PCB
Si001422E
10
Removal Procedure
3. PCB
Warning
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
Step
Procedure
Points
1. Remove the service
monitor PCB.
1
Peel off the filament
tape and open the
electrical box cover.
2
Disconnect the
connectors [S2], [S52],
[S102].
[S2]: demand control PCB
[S52] [S102]: main PCB
Cooling only models have no
connector for [S2].
Cooling only models have no
terminal block for smart
meter.
3
Release the harness
from the hook and
groove.
In case of cooling models,
the service monitor PCB is
fixed with clamps instead of
the hooks.
Pinch the 4 clamps and
remove the service monitor
PCB.
4
Unfasten the 2 hooks
and remove the service
monitor PCB.
Electrical box cover
Filament tape
(R21690)
[S102]
[S52]
[S2]
(R21691)
Terminal block
for smart meter
Hook
(R21692)
Clamp
(R21694)
(R21693)
Service monitor PCB
Hook
Hook