Installation manual

R32 split series

English

Installation manual

R32 split series

RXA20A2V1B
RXA25A2V1B
RXA35A2V1B

Содержание RXA20A2V1B

Страница 1: ...Installation manual R32 split series English Installation manual R32 split series RXA20A2V1B RXA25A2V1B RXA35A2V1B...

Страница 2: ...s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standa...

Страница 3: ...klist before commissioning 10 5 2 Checklist during commissioning 10 5 3 To perform a test run 10 6 Configuration 10 6 1 To set the facility mode 10 7 Troubleshooting 11 7 1 Fault diagnosis using LED o...

Страница 4: ...he air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet Do NOT install the unit in sound sensitive areas e g near a bedroom so...

Страница 5: ...fference 15 m 3 2 3 Refrigerant piping insulation Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 12 15 mm i i t p p If the temperature is...

Страница 6: ...outdoor unit from falling over In case the unit is installed in places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field su...

Страница 7: ...with nitrogen gas up to a gauge pressure of at least 200 kPa 2 bar It is recommended to pressurize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test solut...

Страница 8: ...4 4 3 To determine the additional refrigerant amount If the total liquid piping length is Then 10 m Do NOT add additional refrigerant If the total liquid piping length is Then 10 m R total length m o...

Страница 9: ...ELECTROCUTION All electrical parts including thermistors are powered by the power supply Do not touch them with bare hands DC DC g h b c d e f a a Multimeter DC voltage range b S70 fan motor lead wire...

Страница 10: ...etween the outdoor unit and the indoor unit Drainage Make sure drainage flows smoothly Possible consequence Condensate water might drip The indoor unit receives the signals of the user interface The s...