Si34-603
Field Setting
Test Operation
95
a. “Setting mode 1”
This mode is used to set and check the following items.
1. Set items ············ In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
• COOL/HEAT selection (IND) ·····················Used to select COOL or HEAT by individual outdoor
unit (factory set).
• COOL/HEAT selection (MASTER) ············Used to select COOL or HEAT by outdoor unit group
with the master unit.
• COOL/HEAT selection (SLAVE)················Used to select COOL or HEAT by outdoor unit group
with the slave unit.
2. Check items ······· The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
Procedure for changing COOL/HEAT selection setting
Push the SET (BS2) button to set
the blinking of LED to any of
conditions shown on the right.
Push the RETURN (BS3) button to
determine the setting.
The system is normally set to "Setting
mode 1".
Should the system be set to any
mode other than that, push the
MODE (BS1) button to set the
system to "Setting mode 1".
“Normally, “Setting mode 1” is set.
In case of other status, push MODE
(BS1) button one time and set to
“Setting mode 1”.
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
Pushing the RETURN (BS3) button
will bring the system to the initial
state of "Setting mode 1".
7
7
7
7
7
7
9
7
7
7
9
7
7
7
9
7
7
7
7
7
7
8
ON
7
OFF
9
Blink
Procedure for checking check items
(V2763)
MODE
H1P
TEST
H2P
COOL/HEAT select
IND
H3P
MASTER
H4P
SLAVE
H5P
Low
noise
H6P
Demand
H7P
7
7
8
7
7
7
7
Setting (displaying) item
MODE
H1P
TEST
H2P
COOL/HEAT select
IND
H3P
MASTER
H4P
SLAVE
H5P
Low
noise
H6P
Demand
H7P
For selection by individual outdoor unit (factory set)
For selection in a batch of outdoor unit group with master unit
For selection in a batch of outdoor unit group with slave unit
Pushing the RETURN (BS3) button will return the system to the initial condition of
"Setting mode 1".
Current operating conditions
7
Normal
8
Abnormal
9
In preparation or in
check operation
Setting of COO/HEAT selection
877
By individual outdoor
unit
787
In a batch of outdoor unit
group with master unit
778
In a batch of outdoor unit
group with slave unit
Low noise operating conditions
7
In normal operation
8
In low noise operation
Demand operating conditions
7
In normal operation
8
In demand operation
Содержание RXMQ4 5 6PVE
Страница 11: ...Introduction Si34 603 x...
Страница 16: ...Si34 603 Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Units 10...
Страница 45: ...Specifications Si34 603 34 Specifications...
Страница 56: ...Si34 603 Refrigerant Circuit Refrigerant Circuit 45 C 3D052627A A P G N M D D O H F S E T...
Страница 121: ...Field Setting Si34 603 110 Test Operation...
Страница 217: ...Piping Diagrams Si34 603 206 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RX Y MQ4 5 6PVE 3D052628...
Страница 220: ...Si34 603 Piping Diagrams Appendix 209 FXUQ BEVQ Indoor Unit Connection Unit 4D037995F 4D034127B...
Страница 221: ...Wiring Diagrams Si34 603 210 Appendix 2 Wiring Diagrams 2 1 Outdoor Unit 2 1 1 Heat Pump RXYMQ4 5 6PVE 3D051730D...
Страница 222: ...Si34 603 Wiring Diagrams Appendix 211 2 1 2 Cooling Only RXMQ4 5 6PVE 3D051731C...
Страница 223: ...Wiring Diagrams Si34 603 212 Appendix 2 2 Field Wiring RX Y MQ4 5 6PVE 3D052597...
Страница 224: ...Si34 603 Wiring Diagrams Appendix 213 2 3 Indoor Unit FXCQ20M 25M 32M 63MVE 3D039556A...
Страница 225: ...Wiring Diagrams Si34 603 214 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Страница 226: ...Si34 603 Wiring Diagrams Appendix 215 FXFQ25M 32M 40M 50M 63M 80M 100M 125MVE 3D039600A...
Страница 227: ...Wiring Diagrams Si34 603 216 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Страница 228: ...Si34 603 Wiring Diagrams Appendix 217 FXDQ20P 25P 32P FXDQ20NA 25NA 32NA 40NA 50NA 63NAVE with Drain Pump 3D045500C...
Страница 229: ...Wiring Diagrams Si34 603 218 Appendix FXDQ20P 25P 32P FXDQ20N 25N 32N 40N 50N 63NAVET without Drain Pump 3D049604A...
Страница 230: ...Si34 603 Wiring Diagrams Appendix 219 FXSQ20M 25M 32M 40M 50M 63M 80M 100M 125MVE 3D039561A...
Страница 231: ...Wiring Diagrams Si34 603 220 Appendix FXMQ40MA 50MA 63MA 80MA 100MA 125MAVE 3D039620B...
Страница 232: ...Si34 603 Wiring Diagrams Appendix 221 FXHQ32MA 63MA 100MAVE 3D039801D...
Страница 233: ...Wiring Diagrams Si34 603 222 Appendix FXAQ20MA 25MA 32MAVE 40MA 50MA 63MAVE 3D034206C...
Страница 234: ...Si34 603 Wiring Diagrams Appendix 223 FXLQ20MA 25MA 32MA 40MA 50MA 63MAVE FXNQ20MA 25MA 32MA 40MA 50MA 63MAVE 3D039826D...
Страница 235: ...Wiring Diagrams Si34 603 224 Appendix FXUQ71MA 100MA 125MAV1 3D044973A...
Страница 236: ...Si34 603 Wiring Diagrams Appendix 225 BEVQ71MA 100MA 125MAVE 3D044901B...
Страница 241: ...Example of Connection Si34 603 230 Appendix...
Страница 247: ...Method of Replacing the Inverter s Power Transistors Modules Si34 603 236 Appendix...
Страница 262: ...Service Manual R 410A RX Y MQ4 5 6PVE Si34 603 Printed in Japan 07 2006 AK July...