Wiring
WARNING
• Do not ground units to water pipes, gas pipes, telephone wires, or lightning rods as incomplete grounding can cause a
severe shock hazard resulting in severe injury or death.
Additionally, grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death.
•
Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electric shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• The circuit must be protected with safety devices in accordance with local and national codes, i.e. a circuit breaker.
• Use an all-pole disconnection type circuit breaker with at least 1/8 inch (3mm) between the contact point gaps.
• When carrying out wiring, take care not to pull at the conduit.
•
Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.
CAUTION
Precautions to be taken for power supply wiring
• When using stranded wires, make sure to use the round crimp-style
terminal for connection to the power supply terminal block.
Stranded wire
Round crimp-style
terminal
Arrow view
Flat washer
Screw
Round
crimp-style
terminal
Good
Round crimp-
style terminal
Flat washer
Screw
Wrong
Flat washer
Round crimp-
style terminal
Screw
A
A
• When connecting the inter-unit wires to the terminal block using a single core wire, be sure to curl the end of the lead.
Improper work may cause heat and fire.
Strip wire end
to this point.
Excessive strip length
may cause electric shock
or current leakage.
Stripping wire at terminal block
Good
Wrong
Good
Wrong
• Do not turn on the circuit breaker until all work is completed.
1) Strip the insulation from the wire (3/4 inch (20mm)).
2) Connect the inter-unit wires between the indoor and outdoor units so that the terminal numbers match. Tighten the
terminal screws securely. It is recommended that a slot-head screwdriver be used to tighten the screws.
1
2
3
1 2 3
Ground
Outdoor unit
Indoor
unit
Power supply
60Hz 208-230V
15A
Firmly fix the
wires with the
terminal screws.
Firmly fix the wires with the te
rminal screws.
L
1
L
2
Follow local codes for wiring
and safety devices between
outdoor unit and power source.
Recommend using AWG14, stranded and
insulated wire for connections between indoor and
outdoor units.
Local code always supersedes recommendation.
NOTE
Take care to ensure that all wiring between indoor unit and outdoor unit has a consistent connection. Any splices can cause
communication errors.