English
6
FOR SYSTEMS WITHOUT COOL/HEAT SELEC-
TOR (Refer to figure 4)
Press the operation mode selector button sev-
eral times and select the operation mode of
your choice;
“
” Cooling operation
“
” Heating operation
“
” Fan only operation
Press the on/off button.
The operation lamp lights up and the system
starts operation.
FOR SYSTEMS WITH COOL/HEAT SELECTOR
(Refer to figure 4 and 7)
Select operation mode with the Cool/Heat
selector as follows:
“
” “
” Cooling operation
(Refer to figure 7.1)
“
” “
” Heating operation
(Refer to figure 7.2)
“
”
“
”
Fan only operation
(Refer to figure 7.3)
Press the on/off button.
(Refer to figure 4)
The operation lamp lights up and the system
starts operation.
ADJUSTMENT (Refer to figure 4)
For adjustment the desired temperature, fan
speed and air flow direction (only for the
remote controller BRC1C62: FXC, FXF, FXH,
FXK, FXA), follow the procedure shown below.
Press the temperature setting button and set
the desired temperature.
Each time this button is pressed, the tem-
perature setting rises or lowers 1°C.
NOTE
• Set the temperature within the operation range.
• The temperature setting is impossible for fan
only operation.
Press the fan speed control button and select
the fan speed of your preference.
Press air flow direction adjust button.
Refer to the chapter “Adjusting the air flow
direction” for details.
STOPPING THE SYSTEM (Refer to figure 4)
Press the on/off button once again.
The operation lamp goes off and the system
stops operation.
NOTE
• Do not turn off the power immediately after
the unit stops.
• The system need at least 5 minutes for
residual operation of drain pump device.
Turning off the power immediately will cause
water leak or trouble.
EXPLANATION OF HEATING OPERATION
• For general heating operation, it may take longer to
reach the set temperature than in cooling operation.
We recommend starting the operation which was
used before using timer operation.
• The following operation is performed in order to
prevent the heating capacity from dropping or
cold air from blowing.
Defrost operation
• In heating operation, freezing of the outdoor
unit heat exchanger increases. Heating
capability decreases and the system goes
into defrost operation.
• The indoor unit fan stops and the remote
controller displays
“
”.
• After maximum 10 minutes of defrost opera-
tion, the system returns to heating operation
again.
Hot start
• In order to prevent cold air from blowing out
of an indoor unit at the start of heating oper-
ation, the indoor fan is automatically
stopped. The display of the remote controller
shows “
”.
NOTE
• The heating capacity drops as the outside tem-
perature falls. If this happens, use another heat-
ing device together with the unit. (When using the
appliances which produce open fire together, ven-
tilate a room constantly.)
Do not place appliances which produce open fire
in places exposed to the air flow from the unit or
under the unit.
• It takes some time for the room to warm up from
the time the unit is started since the unit uses a
hot-air circulatory system to warm the entire room.
• If the hot air rises to the ceiling, leaving the area
above the floor cold, we recommend using the cir-
culator (the indoor fan for circulating air). Contact
your dealer for details.
6-2 PROGRAM DRY OPERATION
• The function of this operation is to decrease
the humidity in your room with a minimum
temperature decrease.
• The micro computer automatically deter-
mines temperature and fan speed.
• The system does not go into operation if the
room temperature is low.
• The microcomputer automatically controls
the temperature and fan speed, so these
cannot be set using the remote controller.
• This function is not available if the room tem-
perature is 20°C or lower.
1
2
1
2
3
4
5
6
01_EN_3P226891-12Q.fm Page 6 Saturday, November 27, 2010 2:08 PM
Содержание RQYQ8PY1B
Страница 2: ...00_CV_3P226891 12Q fm Page 2 Saturday November 27 2010 2 07 PM...
Страница 4: ...2 1 4 3 5 6 7 1 7 3 7 2 00_CV_3P226891 12Q fm Page 4 Saturday November 27 2010 2 07 PM...
Страница 5: ...8 9 10 11 12 13 14 00_CV_3P226891 12Q fm Page 5 Saturday November 27 2010 2 07 PM...
Страница 6: ...00_CV_3P226891 12Q fm Page 6 Saturday November 27 2010 2 07 PM...
Страница 20: ...3P226891 12Q EM10A039 1012 HT 00_CV_3P226891 12Q fm Page 7 Saturday November 27 2010 2 07 PM...