manualshive.com logo in svg
background image

English

Français

Español

INSTALLATION MANUAL

MODEL

RELQ72TBTJ

*

RELQ96TBTJ

*

RELQ120TBTJ

*

RELQ144TBTJ

*

RELQ192TBTJ

*

RELQ240TBTJ

*

RELQ72TBYD

*

RELQ96TBYD

*

RELQ120TBYD

*

RELQ144TBYD

*

RELQ192TBYD

*

RELQ240TBYD

*

RELQ72TBYC

*

RELQ96TBYC

*

RELQ120TBYC

*

RELQ144TBYC

*

RELQ192TBYC

*

RELQ240TBYC

*

Aurora Series

VRV

System air conditioner

Please visit http://www.daikinac.com/content/resources/manuals for the most current version of installation instructions 

and service manual. In the event of conflicting information, the online instructions are to be used.

Veuillez visiter http://www.daikinac.com/content/resources/manuals pour obtenir la version la plus récente des 
instructions d’installation et du manuel de service. En cas de conflit d’informations, les instructions en ligne sont à 
privilégier.

Por favor visite http://www.daikinac.com/content/resources/manuals para obtener la versión más actualizada de las 
instrucciones de instalación y del manual de servicio. En caso de información conflictiva, se utilizarán las 

instrucciones en línea.

00_CV_3P734038-2.indd   1

00_CV_3P734038-2.indd   1

2023/09/15   9:31:00

2023/09/15   9:31:00

Содержание RELQ72TBTJ Series

Страница 1: ...the event of conflicting information the online instructions are to be used Veuillez visiter http www daikinac com content resources manuals pour obtenir la version la plus r cente des instructions d...

Страница 2: ...tion work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When installing the unit in a small room take...

Страница 3: ...ed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oil spray or vapor is pro duced for...

Страница 4: ...18 9 Field wiring 19 9 1 Power circuit safety device and cable requirements 20 9 2 Wiring connection example for whole system 20 9 3 Leading wire procedure 20 9 4 Transmission wiring connection proce...

Страница 5: ...and right where RELQ 144 240 consists of multiple RELQ 72 120 single modules as indicated 72 96 120 RELQ72TBTJ TBYD TBYC 1 RELQ96TBTJ TBYD TBYC 1 RELQ120TBTJ TBYD TBYC 1 RELQ144TBTJ TBYD TBYC 2 RELQ1...

Страница 6: ...TJ TBYD TBYC 168 312 NOTE Higher capacity than the above table can be selected this may affect heating and cooling capacity For additional information see technical engineering data 1 4 Scope of the m...

Страница 7: ...he unit Installation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for maintenance and servic ing refer to 5 2 Serv...

Страница 8: ...lt in the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will disturb the operation of the unit...

Страница 9: ...the possibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a e d f c 1 2 3 5 4 ABCD Sides along the installation site with obstacles Suction side A B C D A B 1 a 3 8 10 b 11 3 4 300 c...

Страница 10: ...ngineering Data Book 6 Inspecting handling and unpacking the unit 6 1 Inspection At delivery the unit must be checked and any damage must be re ported immediately to the carrier s claims agent 6 2 Han...

Страница 11: ...gth remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor units in the case of the multi system Se...

Страница 12: ...ng work is complete do not under any circumstances open the stop valve until 9 Field wiring on page 19 and 12 Checking of device and installation conditions on page 25 are complete Do not use flux whe...

Страница 13: ...Branch Selector units C Choose from the following table in accordance with the indoor unit total capacity connected downstream Do not let the connection pip ing exceed the refrigerant piping size chos...

Страница 14: ...P25M33H9 KHRP25M33HA KHRP26M22H9 KHRP26M22HA maximum 4 indoor units or KHRP26M33H9 KHRP26M33HA maximum 8 indoor units 72 111 KHRP26M33H9 KHRP26M33HA 111 230 KHRP25M72H9 KHRP25M72HA KHRP26M72H9 KHRP26M...

Страница 15: ...m to the below length when calculating an equivalent length to each indoor unit connected to BSF Q54T Total capacity of the indoor units to be connected down stream Equivalent length BSF4Q54T BSF6Q54T...

Страница 16: ...he figure below referring to the table below Do not upsize the high low pressure gas pipe and the suction gas pipe Outdoor unit capacity type Liquid pipe Main pipe Upsize the liquid pipe First refrige...

Страница 17: ...pe and lines that are not upsized should not be doubled a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p q r s 1640 ft 500 m 3 The actual piping length from each indoor units to the nearest refriger ant bran...

Страница 18: ...m ad versely affects valves and compressors in the refrigerating system and prevents proper operation The Dry Nitrogen pressure should be set to 2 9 psi 0 02 MPa i e just enough so it can be felt on t...

Страница 19: ...op valve Suction gas pipe stop value Protective plate Stop valves mounting plate High low pressure gas pipe stop valve 5 Cut off the lower part of the smaller pinched piping with an ap propriate tool...

Страница 20: ...ller field piping 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor units system To connect the piping between outdoor units an optional multi connection piping kit BHFP2...

Страница 21: ...eader so that it branches horizontally 2 Installation of the multi connection piping kit 1 B 1 C D 15 15 A C 4 3 4 in 120 mm D 19 11 16 in 500 mm Install the joints horizontally so that the caution la...

Страница 22: ...lve Check for refrigerant leaks after tightening the service port cover 9 Field wiring NOTE All field wiring and components must be installed by a licensed elec trician and must comply with relevant l...

Страница 23: ...RELQ96TBYD RELQ120TBYD RELQ144TBYD RELQ192TBYD RELQ240TBYD f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz 460V 460V 460V 460V 460V 460V 28 1 39 8 43 4 28 1 28 1 39 8 39 8 43 4 43 4 35 45 50 35 35 45...

Страница 24: ...ation work onsite settings and so on are done by operating the printed circuit board A1P of Master unit NOTE Do not connect the power wiring to terminals for the transmission wiring Doing so would des...

Страница 25: ...ctions See the figure below Crimp style terminal Insulating sleeve Power wire For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on the t...

Страница 26: ...r the air tightness test Absolutely do not open the stop valve until the main power circuit insulation measurement has been completed Measuring after the stop valve is opened will cause the insulation...

Страница 27: ...ns vacuum break with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to 500 microns or less vacuum drying If the system cannot be evacuated to 500 microns within 2 hours re...

Страница 28: ...ccess you can remove the service window cover see figure Now you can open the inspection door of the control box cover see figure You can see 3 push buttons and 3 seven segment displays and DIP switch...

Страница 29: ...cted to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function push BS1 one time you will return to the default situation...

Страница 30: ...refrigerant charge In case recharge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount 14 2 Calculating the additional refrigerant charge NOTE The re...

Страница 31: ...2 Indoor units FXSQ type 12 2 FXMQ type 15 2 18 5 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft f f1 4 5 ft k f3 8 10 ft p f3 8 15 ft u f3 8 10 ft b f3 4 10 ft g f1 4 5 ft f3 8 10 ft q f1 4 10...

Страница 32: ...it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon tube or not If a siphon tube...

Страница 33: ...valve C Make sure that all outdoor unit stop valves as well as valves A and C are closed 1 2 3 4 5 6 B 9 8 11 11 12 10 14 13 15 16 A C 7 1 Pressure reducing valve 2 Nitrogen 3 Measuring instrument 4...

Страница 34: ...the refrigerant Operating with the stop valves closed will damage the compressor 15 Start up and configuration INFORMATION It is important that all information in this chapter is read sequentially by...

Страница 35: ...low noise operation based on an external input For this operation an optional acces sory is required 1 2 shows the status of power consumption limitation operation 1 unit is currently operating under...

Страница 36: ...nal external control adaptor DTA104A61 62 is installed Default value 0 To activate this function change 2 12 1 2 18 Fan high static pressure setting In order to increase the static pressure the outdoo...

Страница 37: ...or is required to perform power consumption limitation If the system always needs to run under power consump tion limitation conditions this setting activates and defines the level power consumption l...

Страница 38: ...lt 2 Quick 3 Powerful Change 2 81 0 1 2 or 3 in function of required limitation This setting is used in conjunction with setting 2 8 and 2 47 In the case of 2 81 0 the original refrigerant temperature...

Страница 39: ...X Heater is not allowed to energize when the outdoor ambient temp is recovered by differential below above the AUX Heater Max Allowable Temp AUX Heater Max Allowable temp Release differential Fahrenhe...

Страница 40: ...ary or secondary heat source to be automatically energized in the event of a system failure Error codes capable of auto backup are listed in the table below Please be aware that the error codes that a...

Страница 41: ...feeling for the customer The selection method of indoor units is important and has to be considered as the available capacity is not the same as under basic operation For details concerning to Hi sens...

Страница 42: ...t from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above The start up condition is different from the po...

Страница 43: ...air purge etc See installation manual of the Branch Selector units and the indoor units for details CAUTION Do not insert fingers rods or other objects into the air inlet or outlet When the fan is ro...

Страница 44: ...pressor 4 Make sure the default idle situation is existing see 13 2 Operat ing the push buttons and DIP switches on the printed circuit board on page 25 Push BS2 for 5 seconds or more The unit will st...

Страница 45: ...it board or actuator 31 36 Electronic expansion valve malfunction 208 230 460V Y6E A6P X10A 575V Y6E A7P X10A Check connection on printed circuit board or actuator 32 37 Electronic expansion valve mal...

Страница 46: ...function open circuit S1NPL A1P X31A Check connection on printed circuit board or actuator 07 09 Low pressure sensor malfunction short circuit S1NPL A1P X31A Check connection on printed circuit board...

Страница 47: ...ring to the wiring diagram for Branch Selector units and correct if there are any errors Check that the DIP switches settings are correct referring to the installation manual enclosed in Branch Selec...

Страница 48: ...s due to strong wind it may store electricity in the capacitor or in the main circuit and cause electric shock 5 After the service is finished plug the junction connector back in Otherwise the malfunc...

Страница 49: ...event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of refrigerant and the calculation of the max...

Страница 50: ...3P734038 2 EM23A007 2311 SP Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P734038 2 indd 2 00_CV_3P734038 2 indd 2 2023 05 29 11 57 22 2023 05 29 11 57 22...

Отзывы: