manualshive.com logo in svg
background image

INSTALLATION 
MANUAL

R410A Split Series

Models 
RXS09JEVJU

RKS09JEVJU

RXS12JEVJU

RKS12JEVJU

RXN09JEVJU

RKN09JEVJU

RXN12JEVJU

RKN12JEVJU

English

Français

Español

Installation manual

R410A Split series

Manuel d’installation

Série split R410A

Manual de instalación

Serie Split R410A

00_CV_3P253189-4E.fm  Page 1  Monday, September 6, 2010  4:18 PM

Содержание RKN09JEVJU RXN12JEVJU RKN12JEVJU

Страница 1: ...XS12JEVJU RKS12JEVJU RXN09JEVJU RKN09JEVJU RXN12JEVJU RKN12JEVJU English Fran ais Espa ol Installation manual R410A Split series Manuel d installation S rie split R410A Manual de instalaci n Serie Spl...

Страница 2: ...t children will not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk of explos...

Страница 3: ...ead to equipment damage and personal injury Be sure to install a ground fault circuit interrupter breaker Failure to install a ground fault circuit interrupter breaker may result in electrically shock...

Страница 4: ...feet 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out o...

Страница 5: ...ired for refrigerant pipe exceeding 33ft 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced perfomance The suggested shortest pipe length i...

Страница 6: ...When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary follow the procedures below 2 Drain work Heat...

Страница 7: ...ts and gas leakage Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches A Check Flare s inner surface must be flaw free The...

Страница 8: ...anifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do...

Страница 9: ...4 to 0 030Btu fth F 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 230 F 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insula...

Страница 10: ...eration to stop press the indoor unit ON OFF button Using the main unit s remote controller 1 Press the ON OFF button Operation will start 2 Press the TEMP button and the MODE button at the same time...

Страница 11: ...before wiring A protection plate is fixed for protection from the high voltage section Before staring wiring work dismount the protection plate by removing the 2 screws and dismount the conduit mount...

Страница 12: ...s with the work may cause heat and fires 3 Pull the wire and make sure that it does not disconnect Then fix the wire in place with a wire stop Strip wire end to this point Excessive strip length may c...

Страница 13: ...tion in accordance with the operation manual to ensure that all functions and parts such as fin movement are working properly The air conditioner requires a small amount of power in its standby mode I...

Страница 14: ...1010 HT 3P253189 4E M09B111C Two dimensional barcodeisacode for manufacturing 66163045 00_CV_3P253189 4E fm Page 2 Monday September 6 2010 4 18 PM...

Отзывы: