Daikin MicroTech III Скачать руководство пользователя страница 15

OM 931-6 • MicroTech III Unit Controller for WSHP 

15 

www.DaikinApplied.com

Microtech

®

 III Unit Controller 

Interface to External Equipment

■  The MicroTech III unit controller’s thermostat 

input terminals may be directly interfaced with any 

standard or night setback thermostat that uses 

mechanical dry contacts. Power cannot be supplied 

from the water source heat pump for electronic 

thermostats that require a separate power supply 

for their internal operation except hose provided 

by Daikin. Only thermostats offered by Daikin are 

proven to operate properly with the MicroTech III unit 

controller. Daikin makes no guarantees about any 

other thermostat or control device interfaced by the 

end user with the MicroTech III unit controller.

■  Care must be used to isolate all external power 

sources from the MicroTech III unit controller to 

prevent ground loops and other unpredictable 

electrical problems. Only dry mechanical contacts 

should be used to operate or interface with the 

MicroTech III unit controller’s thermostat and or 

control inputs. Use mechanical relays to isolate 

two power systems when external equipment with 

its own power supply is used to interface with or 

control the MicroTech III unit controller’s thermostat 

and or control inputs.  For example, if you have 

a Building Automation System (BAS), controller, 

etc., and you wish to use a digital output from the 

building automation system or controller that is 

internally powered, then you must use an additional 

mechanical relay (not supplied by Daikin) to isolate 

the MicroTech III unit controller.

■  Due to the nature of triacs and other solid state 

devices, triacs cannot be directly used to operate 

the MicroTech III’s unit controller’s thermostat or 

control inputs. To interface triacs or other solid 

state switching devices to the MicroTech III unit 

controller inputs, separate them from the board 

using mechanical relays. To do this, use the triac or 

solid state device to drive a mechanical relay (not 

supplied by Daikin), then use the mechanical relay’s 

dry contacts to drive the desired MicroTech III unit 

controller input.

■   The MicroTech III unit controller’s valve or pump 

request terminal {IV/PR (H8)} is an output signal 

to external devices to allow water flow as required 

by the heat pump. The IV/PR (H8) terminal follows 

compressor operation inversely if connected to the 

normally open terminal and simultaneously when 

connected to the normally closed terminal. The IV/

PR (H8) terminal can be used as a signal to an 

external pump or valve to enable flow to the unit. The 

compressor start is delayed for 45 seconds after the 

IV/PR (H8) output is energized.

Table 6:  IV/PR(H8) Terminal and Compressor Operation

IV/PR(H8)

Compressor On

Compressor Off

Normally Open

24 VAC

0 VAC

Normally Closed

0 VAC

24 VAC

Appendix A

Operation and Maintenance of I/O 

Expansion Module

Introduction

The I/O Expansion Module is a field-installed option.  It 

is an extension of the main board and provides extra 

functionality to the MicroTech III control system. 
The I/O Expansion Module has 4 main purposes:
■  The MicroTech III unit controller in combination 

with the I/O Expansion Module will be the standard 

control system for two stage Water Source Heat 

Pump equipment.

■  The I/O Expansion Module has outputs to control 

boilerless electric or supplemental electric secondary 

heating options on a standard Water Source Heat 

Pump.

■  The I/O Expansion Module has outputs for multi-

speed fans on a standard Water Source Heat Pump.

■  The I/O Expansion Module has an independent LED 

annunciator to identify operational fault conditions on 

second stage equipment.

Adding an I/O Expansion Module (with an interconnect 

cable) to the main controller allows two stage operation 

of the water source heat pump.

Features

Standard Heat Pumps / Single Circuit Units

 

■  Monitors entering water temperature for 

boilerless electric heat control

 

■  Outputs for medium and high speed fan controls

Second Circuit

 

■  High pressure switch

 

■  Low pressure switch

 

■  Low suction line temperature sensor

 

■  Compressor output

 

■  Reversing valve

M

ICro

t

eCh

 III u

nIt

 C

ontroller

Содержание MicroTech III

Страница 1: ...ion Maintenance Manual MicroTech III Unit Controller for Water Source Heat Pump Units Used with Enfinity Models CCH CCW VFC VFW MHC MHW LVC LVW OM 931 6 Group WSHP Part Number 910157590 Date September...

Страница 2: ...al Equipment 15 Appendix A 15 Operation and Maintenance of I O Expansion Module 15 Start up 16 Initial Power up 16 Operation 17 Electric Heat Controls 17 Multiple Speed Fan Control 17 Circuit Two Addi...

Страница 3: ...ump LonWorks Communication Module IM 928 MicroTech III Water Source Heat Pump Unit Controller BACnet MS TP Communication Module IM 933 LonWorks Plug In Software for use with MicroTech III Unitary Cont...

Страница 4: ...put H7 1 1 No Connection H7 2 No Connection MicroTech III Unit Controller H7 3 Red LED Output H7 4 Green LED Output H7 5 Yellow LED Output H7 6 Red Green Yellow LED Common H8 1 1 Isolation Valve Pump...

Страница 5: ...M 931 6 MicroTech III Unit Controller for WSHP 5 www DaikinApplied com MicroTech III Unit Controller MicroTech III Unit Controller Connections Figure 1 MicroTech III Unit Controller Terminal Locations...

Страница 6: ...ed Service Test Mode Fan Operation JP2 Open Continuous Fan Operation On when not operating in the unccupied mode Shorted Cycling Fan Operation Auto Loop Fluid JP3 see warning Open Water Loop Fluid wat...

Страница 7: ...1 and Y1 respectively for single circuit units in occupied mode For information on W2 and Y2 for dual circuit units refer to Dual Circuit Units on page 17 The MicroTech III unit controller is configur...

Страница 8: ...hen the Y1 terminal is de energized the following occurs 1 The compressor de energizes 2 The fan de energizes unless the G terminal is energized 24VAC or JP2 is open 3 The IV PR H8 control output ener...

Страница 9: ...unit operation No faults or modes have higher priority than a brownout fault condition Remote shutdown and brownout conditions have the same level of priority See Priority of Faults and Modes on page...

Страница 10: ...r LP circuit is closed the unit does not return to normal operation until the control board is reset The unit is locked out in this manner until the unit can be serviced The control board is reset by...

Страница 11: ...ers an automatic lockout on the 3rd fault The retry count is reset to zero every 24 hours Refer to Table 3 Faults Tenant Override Note It is recommended that the Occupied Opera tion on page 7 and Unoc...

Страница 12: ...figured with mode and fault priorities Table 4 illustrates that the lower the priority level number the higher the priority of the fault or mode There are some exceptions to this priority list For exa...

Страница 13: ...y adhere to field wiring procedures regarding proper lockout and tagout of components Figure 6 MicroTech III Unit Controller LED Status and Faults Troubleshooting Reference Flash Yellow LED Read Outpu...

Страница 14: ...pressor wiring for defective wiring or loose connection Check for faulty compressor capacitor Insufficient cooling or heating Check for lock rotor amp draw Check for defective compressor internal wind...

Страница 15: ...evice to drive a mechanical relay not supplied by Daikin then use the mechanical relay s dry contacts to drive the desired MicroTech III unit controller input The MicroTech III unit controller s valve...

Страница 16: ...R Dehumidification JP2 JP2 Open None default JP2 Shorted Hot Gas Water Reheat HGR Secondary Heating Options JP3 JP4 JP3 Open None JP4 Open JP3 Shorted Supplemental Electric Heat JP4 Open JP3 Open Boil...

Страница 17: ...xpansion Module and no electric heat it is possible to configure the I O Expansion Module for a two speed fan If there is a call for continuous fan compressor off the fan motor runs in low speed If th...

Страница 18: ...in 6 H8 Pin 1 Dual compressor compressor 2 normally open output all others fan medium speed normally open Pin 2 24 VAC common Pin 3 No connection Pin 4 Dual compressor reversing valve for circuit 2 al...

Страница 19: ...nit mounted return air discharge air and leaving water temperature sensor Wall mounted temperature sensors include setpoint adjustment and tenant override The user has the capability of substituting t...

Страница 20: ...he range 0 127 Four green status LEDs on the communication module indicate communication activity on the MS TP communication network and with the unit controller Figure 10 MicroTech III BACnet MS TP S...

Страница 21: ...emperature EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor CDS Condensate Ov...

Страница 22: ...ering Water Temperature EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor CDS...

Страница 23: ...d Entering Water Temperature EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor...

Страница 24: ...d with ECM and or Secondary Electric Heat Table B 208V RED 230V ORG 460V BLK RED Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor CDS Conden...

Страница 25: ...able B 208V RED 230V ORG Notes Transformer Unused wire to be capped Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor COS Condensate Overflow...

Страница 26: ...alve Capability Short Cycle Protection Random Start Unoccupied Mode Override Mode Pump Restart Loadshed Brownout Protection Unit Shutdown Condensate Overflow Protection Remote Reset 1 Intelligent Rese...

Страница 27: ...OM 931 6 MicroTech III Unit Controller for WSHP 27 www DaikinApplied com This page left intentionally blank...

Страница 28: ...o its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative go...

Отзывы: