8.3. Guidelines for handling stop valve
8.3.1. Cautions on handling the stop valve
• Make sure to keep all stop valves open during operation.
•
6JGƂIWTGDGNQYUJQYUVJGPCOGQHGCEJRCTVTGSWKTGFKPJCPFNKPI
the stop valve.
• The stop valves are factory closed.
3
4
1
2
1 Service port and service port
cover
2 Stop valve
3 Field piping connection
4 Stop valve cover
1
2
3 5
4
1 Service port
2 Stop valve cover
3
*GZCIQPJQNG
4 Shaft
5 Seal
8.3.2. How to use the stop valve
Tightening torques
Stop valve
size
6KIJVGPKPIVQTSWG6WTPENQEMYKUGVQENQUG
5JCHVXCNXGDQF[
Service port
I
3/8
3.7-5.1 ft
x
lbf
(5.0-7.0 N
x
m)
*GZCIQPCNYTGPEJ
4 mm
7.9-10.8 ft
x
lbf
(10.7-14.7 N
x
m)
I
1/2
5.9-7.3 ft
x
lbf
(8.0-10.0 N
x
m)
I
5/8
10.4 - 11.7 ft
x
lbf
(14.0-16.0 N
x
m)
*GZCIQPCNYTGPEJ
6 mm
I
3/4
14.0-15.4 ft
x
lbf
(19.0-21.0 N
x
m)
*GZCIQPCNYTGPEJ
8 mm
I
1
I
1-1/8
19.9 - 24.3 ft
x
lbf
(27.0-33.0 N
x
m)
*GZCIQPCNYTGPEJ
10 mm
Opening the stop valve
1
Remove the stop valve cover.
2
+PUGTVCJGZCIQPYTGPEJKPVQVJGUVQRXCNXGCPFVWTPVJGUVQRXCNXG
counterclockwise.
3
When the stop valve cannot be turned any further, stop turning.
The valve is now open.
• Turn the stop valve until the shaft stops and the designated
torque is achieved.
4
Attach the stop valve cover.
1
2
3
4
Closing the stop valve
1
Remove the stop valve cover.
2
+PUGTVCJGZCIQPYTGPEJKPVQVJGUVQRXCNXGCPFVWTPVJGUVQRXCNXG
clockwise.
3
Turn until the shaft stops by applying the designated torque.
The valve is now closed.
4
Attach the stop valve cover.
Closing direction
8.3.3. Cautions on handling the service port
• Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
• After handling the service port, make sure to tighten the service
port cover securely. For the tightening torque, refer to 8.3.2. How to
use the stop valve.
• Check for refrigerant leaks after tightening the service port cover.
9. Field wiring
NOTE
•
#NNƂGNFYKTKPICPFEQORQPGPVUOWUVDGKPUVCNNGFD[CNKEGPUGFGNGE
-
trician and must comply with relevant local and national regulations.
• Be sure to use a dedicated power circuit. Never use a power supply
shared by another appliance.
• Never install a phase-advancing capacitor. As this unit is equipped
with an inverter, installing a phase-advancing capacitor will not only
deteriorate power factor improvement effect, but also may cause
capacitor abnormal heating accident due to high-frequency waves.
•
#FKUEQPPGEVKQPKPEQTRQTCVGFKPVJGƂZGFYKTKPIKUVQDGRTQXKFGF
Use an all-pole disconnection type breaker with at least 1/8 in. (3
mm) between the contact point gaps.
• Only proceed with wiring work after blocking off all power.
• Always ground wires in accordance with relevant local and national
regulations.
• This machine includes an inverter device. Connect ground and
leave charge to eliminate the impact on other devices by reducing
noise generated from the inverter device and to prevent leaked cur-
rent from being charged in the outer shell of the product.
• Do not connect the ground wire to gas pipes, sewage pipes, light-
ning rods, or telephone ground wires.
Gas pipes
ECPGZRNQFGQTECVEJƂTGKHVJGTGKUCICUNGCM
Sewage pipes:
no grounding effect is possible if hard plastic piping
is used.
Telephone ground wires and lightning rods
are dangerous when
struck by lightning due to abnormal rise in electrical potential in the
grounding.
• This equipment can be installed with a Ground-Fault Circuit Inter-
rupter (GFCI). Although this is a recognized measure for additional
protection, with the grounding system in North America, a dedi-
cated GFCI is not necessary.
• Electrical wiring must be done in accordance with the wiring dia-
grams and the description herein.
• Do not operate until refrigerant piping work is completed. Operating
the unit before completing piping work could cause the compressor
to break.
• Never remove a thermistor, sensor or similar parts when connecting
power wiring and transmission wiring.
B(1B0DLQB959B,0LQGG