Installation manual

13

20B7Y1R

Air cooled refrigeration condensing unit

4P360438-1B – 2014.01

• Use a T-joint for the gas refrigerant branch and connect from the 

top of the main piping.

• Make sure that the horizontal portion of the gas piping slants 

downward to the outdoor unit (see the illustration above).

• If the outdoor unit is located above, make a trap on the gas pipe at 

5 m intervals from outdoor unit. This will ensure the smooth 
returning of oil in the piping slanting upward.

Gas piping

• Make sure that the horizontal run of the gas piping slants 

downward to the outdoor unit.

• In order to prevent oil retention, do not make a trap in the horizontal 

run of the gas piping.

7. FIELD WIRING

To electric engineering contractors

• Be sure to install an earth leakage breaker. The product 

incorporates inverter equipment. In order to prevent the 
malfunctioning of the earth leakage breaker, make sure that the 
earth leakage breaker withstands harmonic interference.

• Do not operate the condensing unit until refrigerant piping work is 

completed, or otherwise the compressor will malfunction.

• Do not remove any electrical components such as thermistors or 

sensors when connecting power supply wires or transmission 
wires. The compressor may malfunction if the condensing unit is 
operated with such electrical components removed. 

CAUTION

• All field wiring and components must be installed by a licensed 

electrician and must comply with relevant local and national 
regulations.

• Be sure to use a dedicated power circuit. Never use a power supply 

shared by another appliance.

• Never install a phase advancing capacitor. As this unit is equipped 

with an inverter, installing a phase advancing capacitor will not only 
deteriorate power factor improvement effect, but also may cause 
capacitor abnormal heating accident due to high-frequency waves.

• Only proceed with wiring work after blocking off all power.
• Always ground wires in accordance with relevant local and national 

regulations.

• This machine includes an inverter device. Connect earth and leave 

charge to eliminate the impact on other devices by reducing noise 
generated from the inverter device and to prevent leaked current 
from being charged in the outer hull of the product.

• Do not connect the ground wire to gas pipes, sewage pipes, 

lightning rods, or telephone ground wires.

Gas pipes:

 can explode or catch fire if there is a gas leak.

Sewage pipes:

 no grounding effect is possible if hard plastic 

piping is used.

Telephone ground wires and lightning rods:

 dangerous when 

struck by lightning due to abnormal rise in electrical potential in the 
grounding.

• Be sure to install an earth leakage circuit breaker.

This unit uses an inverter, so install the earth leakage circuit 
breaker that be capable of handling high harmonics in order to 
prevent malfunctioning of the earth leakage circuit breaker itself.

• Earth leakage circuit breaker which are especially for protecting 

ground-faults should be used in conjunction with main switch or 
fuse for use with wiring.

• Electrical wiring must be done in accordance with the wiring 

diagrams and the description herein.

• Do not operate until refrigerant piping work is completed.

(If operated before complete the piping work, the compressor may 
be broken down.)

• Never remove thermistor, sensor or etc. when connecting power 

wiring and transmission wiring.
(If operated with thermistor, sensor or etc. removed, the 
compressor may be broken down.)

• This product have reversed phase protection detector that only 

works when the power is turned on. If there exists black out or the 
power goes on and off which the product is operating, attach a 
reversed phase protection circuit. Running the product in reversed 
phase may break the compressor and other parts.

• Attach the power wire securely. Introducing power with a missing 

N-phase or with a mistaken N-phase will break the unit.

• Never connect the power supply in reversed phase. 

The unit can not operate normally in reversed phase.
If you connect in reversed phase, replace two of the three phases.

• Make sure the electrical unbalance ratio is no greater than 2%. If it 

is larger than this, the unit’s lifespan will be reduced.
If the ratio exceeds 4%, the unit will shut down and an malfunction 
code will be displayed on the indoor remote controller.

• Connect the wire securely using designated wire and fix it with 

attached clamp without applying external pressure on the terminal 
parts (terminal for power wiring, terminal for transmission wiring 
and earth terminal).

• Install a switch that allows you to switch OFF all poles from the 

main power supply.

7-1 Example of wiring entire system 

1

3 phase 50 Hz 380~415 V
Earth leakage circuit breaker (high-frequency type) (for earth 
fault, overload, and short-circuit protection)

2

Master units

3

Slave unit

T-joint

Main piping

Indoor unit side

Outdoor unit side

Branch piping

Make the piping 
slant downward

Branch piping

Make the piping 
slant downward

Main piping
Make the piping 
slant downward

T-joint

Ry1

Relay

S1T

Thermostat for inner temperature adjustment

Y1S

Solenoid valve

Note: 1.  In case of used remote switch, use dry contact for microcurrent  

(not more than 1mA, 12VDC).

Note: 2.  Total capacity for caution, warning : 0.5A or less at AC 220 to 240V.

Capacity for operation output run output : 0.5A or less at AC 220 to 240V.

2

X3M

1

X1M(A1P)

Q1

X1M(A1P)

Q2

Q2

Q1

L3

C

L2

X1M

L1

A

X1M

N

B

L1

L2

X1M(A5P)

W1

N

L3

Ry1

Ry1

P1

P2

R

C1

C

2

7

9

3

1

10

11

5
6

8

12

13

4

S1T

Y1S

Содержание LREQ15B7Y1R

Страница 1: ...INSTALLATION MANUAL LREQ15B7Y1R LREQ20B7Y1R Air cooled refrigeration condensing unit...

Страница 2: ...jennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jot...

Страница 3: ...PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksima...

Страница 4: ...accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or fire When installing the unit in a small room take measures so that t...

Страница 5: ...containing less than 95 kg refrigerant charge CAUTION This unit is already filled with a certain amount of R410A Never open liquid and gas shutoff valve until the step specified in 9 CHECKS AFTER WOR...

Страница 6: ...ber of indoor units be sure to install them at the same level Use either off cycle defrosting or electric heater defrosting as the defrosting type Hot gas defrosting models cannot be used Make sure th...

Страница 7: ...for front side no higher than 1500 mm Wall height on the suction side no higher than 500 mm Wall height for sides no limit Make sure each unit is installed level Install the slave unit adjacent to the...

Страница 8: ...See Engineering Data for details 5 If the outdoor units are installed in areas with heavy snowfall the installation of a snowbreak hood is required This is available as an optional accessory If the un...

Страница 9: ...hen installing on a roof make sure the roof floor is strong enough and be sure to water proof all work Make sure the area around the machine drains properly by setting up drainage grooves around the f...

Страница 10: ...used is clean and free of contaminants such as sulphur oxide dust chips oil and fat and water It is desirable that the maximum oil adhesion in the piping is 30 mg per 10 m Use the following type of re...

Страница 11: ...f indoor units connected downstream Total capacity of indoor units after branching Liquid pipe size less than 4 0 kW 6 4 x 0 8 O type 4 0 kW over and less than 14 0 kW 9 5 x 0 8 O type 14 0 kW over an...

Страница 12: ...plete Wait until all oil is dripped out 7 Cut the pinched piping off with a pipe cutter just above the brazing point or just above the marking in case there is no brazing point 8 Wait until all oil is...

Страница 13: ...t to the valve cover mount and the screw thread of the service port Otherwise dew condensation water will intrude inside and freeze Therefore refrigerant gas leakage or a compressor malfunction may re...

Страница 14: ...nnected at the lateral side bottom CAUTION Only use the dedictated outdoor unit multi connection piping kit EKHRQZM When brazing make sure there are no flammable materials around 1 Connect gas side ac...

Страница 15: ...oisture Follow instructions in the dryer instruction manual concerning dryer brazing Repair any burning of dryer paint that occurs during dryer brazing Contact the manufacturer for more information ab...

Страница 16: ...to install an earth leakage circuit breaker This unit uses an inverter so install the earth leakage circuit breaker that be capable of handling high harmonics in order to prevent malfunctioning of the...

Страница 17: ...field supply 7 3 Procedure for power supply wiring Procedure for Power Supply Wiring 1 Power supply 3 phase 50 Hz 380 415 2 Overcurrent circuit breaker earth leakage circuit breaker all pole disconne...

Страница 18: ...stem on page 13 by all means when connecting the operation output wiring A compressor failure may result if the operating output wiring is not connected Remote switch wiring connections When installin...

Страница 19: ...ut operation output wiring from the front 10 When routing remote operating switch wiring from the front 11 Remote switch terminal block X3M 12 When routing remote switch wiring through a wiring openin...

Страница 20: ...e the outdoor unit for one hour and then check that the reading on the vacuum gauge is not rising If the reading on the vacuum gauge is rising water may be remaining in the system or leakage may be oc...

Страница 21: ...page 19 see the illustrations below Use the piping outlet for jobs required during the steps of 10 REFRIGERANT REPLENISHMENT on page 19 e g a job of taking in the charge hose Note After knocking out t...

Страница 22: ...n operation d Turn off the operation switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the g...

Страница 23: ...in ballpoint or another non conducting object Close the inspection door after the work is finished A Inspection hole upper left B Inspection hole upper right 1 Inspection door left 2 Lift to open 3 Op...

Страница 24: ...malfunction code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts b...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...4P360438 1B 2014 01 Copyright 2013 Daikin 4P360438 1 B 0000000_...

Отзывы: