SiUS181305E
Basic Control
Function
42
2. Basic Control
2.1
Normal Operation
<Cooling Operation>
<Heating Operation>
Heating operation does not start when the outdoor temperature is above 24
CDB (75.2
FDB).
2.2
Compressor PI Control
The PI control of the compressor capacity is carried out to keep Te constant during cooling
operation and Tc constant during heating operation to ensure stable unit performance.
<Cooling operation>
<Heating operation>
Actuator
Operation
Remarks
Compressor
Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with inverter
protection control.
Outdoor fan
Cooling fan control
Four-way valve (Y1S)
OFF
Main electronic expansion valve (Y1E)
480 pulse
Subcooling electronic expansion valve
(Y3E)
PI control
Hot gas bypass solenoid valve (Y2S)
OFF
This valve turns on with low pressure protection
control.
Actuator
Operation
Remarks
Compressor
Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with inverter
protection control.
Outdoor fan
STEP 7 or 8
Four-way valve (Y1S)
ON
Main electronic expansion valve (Y1E)
PI control
Subcooling electronic expansion valve
(Y3E)
PI control
Hot gas bypass solenoid valve (Y2S)
OFF
This valve turns on with low pressure protection
control.
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te: Low pressure equivalent saturation temperature
TeS: Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
Te setting (Set in setting mode 2)
L
M (Normal)
: factory setting
H
3°C
(37.4°F)
6°C
(42.8°F)
9°C
(48.2°F)
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Tc: High pressure equivalent saturation temperature
TcS: Target Tc value
(Varies depending on Tc setting, operating frequency,
etc.)
Tc setting (Set in setting mode 2)
L
M (Normal)
: factory setting
H
43°C
(109.4°F)
46°C
(114.8°F)
49°C
(120.2°F)
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...