
Страница 223: ...Wiring Diagrams Si34 603 212 Appendix 2 2 Field Wiring RX Y MQ4 5 6PVE 3D052597...
Страница 224: ...Si34 603 Wiring Diagrams Appendix 213 2 3 Indoor Unit FXCQ20M 25M 32M 63MVE 3D039556A...
Страница 225: ...Wiring Diagrams Si34 603 214 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Страница 226: ...Si34 603 Wiring Diagrams Appendix 215 FXFQ25M 32M 40M 50M 63M 80M 100M 125MVE 3D039600A...
Страница 227: ...Wiring Diagrams Si34 603 216 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Страница 228: ...Si34 603 Wiring Diagrams Appendix 217 FXDQ20P 25P 32P FXDQ20NA 25NA 32NA 40NA 50NA 63NAVE with Drain Pump 3D045500C...
Страница 229: ...Wiring Diagrams Si34 603 218 Appendix FXDQ20P 25P 32P FXDQ20N 25N 32N 40N 50N 63NAVET without Drain Pump 3D049604A...
Страница 230: ...Si34 603 Wiring Diagrams Appendix 219 FXSQ20M 25M 32M 40M 50M 63M 80M 100M 125MVE 3D039561A...
Страница 231: ...Wiring Diagrams Si34 603 220 Appendix FXMQ40MA 50MA 63MA 80MA 100MA 125MAVE 3D039620B...
Страница 232: ...Si34 603 Wiring Diagrams Appendix 221 FXHQ32MA 63MA 100MAVE 3D039801D...
Страница 233: ...Wiring Diagrams Si34 603 222 Appendix FXAQ20MA 25MA 32MAVE 40MA 50MA 63MAVE 3D034206C...
Страница 234: ...Si34 603 Wiring Diagrams Appendix 223 FXLQ20MA 25MA 32MA 40MA 50MA 63MAVE FXNQ20MA 25MA 32MA 40MA 50MA 63MAVE 3D039826D...
Страница 235: ...Wiring Diagrams Si34 603 224 Appendix FXUQ71MA 100MA 125MAV1 3D044973A...
Страница 236: ...Si34 603 Wiring Diagrams Appendix 225 BEVQ71MA 100MA 125MAVE 3D044901B...
Страница 241: ...Example of Connection Si34 603 230 Appendix...
Страница 247: ...Method of Replacing the Inverter s Power Transistors Modules Si34 603 236 Appendix...
Страница 262: ...Service Manual R 410A RX Y MQ4 5 6PVE Si34 603 Printed in Japan 07 2006 AK July...