OM 1280-2 • MICROTECH UNIT CONTROLLER 52 www.DaikinApplied.com
UVC Configuration Parameters
Parameter (LUI)
Operating Range (Default)
ABV
Min
Max
Default
Description
LwSctLnDifSpt
(4.0°F)
1
8
4
“The low suction line temperature alarm setpoint
is fixed at 28°F.
The alarm becomes INACTIVE when the
temperature gets to 28°F + this setpoint.”
DefInFanSpt
30°F to 110°F
30
110
90
If aiIndoorCoilTemp ≥ to this setpt then the
indoor fan is turned off, otherwise it can run.
OACoilTmpSpt
30°F to 40°F
30
40
32
Defrost mode ends when the defrost timer
expires or when aiOutdoorCoilTemp ≥
cpOACoilTem cpDefrostTempDiff.
DefTmpDiff
5°F to 40°F
5
40
20
Defrost mode ends when the defrost timer
expires or when aiOutdoorCoilTemp ≥
cpOACoilTem cpDefrostTempDiff.
Network Communications
MinInst
0 to 4194302
0
4194302 3101000 Added to BACnetNodeAddress to determine the
Device Instance Number (BNDevInstance).
Loc
0 (“Location”)
Location Location Label
DevInst
0 to 4194302
0
4194302 3101120 BACnet device instance.
DevName
String 20 char.
DevName BACnet device name string.
NdAddr
0 to 127
0
127
120
BACnet MSTP node address.
MSTPBaud
9600, 19200, 38400, 76800
0
3
2
BACnet MSTP baud rate.
MSTPMaxMstr
1 to 127
1
127
127
BACnet MSTP max masters.
MSTPInfoFr
1 to 5
1
5
1
BACnet MSTP info frames.
MeasUnits
IMPERIAL, SI (IMPERIAL)
0
1
0
BACnet measurement units.
SndHrtBt
0 to 6553.4 sec (0.0 sec)
0
6553.4
0
Send Heartbeat. When set to non-zero, for each
NVO, this is the maximum time before each
NVO is sent-out.
RcvHrtBt
0 to 6553.4 sec (0.0 sec)
0
6553.4
0
Receive Heartbeat. If an NVI isn’t received
within this amount of time then the default NVI
will be used.
MnTimeOut
0 to 6553.4 sec (0.0 sec)
0
6553.4
0
Minimum Send Time. This amount of time must
pass before an NVO can be sent.