OM 931-6 • MicroTech III Unit Controller for WSHP
18
www.DaikinApplied.com
o
peratIon
Second Circuit Faults
With the addition of the second circuit the fault recovery and reset table has new faults for the second circuit. Refer to
"Table 3: Faults" on page
11
.
Table 11: I/O Expansion Module Connections & Descriptions
H2
Description
Pin 1
Fan high speed normally open output
Pin 2
No connection
Pin 3
24 VAC Common
H3
Pin 1
For future development
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
H8
Pin 1
Dual compressor: compressor 2 normally open output, all others fan medium speed
normally open
Pin 2
24 VAC common
Pin 3
No connection
Pin 4
Dual compressor: reversing valve for circuit 2, all others electric heat
Pin 5
24 VAC common
H4
Pin 1
Entering water temperature sensor signal
Pin 2
Entering water temperature sensor common
HP6
HP2-1
High pressure switch for circuit 2
HP2-2
High pressure switch for circuit 2
H7
Pin 1
Suction line temperature sensor circuit 2 signal
Pin 2
Suction line temperature sensor circuit 2 common
Pin 3
Low pressure switch circuit 2 signal
Pin 4
Low pressure switch circuit 2 source
H5
LED Annunciator
TB1
For future use