Unit Options
www.DaikinApplied.com 61
IM 991-2 • MAVERICK II ROOFTOP
Entering Fan Temperature Sensor
The entering fan temperature (EFT) sensor and an associated “Lo
Airflow Problem” alarm are provided on VAV units with MicroTech
III control and gas or electric heat. The EFT sensor is located in
the supply fan section of the unit at the supply air funnel.
Heat is disabled whenever the airflow is detected to be too low
for safe heating operation. This condition is indicated when the
supply air temperature exceeds the mixed air temperature by
more than 60°F (16°C).
NOTE:
This value is not always 60°F. It depends on whether
the unit is gas or electric heat and on the burner/
baffling arrangement on gas heat units.
In this case, a “Lo Airflow Problem” alarm is
generated and heat is not enabled until the alarm
is manually cleared. Refer to the operation manual
supplied with the unit for information clearing alarms
).
Duct High Pressure Limit
The duct high pressure limit control (DHL) is provided on all
VAV units.The DHL protects the duct work, the terminal boxes,
and the unit from over pressurization, which could be caused
by, for example, tripped fire dampers or control failure.
The DHL control is factory set to open when the discharge
plenum pressure rises to 3.5" wc (872 Pa). This setting should
be correct for most applications; however, it is adjustable.
Removing the front cover of the device reveals a scale showing
the current setting. Turning the adjustment screw (located on
the bottom of the device) adjusts the setting up or down.
If the DHL switch opens, digital input MCB BI 14 on the Main
Control Board de-energizes. The MicroTech III controller then
shuts down the unit and enters the OFF-Alarm state. The
alarm must be manually cleared before the unit can start again.
Refer to the operation manual supplied with your unit for more
information on clearing alarms (
Variable Frequency Drive Operation
Refer to the vendor instructions supplied with the unit.
Содержание Maverick II MPS062E
Страница 45: ...Wiring Diagrams www DaikinApplied com 45 IM 991 2 MAVERICK II ROOFTOP Figure 45 MPS 070 Condensing Unit Power...
Страница 46: ...IM 991 2 MAVERICK II ROOFTOP 46 www DaikinApplied com Wiring Diagrams Figure 46 VFD Control...
Страница 47: ...Wiring Diagrams www DaikinApplied com 47 IM 991 2 MAVERICK II ROOFTOP Figure 47 VAV Control Inputs...
Страница 48: ...IM 991 2 MAVERICK II ROOFTOP 48 www DaikinApplied com Wiring Diagrams Figure 47 continued VAV Control Inputs...
Страница 49: ...Wiring Diagrams www DaikinApplied com 49 IM 991 2 MAVERICK II ROOFTOP Figure 48 Gas Burner Control...
Страница 50: ...IM 991 2 MAVERICK II ROOFTOP 50 www DaikinApplied com Wiring Diagrams Figure 48 continued Gas Burner Control...
Страница 51: ...Wiring Diagrams www DaikinApplied com 51 IM 991 2 MAVERICK II ROOFTOP Figure 49 Electric Heat Control...
Страница 52: ...IM 991 2 MAVERICK II ROOFTOP 52 www DaikinApplied com Wiring Diagrams Figure 49 continued Electric Heat Control...
Страница 119: ......