Si001658EA
Electronic Expansion Valve
Removal Procedure
17
2
Remove the terminal
cover.
3
4
Remove the protection
bushing.
Disconnect the
compressor lead wires
(U, V, W) and the
overload protector.
5
6
7
Cut the clamp.
Remove the putties.
Heat up the 2 brazed
parts and remove the
electronic expansion
valve.
Step
Procedure
Points
Terminal cover
(R23737)
Protection bushing
U (red)
Overload
protector
V (yellow)
W (blue)
(R23738)
Clamp
Electronic expansion
valve
Putty
Brazed part
(R23739)