14
|
About the units and options
Installer and user reference guide
43
LRYELRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4P605460-1 – 2020.08
14.2.1 Labels on outdoor unit
Label about flow directions
Text on caution label
Translation
from LRYEN10A7Y1 to Refrigeration
From LRYEN10A7Y1 to Refrigeration
Gas for Airco
Gas for Airco
Liquid for Airco
Liquid for Airco
Gas from Refrigeration
Gas from Refrigeration
Liquid to LRNUN5A7Y1 or to
Refrigeration
Liquid to LRNUN5A7Y1 or to
Refrigeration
Label about safety valve
WARNING
Unit is charged and under high pressure.
Set pressure of safety valve is
86 bar g
.
If refrigerant temperature is higher than
31°C
there is a possibility that the safety valve will
open during service or power shutdown.
Text on warning label
Translation
Unit is charged and under high
pressure.
Unit is charged and under high
pressure.
Set pressure of safety valve is 86 bar g.
Set pressure of safety valve is
86 bar g
.
If refrigerant temperature is higher than
31°C there is a possibility that the safety
valve will open during service or power
shutdown.
If refrigerant temperature is higher than
31°C
there is a possibility that the safety
valve will open during service or power
shutdown.
Check the set pressure of the safety valve at the low pressure side of the
refrigeration cabinet to verify a safe service temperature.
"16.3.8 Guidelines to install safety valves"
83].