4.4
Control network details
Peripheral Bus is used to connect I/O extensions to the main controller.
Controller/
Extension Module
Siemens Part Number
Address
Usage
Unit
POL687.70/MCQ
POL688.80/MCQ
n/a
Used on all configurations
Comp. #1
POL965.00/MCQ
2
EEXV #1
POL94U.00/MCQ
3
Comp. #2
POL965.00/MCQ
4
Used when configured for 2
EEXV #2
POL94U.00/MCQ
5
Fan#2
POL945.00/MCQ
6
Comp. #3
POL965.00/MCQ
7
Used when configured for 3
EEXV #3
POL94U.00/MCQ
8
Fan#3
POL945.00/MCQ
9
HP
POL925.00/MCQ
25
Heat Pump Option (old version)
HP
POL945.00/MCQ
26
Heat Pump Option (new version) +
Leak de Marine version.
Communication modules
The new Microtech 4 has the possibility to offer Modbus RTU and Bacnet (MSTP or IP) communications integrated in the
controller. To activate this feature a specific procedure is used to activate them. This procedure will ask for an activation
key to be entered as a setpoint. This will be done in the factory as part of the unit manufacturing or in the field by asking
for the activation code as a Spare part. Because these features may conflict with others (for example Bacnet IP and Daikin
on Site).
Any of the following modules can be connected directly to the left side of the main controller to allow a BAS interface to
function.
Module
Siemens Part Number
Usage
BacNet/IP
POL908.00/MCQ
Optional
Lon
POL906.00/MCQ
Optional
Modbus
POL902.00/MCQ
Optional
BACnet/MSTP
POL904.00/MCQ
Optional