IM 1102 • PARALLEL TERMINAL BOX 4 

www.DaikinApplied.com

I

nsTallaTIon

I

nsTallaTIon

Receiving Inspection

 CAUTION

Do  not  use  the  flow  sensor,  connecting  tubing,  or  damper 

shaft  as  a  lift  point.  Damage  to  the  flow  sensor  or  controls 

may result. 

Prior to removing the shipping material, visually inspect 

the packing materials. There should be a black plastic strip 

wrapped in the clear plastic shrink wrap. If this black plastic 

strip is missing, the shipment may have been repacked by 

the shipper and you should make note of this on the shipping 

documents and inform the delivering carrier. After unpacking 

the terminal, check it for shipping damage. If any shipping 

damage is found, report it immediately to the delivering 

carrier. Store units in a clean, dry location prior to installation. 

Units with controls are not recommended for use in ambient 

temperatures greater than 95°F. For protection of controls, do 

not store in ambient temperatures greater than 135°F.  

Hanging/Installation Requirements

 CAUTION

If  equipped  with  pneumatic  controls,  the  orientation  of  the 

terminal is critical. The pneumatic controls must be mounted 

right side up. The fan powered unit must be level  

or – 10 degrees of horizontal, both parallel to the air flow and 

at the right angle of air flow. The control side of the terminal 

is labeled with an arrow indicating UP. Unless otherwise 

noted,  most  analog  and  digital  controls  may  be  installed  in 

any orientation. 

Check with the local Daikin representative for verification. 

 CAUTION

The equipment is heavy and mounted in the ceiling. Use 

caution and follow OSHA or SMACNA installation guidelines.

The Fan Powered Air Terminal should be suspended from the 

building structure in a horizontal plane with the two bottom 

access panels facing downward. Do not obstruct the bottom 

access panels or control panel enclosure cover. At both 

ends of the air terminal unit, a three inch wide mounting lip 

provides easy installation of either trapeze type hangers or 

hanging straps.  

•  Use the required mounting support method prescribed for 

the rectangular duct per the job specifications, or 

•  Use hanging straps located at both ends of the fan 

powered unit (

Figure 1

), or 

•  Use trapeze mounts located at both ends of the fan 

powered terminal unit (

Figure 2

), or 

•  Fan powered air terminals may be suspended with 

optional hanging brackets and hanger rod. (

Figure 3

The Fan Powered Air Terminal is not suitable for outdoor use. 

Содержание MQFVI5

Страница 1: ...Installation and Maintenance Manual IM 1102 Group Applied Air Systems Part Number IM 1102 Date October 2010 Parallel Fan Powered Variable Air Volume VAV Terminal Box Model MQFVI5 ...

Страница 2: ... 4 Connecting Ductwork 6 Minimum Clearance for Access 6 Field Electrical Wiring 6 Fan Powered Air Terminal Units with Electric Heat 6 Fan Powered Air Terminal Units with Hot Water Coils 6 Controls 7 Labeling 7 Flow Sensor 7 Initial Start up Adjustment of Fan Flow Rate 7 Fan Maintenance Procedure 7 Troubleshooting 8 Possible Conditions 8 Investigating Noise Complaints 9 Controls 9 Electric Duct Hea...

Страница 3: ... for his or her application The following are trade names or registered trademarks of their respective companies BACnet from the American Society of Heating Refrigerating and Air Conditioning Engineers Inc Windows from Microsoft Corporation Daikin and MicroTech from Daikin Applied Hazardous Information Messages Familiarize yourself with the hazard identification messages used in this manual DANGER...

Страница 4: ...e mounted right side up The fan powered unit must be level within or 10 degrees of horizontal both parallel to the air flow and at the right angle of air flow The control side of the terminal is labeled with an arrow indicating UP Unless otherwise noted most analog and digital controls may be installed in any orientation Check with the local Daikin representative for verification CAUTION The equip...

Страница 5: ...Installation www DaikinApplied com 5 IM 1102 PARALLEL TERMINAL BOX Figure 1 Hanging straps Figure 2 Trapeze Hangers Figure 3 Optional hanging brackets and hanger rods ...

Страница 6: ...ck hazard Can cause personal injury or equipment damage This equipment must be properly grounded Connections and service to the MicroTech III Chiller Unit Controller must be performed only by personnel knowledgeable in the operation of the equipment being controlled All field wiring must comply with the local codes and with the National Electrical Code ANSI NFPA 70 2002 When applicable electrical ...

Страница 7: ...pped to California 7 Orientation label identifies the proper air flow direction and the top of the unit Flow Sensor Fan Powered Air Terminals are shipped with a factory installed pressure differential flow sensor installed See Figure 4 for the calibration curve Initial Start up Adjustment of Fan Flow Rate WARNING Solid state speed controls cause all electric motors to run hotter and speed reductio...

Страница 8: ...ged intake filter if supplied 4 Re adjust the fan speed control 5 Discharge static pressure too high If repair or replacement of blower or motor is required the motor and fan should be removed as an assembly 1 Disconnect power prior to removal 2 Remove the bottom blower access panel 3 Disconnect the two electrical leads from Terminal Connection 1 and 2 on the motor 4 Remove the bottom two lug scre...

Страница 9: ...n concerning controls provided by Daikin For controls provided by others contact the local control representative for assistance Electric Duct Heater WARNING Electric shock hazard Can cause personal injury or equipment damage This equipment must be properly grounded Connections and service to the MicroTech III Chiller Unit Controller must be performed only by personnel knowledgeable in the operati...

Страница 10: ...rom the pitot tube located in the control cabinet Attach a magnehelic gauge to the pitot tube Available static pressure at the pitot tube should be 0 03 S P or 0 03 S P If the available static pressure is in the dead band between these two ranges the switch will not engage and some method must be devised to increase the available static pressure If sufficient static pressure is available check to ...

Страница 11: ...Troubleshooting www DaikinApplied com 11 IM 1102 PARALLEL TERMINAL BOX Figure 4 MI Flow Sensor Calibration Chart ...

Страница 12: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinApplie...

Отзывы: