I

nsTallaTIon

www.DaikinApplied.com 

IM 1102 • PARALLEL TERMINAL BOX

Controls

 CAUTION

Static sensitive components . Can cause equipment 

damage . 

Discharge any static electrical charge by touching the bare 

metal inside the control panel before performing any service 

work. Never unplug cables, circuit board terminal blocks, or 

power plugs while power is applied to the panel. 

Detailed information regarding connection, start-up and 

operating procedures for controls provided by Daikin 

are available from your local Daikin representative. For 

information on controls by other manufacturers, contact that 

manufacturer’s local branch or dealer. 

IMPORTANT: 

Units with digital controls, if factory programmed, 

incorporate specific communication addresses. Installing the 

terminal in a different location than noted on unit label and 

building plans may result in excessive start-up labor. 

Labeling

Fan Powered Air Terminals are shipped from the factory with 

up to seven different information labels (not all labels pertain 

to all fan powered units depending upon the type of insulation 

and the final ship to state). 

1.

Control Label – affixed to the fan powered terminal

casing or the inside of the control panel cover. Shows

piping/wiring diagram and control sequence number and

fusing (if applicable).

2.

Calibration Label – affixed to the fan powered terminal

casing. Shows air flow calibration data and control

settings (if applicable).

3.

I.D. Label – affixed to the fan powered terminal casing.

Shows tagging information, customer order number, ETL

Logo, Daikin Logo, etc.

4.

ARI Certification Label on Fan Powered Terminal Unit –

identifies applicable industry test standard and certifies

unit is in compliance.

5.

ARI Certification Label on Hot Water Coils – identifies

applicable industry test standard and certifies hot water

coil compliance (if hot water coils is ordered as an

accessory).

6.

Fiberglass Label – identifies insulation type for units

shipped to California.

7.

Orientation label – identifies the proper air flow direction

and the top of the unit.

Flow Sensor

Fan Powered Air Terminals are shipped with a factory installed 

pressure differential flow sensor installed. See (Figure 4) for 

the calibration curve. 

Initial Start-up/Adjustment of Fan 

Flow Rate

 WARNING

Solid state speed controls cause all electric motors to run 

hotter and speed reduction should never be below 700 RPM 

for proper lubrication of motor bearings.

1. Check that the discharge duct work is connected. The

minimum recommended discharge static pressure is 0.2

inches of w.g.

2. Make certain that the electrical connection is properly

installed and that all safety covers and access panels are

in place.

3. Inspect the fan box and duct work for the presence of

any packing / foreign materials and remove if found.

4. Motor is shipped from the factory set at full speed.

Allow the motor to warm up for a period greater than

10 minutes prior to adjusting speed control. During this

warm up period, inspect the ductwork for leaks and make

any necessary repairs.

CAUTION:

 Do not operate the fan box if the downstream

ductwork is not present.

5. Flow adjustment: Turn the speed control

counterclockwise to reduce the fan speed. Clockwise

rotation will increase the fan speed.

6. Set the unit to full heating (maximum induction). Adjust

the downstream balancing dampers (if present). Adjust

the speed control to deliver the desired air flow rate by

measuring the air delivered to the room outlets using a

flow hood or other instruments.

7. Set the unit to full cooling (maximum primary air). (Refer

to controls literature for detailed control installation

information.) The fan may need to be readjusted with the

primary air and ventilation air at maximum set point to

insure that no supply air is discharged at the plenum air

intake port, then recheck full heating.

Fan Maintenance Procedure

The motor is equipped with permanently lubricated bearings. 

Inspect the motor, fan and terminal unit for the buildup of dust 

or other foreign material. Clean as required by the operating 

environment and type of insulation installed. 

Содержание MQFVI5

Страница 1: ...Installation and Maintenance Manual IM 1102 Group Applied Air Systems Part Number IM 1102 Date October 2010 Parallel Fan Powered Variable Air Volume VAV Terminal Box Model MQFVI5 ...

Страница 2: ... 4 Connecting Ductwork 6 Minimum Clearance for Access 6 Field Electrical Wiring 6 Fan Powered Air Terminal Units with Electric Heat 6 Fan Powered Air Terminal Units with Hot Water Coils 6 Controls 7 Labeling 7 Flow Sensor 7 Initial Start up Adjustment of Fan Flow Rate 7 Fan Maintenance Procedure 7 Troubleshooting 8 Possible Conditions 8 Investigating Noise Complaints 9 Controls 9 Electric Duct Hea...

Страница 3: ... for his or her application The following are trade names or registered trademarks of their respective companies BACnet from the American Society of Heating Refrigerating and Air Conditioning Engineers Inc Windows from Microsoft Corporation Daikin and MicroTech from Daikin Applied Hazardous Information Messages Familiarize yourself with the hazard identification messages used in this manual DANGER...

Страница 4: ...e mounted right side up The fan powered unit must be level within or 10 degrees of horizontal both parallel to the air flow and at the right angle of air flow The control side of the terminal is labeled with an arrow indicating UP Unless otherwise noted most analog and digital controls may be installed in any orientation Check with the local Daikin representative for verification CAUTION The equip...

Страница 5: ...Installation www DaikinApplied com 5 IM 1102 PARALLEL TERMINAL BOX Figure 1 Hanging straps Figure 2 Trapeze Hangers Figure 3 Optional hanging brackets and hanger rods ...

Страница 6: ...ck hazard Can cause personal injury or equipment damage This equipment must be properly grounded Connections and service to the MicroTech III Chiller Unit Controller must be performed only by personnel knowledgeable in the operation of the equipment being controlled All field wiring must comply with the local codes and with the National Electrical Code ANSI NFPA 70 2002 When applicable electrical ...

Страница 7: ...pped to California 7 Orientation label identifies the proper air flow direction and the top of the unit Flow Sensor Fan Powered Air Terminals are shipped with a factory installed pressure differential flow sensor installed See Figure 4 for the calibration curve Initial Start up Adjustment of Fan Flow Rate WARNING Solid state speed controls cause all electric motors to run hotter and speed reductio...

Страница 8: ...ged intake filter if supplied 4 Re adjust the fan speed control 5 Discharge static pressure too high If repair or replacement of blower or motor is required the motor and fan should be removed as an assembly 1 Disconnect power prior to removal 2 Remove the bottom blower access panel 3 Disconnect the two electrical leads from Terminal Connection 1 and 2 on the motor 4 Remove the bottom two lug scre...

Страница 9: ...n concerning controls provided by Daikin For controls provided by others contact the local control representative for assistance Electric Duct Heater WARNING Electric shock hazard Can cause personal injury or equipment damage This equipment must be properly grounded Connections and service to the MicroTech III Chiller Unit Controller must be performed only by personnel knowledgeable in the operati...

Страница 10: ...rom the pitot tube located in the control cabinet Attach a magnehelic gauge to the pitot tube Available static pressure at the pitot tube should be 0 03 S P or 0 03 S P If the available static pressure is in the dead band between these two ranges the switch will not engage and some method must be devised to increase the available static pressure If sufficient static pressure is available check to ...

Страница 11: ...Troubleshooting www DaikinApplied com 11 IM 1102 PARALLEL TERMINAL BOX Figure 4 MI Flow Sensor Calibration Chart ...

Страница 12: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinApplie...