• Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B
1
3
• Split Sky Air • Outdoor Units
11
3
Electrical data
Unit combination
Power supply
Compressor
OFM
IFM
Indoor unit
Outdoor unit
Hz-Volts
Voltage range
MCA
TOCA
MFA
LRA
RLA
kW
FLA
kW
FLA
FCQ125B
REQ125B8V3B
50-400
Max. 50Hz-400V
Min. 50Hz-360V
12.4
15.3
20
63
8.1
0.065
+0.085
0.6+0.7
0.09
1.0
FCQ125C
REQ125B8V3B
50-400
12.4
15.3
20
63
8.1
0.065
+0.085
0.6+0.7
0.12
1.0
FHQ125
REQ125B8V3B
50-400
12.3
15.0
20
63
8.2
0.065
+0.085
0.6+0.7
0.13
0.7
FBQ125
REQ125B8V3B
50-400
12.2
15.7
20
63
7.6
0.065
+0.085
0.6+0.7
0.225
1.4
FDEQ125
REQ125B8V3B
50-400
12.6
15.7
20
63
7.9
0.065
+0.085
0.6+0.7
0.225
1.4
3TW26639-9A
SYMBOLS
MCA
: Min. Circuit Amps
TOCA
: Total Over Current Amps
MFA
: Max. Fuse Amps (see note 7)
LRA
: Locked Rotor Amps
RLA
: Rated Load Amps
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
kW
: Rated motor output
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. TOCA means the total value of each OC set
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit
terminals is not below or above listed operation range limits
4. Maximum allowable voltage unbalance between phases is 2%.
5. MCA/MFA
MCA = 1.25 x RLA + all FLA, MFA = < 2.25 x RLA + all FLA (next lower standard
fuse rating Min. 16A)
6. Select wire size based on the larger value of MCA or TOCA
7. Instead of fuse, use circuit breaker
8. For more details concerning conditional connections, see
http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select
’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop
down lists, click the search button.
Finally, click on the document title of your choice.