• Outdoor Units • VRV HEAT RECOVERY • REYHQ16-24P
1
1
• VRV Systems • Outdoor Units
3
1
Specifications
Current
Nominal
running current
(RLA)
Cooling
A
16.4
19.1
22.2
21.8
Starting current (MSC)
A
4
79
88
88
Z-max
Text
-
0.27
0.25
0.24
Minimum Ssc value
kVa
2,436
2,332
2,042
2,228
Minimum circuit amps
(MCA)
A
37.0
50.0
53.1
63.0
Maximum fuse amps (MFA) A
50
63
63
80
Full load amps (FLA)
A
1.4
1.9
2.1
2.4
Voltage range
Minimum
V
342
342
342
342
Maximum
V
456
456
456
456
Wiring
connections
For Power
Supply
Quantity
5
5
5
5
Remark
Earth wire include
For connection
with indoor
Quantity
2
2
2
2
Remark
F1 - F2
Power Supply Intake
Both indoor and outdoor unit
Notes
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
RLA is based on following conditions : indoor temperature : 27×CDB/19×CWB , outdoor temperature : 35×CDB
Select wire size based on the value of MCA or TOCA
TOCA means the total value of each OC set
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or
above listed range limits
In accordance with EN/IEC 61000-3-11(1), respectively EN/IEC 61000-3-12(2), it may be necessary to consult the
distribution network operator to ensure that the equipment is connected only to a supply with Zsys(4) <= Zmax,
respectively Ssc(3) >= minimum Ss
1-3 ELECTRICAL SPECIFICATIONS
(50HZ)
REYHQ16PY1B
REYHQ20PY1B
REYHQ22PY1B
REYHQ24PY1B