Unit Options
www.DaikinApplied.com 59
IM 991-2 • MAVERICK II ROOFTOP
External Time Clock
You can use an external time clock as an alternative to (or in
addition to) the MicroTech III controller’s internal scheduling
function. The external timing mechanism is set up to open
and close the circuit between field terminals 101 and 102.
When the circuit is open, power is not supplied to binary input
MCB-BI1. This is the normal condition where the controller
follows the programmable internal schedule. When the circuit
is closed, power is fed to BI1. The MicroTech III controller
responds by placing the unit in the occupied mode, overriding
any set internal schedule. For more information, see the
“Digital Inputs” section of
, “MicroTech III Applied
Rooftop Unit Controller.”
External Time Clock or Tenant Override
There are several methods of switching the rooftop unit between
occupied and unoccupied operation. It can be done by the
controller internal schedule, a network schedule, an external
time clock, or a tenant override switch. If the internal schedule or
a network schedule is used, field wiring is not required.
An external time clock or a tenant override switch can be used
by installing a set of dry contacts across terminals 101 and 102
on the field terminal block (TB2).When these contacts close,
24 V (ac) is applied to binary input MCB-DI3, overriding any
internal or network schedule and placing the unit into occupied
operation (provided the unit is not manually disabled). When
the contacts open (24 V (ac) is removed from MCB-DI3) the
unit acts according to the controller internal time schedule or a
network schedule. Refer to the unit wiring diagrams for specific
wiring termination details.
Figure 56: External Time Clock or Tenant Schematic
Содержание Maverick II MPS062E
Страница 45: ...Wiring Diagrams www DaikinApplied com 45 IM 991 2 MAVERICK II ROOFTOP Figure 45 MPS 070 Condensing Unit Power...
Страница 46: ...IM 991 2 MAVERICK II ROOFTOP 46 www DaikinApplied com Wiring Diagrams Figure 46 VFD Control...
Страница 47: ...Wiring Diagrams www DaikinApplied com 47 IM 991 2 MAVERICK II ROOFTOP Figure 47 VAV Control Inputs...
Страница 48: ...IM 991 2 MAVERICK II ROOFTOP 48 www DaikinApplied com Wiring Diagrams Figure 47 continued VAV Control Inputs...
Страница 49: ...Wiring Diagrams www DaikinApplied com 49 IM 991 2 MAVERICK II ROOFTOP Figure 48 Gas Burner Control...
Страница 50: ...IM 991 2 MAVERICK II ROOFTOP 50 www DaikinApplied com Wiring Diagrams Figure 48 continued Gas Burner Control...
Страница 51: ...Wiring Diagrams www DaikinApplied com 51 IM 991 2 MAVERICK II ROOFTOP Figure 49 Electric Heat Control...
Страница 52: ...IM 991 2 MAVERICK II ROOFTOP 52 www DaikinApplied com Wiring Diagrams Figure 49 continued Electric Heat Control...
Страница 119: ......