English

10

Facility Setting
(cooling at low outdoor temperature)

This function is designed for facilities such as equipment or computer rooms. It is never to be used in 
a residence or office where people occupy the space.

Cutting jumper 6 (J6) on the circuit board will expand the operation range down to –15°C. However it will stop if the outdoor 
temperature drops below –18°C and start back up once the temperature rises again.
1) Remove the 3 screws on the side and remove the top plate of the outdoor unit.
2) Remove the drip proof cover.
3) Cut the jumper (J6) of the PCB inside.

 CAUTION

• If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
• Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
• Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used.

A humidifier might cause dew condensation from the indoor unit outlet vent.

• Cutting jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.

Wiring

 WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical 

shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Be sure to install an earth leak detector. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that it must be used an earth leak detector capable handling harmonics in order to 
prevent malfunctioning of the earth leak detector itself.)

• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Equipment complying with EN/IEC 61000-3-12

(1)

• Do not turn ON the safety breaker until all work is 

completed.

1) Strip the insulation from the wire (20mm).
2) Connect the inter-unit wire between the 

indoor and outdoor units 

so that the 

terminal numbers match

. Tighten the 

terminal screws securely. We recommend a 
flathead screwdriver be used to tighten the 
screws. 

(1)

European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-

voltage systems with input current >16 A and 

75 A per phase.

Top plate

PCB

2) Remove the drip 

proof cover.

1) Remove the 

3 screws.

3) Cut jumper J6.

Drip proof cover

RX-42

10A

RX-50

15A

Safety 
breaker

Earth leakage 
circuit breaker

Earth

Inter-unit wire 
4-core 1.5mm² or more 
H05RN

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power 
supply
50Hz 220-240V 

Firmly fix the wires with 
the terminal screws.

Power supply wire 
3-core 2.5mm² or more
H05RN

Содержание RXM42LV1B

Страница 1: ...n S rie split R32 Fran ais Montagehandleiding R32 Split systeem Nederlands Manual de instalaci n Serie Split R32 Espa ol Manuale d installazione Serie Multiambienti R32 Italiano R32 Manual de Instala...

Страница 2: ...amente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B d...

Страница 3: ...A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o...

Страница 4: ...ion lead as this may cause overheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improp...

Страница 5: ...E Cannot be installed hanging from ceiling or stacked CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In the event of a gas leakage build up of...

Страница 6: ...on side facing the wall Never install the outdoor unit at a site where the suction side may be exposed directly to wind To prevent exposure to wind it is recommended to install a baffle plate on the a...

Страница 7: ...tres From unit s side Max allowable piping height Min allowable piping length Max allowable piping length 30m 1 5m 20m Liquid pipe Gas pipe O D 6 4mm O D 12 7mm 20g m Additional refrigerant required f...

Страница 8: ...e foundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2...

Страница 9: ...que wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully...

Страница 10: ...h 4 1 Connect projection side of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressu...

Страница 11: ...arate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 12 7mm O D 6 4mm I D 14 16mm I D 8 10mm Minimum bend r...

Страница 12: ...d 15 minutes To stop the operation press the indoor unit ON OFF switch Using the indoor unit s remote controller 1 Press MODE button and select the cooling mode 2 Press ON OFF button to turn on the sy...

Страница 13: ...e the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Be sure to install an earth leak detector One that can handle higher harm...

Страница 14: ...imp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place 3 Pull the wire and make sure that it...

Страница 15: ...RMISTOR DS DIPSWITCH RC RECEIVER E H HEATER S C LIMITSWITCH F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S L FLOATSWITCH FG CONNECTOR FRAMEGROUND S NPH PRESSURESENSOR HIGH H HARNESS S NPL P...

Страница 16: ...air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consum...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...3P386698 1C 2015 07 Copyright 2014 Daikin...

Отзывы: