background image

37

English

15.3.  Energy saving and optimum operation

REYQ-X units are equipped with advanced energy saving function-
ality. Depending on the priority, emphasizes can be put on energy 
saving or comfort level. Several parameters can be selected, resulting 
in the optimal balance between energy consumption and comfort for 
the particular application.

Several patterns are available and explained below. Modify the pa-
rameters to the needs of your building and to realize the best balance 
between energy consumption and comfort.

15.3.1.  Three main operation methods are available:

• 

Basic

The refrigerant temperature is fixed independent from the situation. 

It corresponds to the standard operation which is known and can be 
expected from/under previous VRV systems:

•  To activate this operation method under cooling operation:  

change field setting [2-8]=2, [2-47]=2 and [2-81]=0.

•  To activate this operation method under heating operation:  

change field setting [2-9]=6 and [2-82]=0.

• 

Automatic

The refrigerant temperature is set depending on the outdoor ambi-
ent conditions. As such adjusting the refrigerant temperature to 
match the required load (which is also related to the outdoor ambi-
ent conditions).
E.g., when your system is operating in cooling, you do not need as 
much cooling under low outdoor ambient temperatures (e.g., 77°F 

(25°C)) as under high outdoor ambient temperatures (e.g., 95°F 
(35°C)).

Using this idea, the system automatically starts increasing its refrig-
erant temperature, automatically reducing the delivered capacity 

and increasing the system’s efficiency.

•  To activate this operation method under cooling operation: 

change field setting [2-8]=0 (default) and [2-47]=0 (default).

E.g., when your system is operating in heating, you do not need as 

much heating under high outdoor ambient temperatures (e.g., 59°F 
(15°C)) as under low outdoor ambient temperatures (e.g., 23°F 
(–5°C)). 

Using this idea, the system automatically starts decreasing its re-
frigerant temperature, automatically reducing the delivered capacity 

and increasing the system’s efficiency.

•  To activate this operation method under heating operation: 

change field setting [2-9]=0 (default).

• 

Hi-sensible/economic (cooling/heating)

The refrigerant temperature is set higher/lower (cooling/heating) 
compared to basic operation. The focus under high sensible mode 
is comfort feeling for the customer.
The selection method of indoor units is important and has to be 
considered as the available capacity is not the same as under basic 
operation. For details concerning to Hi-sensible applications, please 
contact your dealer.

• 

To activate this setting under cooling operation: change field 
setting [2-8] and [2-47] to the appropriate value, matching the 

requirements of the pre-designed system containing a high 
sensible solution.

Value 

[2-8] and [2-47]

T

e

 target

3

45°F (7°C)

4

46°F (8°C)

5

48°F (9°C)

6

50°F (10°C)

7

52°F (11°C)

• 

To activate this setting under heating operation: change field 
setting [2-9] to the appropriate value, matching the require

-

ments of the pre-designed system containing a high sensible 
solution.

Value 

[2-9]

T

c

 target

1

106°F (41°C)

3

109°F (43°C)

15.3.2.  Several comfort settings are available

For each of above modes a comfort level can be selected. The comfort 
level is related to the timing and the effort (energy consumption) which 
is put in achieving a certain room temperature by temporarily chang-
ing the refrigerant temperature to different values in order to achieve 
requested conditions more quickly.

• 

Powerful

Overshoot (during heating operation) or undershoot (during cooling 
operation) is allowed compared to the requested refrigerant tem-
perature, in order to achieve the required room temperature very 
fast. The overshoot is allowed from the start up moment.
In case of cooling operation the evaporating temperature is allowed 

to go down to 37°F (3°C) on temporary base depending on the 

situation.
In case of heating operation the condense temperature is allowed 

to go up to 120°F (49°C) on temporary base depending on the situ

-

ation.
When the request from the indoor units becomes more moderate, 
the system will eventually go to the steady state condition which is 

defined by the operation method above.

•  To activate the powerful comfort setting under cooling opera-

tion, change field setting [2-81]=3.

This setting is used in conjunction with setting [2-8] and [2-47].

•  To activate the powerful comfort setting under heating opera-

tion, change field setting [2-82]=3.

This setting is used in conjunction with setting [2-9].

• 

Quick

Overshoot (during heating operation) or undershoot (during cooling 
operation) is allowed compared to the requested refrigerant tem-
perature, in order to achieve the required room temperature very 
fast. The overshoot is allowed from the start up moment.

03_EN_3P734038-1.indd   36

03_EN_3P734038-1.indd   36

2023/08/22   14:26:47

2023/08/22   14:26:47

Содержание REYQ72XBTJ Series

Страница 1: ...XBYC REYQ432XBYC VRV System air conditioner Please visit http www daikinac com content resources manuals for the most current version of installation instructions and service manual In the event of co...

Страница 2: ...llation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When installing the unit in a small room t...

Страница 3: ...alled either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oil spray or vapor is pro duced f...

Страница 4: ...Field wiring 18 9 1 Power circuit safety device and cable requirements 19 9 2 Wiring connection example for whole system 19 9 3 Leading wire procedure 19 9 4 Transmission wiring connection procedure...

Страница 5: ...ion for REYQ X units are as indicated in tables right where REYQ 192 456 consists of multiple REYQ 96 168 single modules as indicated 72 96 120 144 168 REYQ72XBTJ XBYD XBYC 1 REYQ96XBTJ XBYD XBYC 1 RE...

Страница 6: ...6XBTJ XBYD XBYC 108 280 REYQ240XBTJ XBYD XBYC 120 312 REYQ264XBTJ XBYD XBYC 132 343 REYQ288XBTJ XBYD XBYC 144 374 REYQ312XBTJ XBYD XBYC 156 405 REYQ336XBTJ XBYD XBYC 168 436 REYQ360XBTJ XBYD XBYC 180...

Страница 7: ...lation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for maintenance and servic ing refer to 5 2 Service space on p...

Страница 8: ...esult in the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will disturb the operation of the u...

Страница 9: ...ossibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a e d f c 1 2 3 5 4 ABCD Sides along the installation site with obstacles Suction side A B C D A B 1 a 3 8 10 b 11 3 4 300 c 3 8 10...

Страница 10: ...e Engineering Data Book 6 Inspecting handling and unpacking the unit 6 1 Inspection At delivery the unit must be checked and any damage must be re ported immediately to the carrier s claims agent 6 2...

Страница 11: ...gth remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor units in the case of the multi system Se...

Страница 12: ...he stop valve until 9 Field wiring on page 18 and 12 Checking of device and installation conditions on page 24 are complete Do not use flux when brazing the refrigerant piping Use the phosphor cop per...

Страница 13: ...mm 24 30 36 42 48 54 5 8 in 15 9 mm 3 8 in 9 5 mm 72 3 4 in 19 1 mm 96 7 8 in 22 2 mm 7 4 Selection of refrigerant branch kits For piping example refer to 7 3 Selection of piping size on page 9 When...

Страница 14: ...ontally paying attention to the installation restrictions indicated in 8 Precautions on refrigerant piping on page 14 Example of connection Outdoor unit side Indoor unit side Branch Selector unit 1 2...

Страница 15: ...valent length 43 ft 13 m B C 33 ft 10 m equivalent length 43 ft 13 m B D 33 ft 10 m equivalent length 43 ft 13 m Allowable height differ ence From outdoor unit to indoor unit Height difference Height...

Страница 16: ...ize the liquid pipes b c d e f and g in the figure in the right The upsizing specifications should be as fol lows 3 8 in 9 5 mm 1 2 in 12 7 mm 1 2 in 12 7 mm 5 8 in 15 9 mm 5 8 in 15 9 mm 3 4 in 19 1...

Страница 17: ...film ad versely affects valves and compressors in the refrigerating system and prevents proper operation The Dry Nitrogen pressure should be set to 2 9 psi 0 02 MPa i e just enough so it can be felt o...

Страница 18: ...tion gas pipe stop value Protective plate Stop valves mounting plate High low pressure gas pipe stop valve 5 Cut off the lower part of the smaller pinched piping with an ap propriate tool such as pipe...

Страница 19: ...ing 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor units system To connect the piping between outdoor units an optional multi connection piping kit BHFP26P100U BHFP26P...

Страница 20: ...he horizontal plane Mount the REFNET header so that it branches horizontally 2 Installation of the multi connection piping kit 1 B 1 C D 15 15 A C 4 3 4 in 120 mm D 19 11 16 in 500 mm Install the join...

Страница 21: ...ightening the service port cover 9 Field wiring NOTE All field wiring and components must be installed by a licensed elec trician and must comply with relevant local and national regulations Be sure t...

Страница 22: ...f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 460V 18 9 21 1 2...

Страница 23: ...work onsite settings and so on are done by operating the printed circuit board A1P of Master unit NOTE Do not connect the power wiring to terminals for the transmission wiring Doing so would destroy t...

Страница 24: ...See the figure below Crimp style terminal Insulating sleeve Power wire For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on the termina...

Страница 25: ...TE Always use nitrogen gas for the air tightness test Absolutely do not open the stop valve until the main power circuit insulation measurement has been completed Measuring after the stop valve is ope...

Страница 26: ...uum break with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to 500 microns or less vacuum drying If the system cannot be evacuated to 500 microns within 2 hours repeat t...

Страница 27: ...t the 7 segment display s To access you can remove the service window cover see figure Now you can open the inspection door of the control box cover see figure You can see 3 push buttons and 3 seven s...

Страница 28: ...nected to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function push BS1 one time you will return to the default situati...

Страница 29: ...e the refrigerant more than the specified amount This outdoor unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths systems require additional charg ing of refrigerant...

Страница 30: ...er for systems and each pipe length is shown below Example 7 5 System piping length limitations on page 11 Outdoor system REYQ240XBYC REYQ120XBYC REYQ120XBYC Branch Selector units BS4Q54T 1 BSQ60T 1 B...

Страница 31: ...form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon tube or not If a siphon tube is equipp...

Страница 32: ...han 22 lbs 10 kg perform step 3 till the end of the procedure 3 Pre charging can be done without compressor running by con necting the refrigerant tank only to the liquid stop valve service port open...

Страница 33: ...not forget to close the cover of the service port The tightening torque for the cover is 8 48 to 10 3 ft lbf 11 5 to 13 9 N m 15 Start up and configuration INFORMATION It is important that all inform...

Страница 34: ...ion of the outdoor unit system The first method is to enable an automatic low noise opera tion during night time by field setting The unit will operate at the selected low noise level during the selec...

Страница 35: ...tional external control adaptor DTA104A61 62 is installed Default value 0 To activate this function change 2 12 1 2 18 Fan high static pressure setting In order to increase the static pressure the out...

Страница 36: ...aptor is required to perform power consumption limitation If the system always needs to run under power consump tion limitation conditions this setting activates and defines the level power consumptio...

Страница 37: ...act your Daikin sales representative for further details 2 81 Cooling comfort setting for VRT control Default value 1 Value 2 81 Cooling comfort setting 0 Eco 1 Mild default 2 Quick 3 Powerful Change...

Страница 38: ...ult 8 40 4 4 9 45 7 2 10 50 10 11 55 12 7 12 60 15 5 13 65 18 3 14 AUX Heater always NOT allowed 15 AUX Heater always allowed 2 98 Aux heater max allowable temp release differential AUX Heater is not...

Страница 39: ...iliary or secondary heat source to be automatically energized in the event of a system failure Error codes capable of auto backup are listed in the table below Please be aware that the error codes tha...

Страница 40: ...rt feeling for the customer The selection method of indoor units is important and has to be considered as the available capacity is not the same as under basic operation For details concerning to Hi s...

Страница 41: ...uest from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above The start up condition is different from the...

Страница 42: ...ing air purge etc See installation manual of the Branch Selector units and the indoor units for details CAUTION Do not insert fingers rods or other objects into the air inlet or outlet When the fan is...

Страница 43: ...compressor 4 Make sure the default idle situation is existing see 13 2 Operat ing the push buttons and DIP switches on the printed circuit board on page 24 Push BS2 for 5 seconds or more The unit will...

Страница 44: ...E A7P X11A Check connection on printed circuit board or actuator F3 01 03 05 Discharge temperature too high R21T Stop valves are closed Reverse connection of high low pressure gas pipe and suction gas...

Страница 45: ...on trouble 208 230 460V A3P X6A A1P X28A 575V A4P X6A A1P X28A Check connection 19 20 21 Transmission trouble 208 230 460V A5P X3A A3P X41A 575V A5P X3A A4P X41A Check connection 24 25 26 Transmission...

Страница 46: ...ct refer ring to the wiring diagram for Branch Selector units and correct if there are any errors Check that the DIP switches settings are correct referring to the installation manual enclosed in Bran...

Страница 47: ...e operation on the inverter equipment Be careful not to touch the live parts If a fan rotates due to strong wind it may store electricity in the capacitor or in the main circuit and cause electric sho...

Страница 48: ...ely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of refrigerant and the calculation of the...

Страница 49: ...3P734038 1 EM23A005 2311 SP Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P734038 1 indd 2 00_CV_3P734038 1 indd 2 2023 05 29 10 17 14 2023 05 29 10 17 14...

Отзывы: