background image

 

R(Y)P71~W1
Split System air conditioners
4PW14486-1B

Installation manual

 

3

 

2

 

When installing the unit in a place exposed to strong wind, pay
special attention to the following.

Strong winds of 5 m/sec or more blowing against the outdoor
unit's air outlet causes short circuit (suction of discharge air),
and this may have the following consequences:
-

Deterioration of the operational capacity.

-

Frequent frost acceleration in heating operation.

-

Disruption of operation due to rise of high pressure.

-

When a strong wind blows continuously on the face of the 
unit, the fan can start rotating very fast until it breaks.

Refer to the figures for installation of this unit in a place where
the wind direction can be foreseen.

 

 

Turn  the air outlet side toward the building's wall, fence or
screen.

 

 

Set the outlet side at a right angle to the direction of the wind.

 

3

 

Prepare a water drainage channel around the foundation, to
drain waste water from around the unit.

 

4

 

If the water drainage of the unit is not easy, please build up the
unit on a foundation of concrete blocks, etc. (the height of the
foundation should be maximum 150 mm).

 

5

 

If you install the unit on a frame, please install a waterproof plate
within 150 mm of the underside of the unit in order to prevent the
invasion of water from the lower direction.

 

6

 

When installing the unit in a place frequently exposed to snow,
pay special attention to the following:

-

Elevate the foundation as high as possible.

-

Remove the rear suction grille to prevent snow from 
accumulating on the rear fins.

7

If you install the unit on a building frame, please install a
waterproof plate (within 150 mm of the underside of the unit) in
order to avoid the drainwater dripping. (See figure).

P

RECAUTIONS

 

ON

 

INSTALLATION

Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
installation.

In accordance with the foundation drawing in the figure, fix the
unit securely by means of the foundation bolts. (Prepare four
sets of M12 foundation bolts, nuts and washers each which are
available on the market.)

It is best to screw in the foundation bolts until their length are
20 mm from the foundation surface.

Installation method for prevention of falling over

If it is necessary to prevent the unit from falling over, install as shown
in the figure.

prepare all 4 wires as indicated in the drawing

unscrew the top plate at the 4 locations indicated A and B

put the screws through the nooses and screw them back tight

A

location of the 2 fixation holes on the front side of the unit

B

location of the 2 fixation holes on the rear side of the unit

C

wires: field supply

Drain pipe disposal

If drain pipe disposal from the outdoor unit causes trouble, provide
the drain piping by using of the drain socket (optional).

Strong wind

Blown air

Strong wind

Make sure there is enough room to do the installation

Discharge side

Bottom view (mm)

Drain hole

20

140

117

219

289

350

(345-355)

47

140

620

614

423

A

B

C

C

B

A

A

Содержание RP71L7V1

Страница 1: ...INSTALLATION MANUAL RP71L7V1 RP100L7V1 RP71L7W1 RP100L7W1 RP125L7W1 RYP71L7V1 RYP100L7V1 RYP71L7W1 RYP100L7W1 RYP125L7W1 Split System air conditioners...

Страница 2: ...C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2 2 2 H1 L1 3 3 H1 H2 L3 L1 L2 4 4 H1 H2 L4 L1 L3 L2 5 5...

Страница 3: ...7 7 8 8 NOTES...

Страница 4: ...se med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standard er eller andre normgivende dokument er under forutssetning av at disse brukes i henhold til v re instrukser vast...

Страница 5: ...eakage electric shocks or fire When a unit is installed in a small room it is necessary to take measures so that the leaked refrigerant amount does not exceed the limit even if it leaks As for the mea...

Страница 6: ...d Places where the indoor and outdoor units piping and wiring lengths come within the allowable ranges Places where water leaking from the unit cannot cause damage to the location e g in case of a blo...

Страница 7: ...following Elevate the foundation as high as possible Remove the rear suction grille to prevent snow from accumulating on the rear fins 7 If you install the unit on a building frame please install a w...

Страница 8: ...tween the branch and the indoor units L2 L4 should have the same size as the indoor connections Branch see marking on figures 3 4 Suction side obstacle Obstacle is present Discharge side obstacle 1 In...

Страница 9: ...equal When using existing refrigerant piping Pay attention to the following points when using existing refrigerant piping In the following situations the existing piping should not be re used and new...

Страница 10: ...torque 19 6 24 5 N m Check for refrigerant leakage after tighten the cap Cautions for handling service port After the work tighten the valve cover in place Tightening torque 10 8 14 7 N m Precautions...

Страница 11: ...installer Confirm that the valves are firmly closed before leak test or vacuuming Set up for vacuuming and leak test see figure 7 Procedure for leak test Leak test must satisfy EN378 2 Piping size Fl...

Страница 12: ...90 kg 3 Refrigerant charge amount R R1 R2 0 0 0 9 0 9 kg Complete charging of the refrigerant after a leak etc When the entire refrigerant pipe length is within 30 meters charge the refrigerant in ac...

Страница 13: ...ure the ground wire to the shut off valve attachment plate so that it does not slide 2 Secure the ground wire to the shut off valve attachment plate one more time along with the electric wiring and th...

Страница 14: ...are open Be sure to close the frontside panel before operation as not doing so can cause electric shock The refrigerant pressure may not rise even if the shut off valve is opened after an air purge i...

Страница 15: ...l check for voltage imbalance If the error code UF is displayed on the remote contol check the inter unit branch wiring connection Diagnosis On the remote control LCD If the machine stops due to some...

Страница 16: ...PRC W1 MODEL Phase reverse circuit Q1M Q2M Thermo switch M1F M2F Q3E Earth leak detector R1T Thermistor air R2T Thermistor coil R3T Thermistor discharche R4C V1 MODEL Resistor RC Signal receiver circu...

Страница 17: ...NOTES NOTES...

Страница 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN14486 1B...

Отзывы: