EDUS30-900-R
Geothermal Operation Limits
RWEYQ-P Water Cooled Inverter Series
57
11. Geothermal Operation Limits
Notes:
1. This figure shows the allowable operation range when the water volume is 21~40 gal/min (80~150 liter/min).
2. When the cooling load is small, the indoor unit may initiate thermostat-off for freeze protection;
this is only for a limited period of time.
3. Hold ambient conditions at 35~95°F (1.6~35°C)~80%RH.
4. During heat recovery operation, if the system is heating-dominant, the heating limits may be used and if
the system is cooling-dominant, the cooling limits may be used. It is highly recommended to consult your
local Daikin representative for design assistance.
5. In heating operation a minimum of 30% ethylene glycol is required when operating at an EWT of
50~23°F (10~
5°C) and 40% when operating between 23~14°F (
5 ~
10°C).
Range for continuous operation:
59 68 77 86
Indoor temperature (ºFWB)
50 59 68 77 86
Indoor temperature (ºFDB)
113
104
95
86
77
68
59
50
41
32
23
14
113
104
95
86
77
68
59
50
41
32
23
14
Inlet w
ater temper
ature (°F)
Inlet w
ater temper
ature (°F)
43
Range for
operation
Содержание RWEYQ-P
Страница 1: ...EDUS 30 900 R AMERICAS AMERICAS RWEYQ P...
Страница 10: ...EDUS30 900 R Dimensions RWEYQ P Water Cooled Inverter Series 9 3 Dimensions RWEYQ72PTJU RWEYQ84PTJU 3D066053...
Страница 54: ...EDUS30 900 R Capacity Table Reference Data RWEYQ P Water Cooled Inverter Series 53 RWEYQ84 168PTJU 3D066052...
Страница 55: ...Capacity Table Reference Data EDUS30 900 R 54 RWEYQ P Water Cooled Inverter Series RWEYQ144PTJU 3D066111...