Outdoor Unit Installation

5.

Purging air and checking gas leakage

• When piping work is completed, it is necessary to purge the air and check for gas leakage.

 WARNING

• Do not mix any substance other than the specified refrigerant (R32) into the refrigeration cycle.
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
• R32, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• Use a vacuum pump for R32 or R410A exclusively. Using the same vacuum pump for different refrigerants may damage the 

vacuum pump or the unit.

• Use tools for R32 or R410A (such as the gauge manifold, charging hose, or vacuum pump adapter.)

• If using additional refrigerant, perform air purging from the refrigerant pipes 

and indoor unit using a vacuum pump, then charge additional refrigerant.

• Use a hexagonal wrench (4mm) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified 

tightening torque.

*1. Pipe length vs. vacuum pump run time.  

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists.  

Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.

2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).  

(High-pressure valve subsequently requires no operation.)

3)  Do vacuum pumping and make sure that the compound pressure gauge reads –0.1MPa (–76cmHg).*1

4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.  

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2

5) Remove caps from liquid stop valve and gas stop valve.

6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve. 

Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.  
After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.

(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

Pipe length

Up to 15m

More than 15m

Run time

Not less than 10 min.

Not less than 15 min.

Gauge 
manifold

Compound 
pressure gauge

Pressure metre

Low-pressure 
valve

High-pressure 
valve 

Charging 
hoses

Vacuum pump

Valve caps

Service port

Liquid 
stop 
valve

Gas 
stop 
valve

Содержание RXM42LV1B

Страница 1: ...n S rie split R32 Fran ais Montagehandleiding R32 Split systeem Nederlands Manual de instalaci n Serie Split R32 Espa ol Manuale d installazione Serie Multiambienti R32 Italiano R32 Manual de Instala...

Страница 2: ...amente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B d...

Страница 3: ...A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o...

Страница 4: ...ion lead as this may cause overheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improp...

Страница 5: ...E Cannot be installed hanging from ceiling or stacked CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In the event of a gas leakage build up of...

Страница 6: ...on side facing the wall Never install the outdoor unit at a site where the suction side may be exposed directly to wind To prevent exposure to wind it is recommended to install a baffle plate on the a...

Страница 7: ...tres From unit s side Max allowable piping height Min allowable piping length Max allowable piping length 30m 1 5m 20m Liquid pipe Gas pipe O D 6 4mm O D 12 7mm 20g m Additional refrigerant required f...

Страница 8: ...e foundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2...

Страница 9: ...que wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully...

Страница 10: ...h 4 1 Connect projection side of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressu...

Страница 11: ...arate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 12 7mm O D 6 4mm I D 14 16mm I D 8 10mm Minimum bend r...

Страница 12: ...d 15 minutes To stop the operation press the indoor unit ON OFF switch Using the indoor unit s remote controller 1 Press MODE button and select the cooling mode 2 Press ON OFF button to turn on the sy...

Страница 13: ...e the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Be sure to install an earth leak detector One that can handle higher harm...

Страница 14: ...imp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place 3 Pull the wire and make sure that it...

Страница 15: ...RMISTOR DS DIPSWITCH RC RECEIVER E H HEATER S C LIMITSWITCH F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S L FLOATSWITCH FG CONNECTOR FRAMEGROUND S NPH PRESSURESENSOR HIGH H HARNESS S NPL P...

Страница 16: ...air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consum...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...3P386698 1C 2015 07 Copyright 2014 Daikin...

Отзывы: