18
The following steps require no power to be applied.
–
Check for any loose, disconnected, broken, or shorted wires
between all connected components
BEFORE
applying power
–
No short between Data 1 or Data 2 wires and R (24 VAC) or C (24
VAC common)
–
Check for Data 1 and Data 2 wires reversed at the indoor unit,
thermostat, or outdoor unit
After fixing all the wiring issues apply power
–
Check for 24 VAC across R (24 VAC) and C (24 VAC common)
terminals
–
If there are still problems discovering the indoor or outdoor
equipment then check for bias reading of 0.6 VDC. Bias reading
of 0.6 VDC indicates a robust network that can handle high data
volume without lock-up.
Wiring Troubleshooting
0.6 VDC
NOTES: If Bias reading is below 0.6 VDC, check the TERM Dip-Switch (DS1) setting
on the outdoor unit. Move the TERM Dip-Switch (DS1) to OFF Position. This
should improve the Bias reading to 0.6 VDC
Содержание One+
Страница 1: ...Daikin One smart thermostat Reference Guide...
Страница 4: ......
Страница 5: ...Introduction...
Страница 14: ...14 Wiring Diagram...
Страница 16: ...16 Wiring Diagram...
Страница 20: ...20 Wiring Troubleshooting View of the DS1 Switch on the Outdoor Unit PC Boards 1 17 SEER Daikin Fit...
Страница 21: ...21 INTRODUCTION 2 18 SEER all tonnage...
Страница 22: ...22 Wiring Troubleshooting 3 20 SEER 2 and 3 Ton...
Страница 23: ...23 INTRODUCTION 4 20 SEER 4 Ton...
Страница 24: ...24 Wiring Troubleshooting 5 20 SEER 5 Ton...
Страница 25: ......
Страница 26: ......
Страница 27: ...System Power Up...
Страница 28: ......
Страница 47: ...47 SYSTEM POWER UP...
Страница 49: ......
Страница 50: ......
Страница 51: ...References...
Страница 53: ...53 REFERENCES...
Страница 67: ...67 Notes...
Страница 68: ...68 Notes...
Страница 69: ...69 Notes...
Страница 70: ...70 Notes...