background image

5 Piping installation

Installation manual

8

RXJ42+50A

R32 split series

3P512025-12X – 2021.12

353

600

240

(mm)

240

a

a

100 mm above expected level of snow

4.2.2

To install the outdoor unit

4× M8/M10

4.2.3

To provide drainage

NOTICE

If  the  unit  is  installed  in  a  cold  climate,  take  adequate
measures  so  that  the  evacuated  condensate  CANNOT
freeze.

NOTICE

If  the  drain  holes  of  the  outdoor  unit  are  blocked  up  by  a
mounting base or floor surface, place additional foot bases
≤30 mm under the outdoor unit's feet.

INFORMATION

For  information  on  the  available  options,  contact  your
dealer.

1

Use a drain plug for drainage.

2

Use a Ø16 mm hose (field supply).

b

c

d

a

a

Drain port

b

Bottom frame

c

Drain plug

d

Hose (field supply)

To close the drain holes and attach the drain
socket

NOTICE

In cold areas, do NOT use a drain socket, hose and caps
(1,  2)  with  the  outdoor  unit.  Take  adequate  measures  so
that the evacuated condensate CANNOT freeze.

1

Install drain caps 1 and 2 (accessory). Make sure the edges of
the drain caps close off the holes completely.

a

b

a

Bottom frame

b

Drain cap

2

Install the drain socket.

a

c

b

b

b

a

a

a

Drain hole. Install a drain cap (2).

b

Drain hole. Install a drain cap (1).

c

Drain hole for drain socket

5

Piping installation

5.1

Preparing refrigerant piping

5.1.1

Refrigerant piping requirements

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Pipe outer diameter (mm)

Liquid piping

Gas piping

Ø6.4

Ø12.7

Refrigerant piping material

Piping material:

 Phosphoric acid deoxidised seamless copper.

Содержание RXJ42A2V1B

Страница 1: ...Installation manual R32 split series English Installation manual R32 split series RXJ42A2V1B RXJ50A2V1B...

Страница 2: ...sina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele resp...

Страница 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Страница 4: ...14 14 2 Piping diagram 15 14 2 1 Piping diagram Outdoor unit 15 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask him her to k...

Страница 5: ...the formation of a harmful gas Turn OFF any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT use the unit until a service person confirms that...

Страница 6: ...is rotating at high speed it will cause injury Maintenance and service see 11 Maintenance and service 413 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING WARNING Before carrying out any m...

Страница 7: ...igned for outdoor installation only and for ambient temperatures specified in the table below unless otherwise specified in the operation manual of the connected indoor unit Cooling Heating 10 50 C DB...

Страница 8: ...asures so that the evacuated condensate CANNOT freeze 1 Install drain caps 1 and 2 accessory Make sure the edges of the drain caps close off the holes completely a b a Bottom frame b Drain cap 2 Insta...

Страница 9: ...2 1 To connect the refrigerant piping to the outdoor unit Piping length Keep field piping as short as possible Piping protection Protect the field piping against physical damage WARNING Connect the r...

Страница 10: ...er than those recommended by the manufacturer Be aware that the refrigerant inside the system is odourless WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the...

Страница 11: ...y the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire...

Страница 12: ...t the facility mode When cutting jumper J6 on the PCB the operation range will expand to 15 C The facility mode will stop if the outdoor temperature drops below 20 C and resume when the temperature ri...

Страница 13: ...e temperature In heating mode select the highest programmable temperature Test run can be disabled if necessary 2 When the test run is finished set the temperature to a normal level In cooling mode 26...

Страница 14: ...circuit connector Fuse Terminal INDOOR Indoor unit Terminal strip OUTDOOR Outdoor unit Wire clamp Residual current device Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink BRN Brown...

Страница 15: ...solenoid valve coil Z C Ferrite core ZF Z F Noise filter 14 2 Piping diagram 14 2 1 Piping diagram Outdoor unit PED categories of equipment High pressure switch category IV Compressor category II Othe...

Страница 16: ...3P512025 12X 2021 12 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Отзывы: