background image

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74303-1C – 2016.02

Operation manual

6

10. AFTER-SALE SERVICE

10-1 After-sale service

WARNING

Consult your local dealer regarding modification, repair and 
maintenance of the condensing unit.

Improper workmanship may result in water leakage, electric shocks 

or fire hazards.

Consult your local dealer regarding relocation and 

reinstallation of the condensing unit.

Improper installation work may result in leakage, electric shocks or 

fire hazards.

Beware of fire in case of refrigerant leakage.

If the condensing unit is not operating correctly (i.e. the interior 

temperature of the condensing unit does not drop efficiently), 

refrigerant leakage could be the cause. 

 

Consult your dealer for assistance. 

 

The refrigerant used for the condensing unit is safe and normally 

does not leak.

 

However, if the refrigerant leaks and gets in contact with a naked 

burner, heater or cooker, it may generate hazardous compounds. 

Turn off the condensing unit and call the dealer. Make sure to turn 

on the condensing unit after the qualified service person confirms 

that the leakage is repaired.

1. Inform your dealer of the following items when you request 

repairs.

Model name

Described in the warranty card.

Serial number and date of installation

 

Described in the warranty card.

Defective condition – as precise as possible

Your address, name, and telephone number

2. Repairs after expiration of warranty period

Consult your dealer. Onerous repairs will be possible if the unit 
can maintain its original functions after the repairs are made.

3. Maintenance inspection

The interior of the refrigeration condensing unit will become dirty 
and its performance may be degraded if it is used for several 
seasons.
We recommend to check all pressure containing parts yearly. In 
case of corrosion, contact your dealer.
The disassembly and internal cleaning of the unit requires 
specialized techniques. Therefore, our dealer recommends an 
onerous maintenance inspection besides usual maintenance 
services.
For details, consult your dealer.
Keep in mind that our dealer’s warranty may not cover 
malfunctions resulting from the disassembly or internal cleaning 
of the unit conducted by contractors not authorized by our dealer.

4. Relocation and disposal

Contact your dealer for removing and reinstalling the system 
condensing unit since they require technical expertise.

The system condensing unit uses fluorocarbon refrigerant.

 

Contact your dealer for discarding the system condensing unit 
since it is required by law to collect, transport and discard the 
refrigerant in accordance with relevant local and national 
regulations.

In either case, consult your dealer.

5. Inquiries

Contact your dealer for after-sale services.

10-2 Onerous repairs 

 

(Outside scope of warranty coverage)

10-2-1

Accidents resulting from use beyond standards 
for use

Use beyond Limits

Applications other than its designed purpose of use or modification.

Standards for use

Condensing unit 

Restrictions for the refrigeration-side 

Note:

*1

. Connection piping length differs according to set value of 

evaporating temperature.

 

Set the total value of the internal volume for the evaporator 
(refrigerator/freezer) to connect and the amount of refrigerant 
inside the evaporator that can be recovered in the condensing unit 
by closing the liquid solenoid valve installed on the 
refrigeration-side to the below amount or lower.
LREQ5, 6:

22 l

LREQ8, 10, 12:

33 l

LREQ15, 20:

42 l

*2

. When the outdoor temperature is lower than evaporating 

temperature, evaporating temperature is lower than set 
evaporating temperature

*3

. Trap is required at 5 m intervals from outdoor unit.

Item

Standard for use

Refrigerant

R410A

Refrigeration oil

Daphne FVC68D

Range of evaporating 
temperature (Te)

–45°C ~ +10°C (

*2

)

Range of outdoor temperature

–20°C ~ +43°C

Suction gas superheated degree

10 K or higher

Suction gas temperature

20°C or lower

Power supply 

Voltage 
regulation

within ±10% of rated 
voltage

Voltage 
imbalance 
rate

within ±2% of rated voltage

Frequency 
regulation

within ±2% of rated 
frequency

Compressor ON/OFF frequency

6 times or less/hour

Connection piping length (piping 
equivalent length) (

*1

)

130 m or lower

 

(Te = –20°C ~ +10°C)
100 m or lower

 

 (Te = –45°C ~ –20°C)

Max. difference in height 
between indoor and outdoor 
units

35 m or lower (

*3

)

 

(When the condensing unit 
is installed higher than the 
refrigeration-side)
10 m or lower

 

(When the condensing unit 
is installed lower than the 
refrigeration-side)

Installation space

According to the 
installation service space

Connectable 
minimum load 
capacity

2.0 kW or higher (Te = –20°C ~ +10°C)

 

1.6 kW or higher (Te = –45°C ~ –20°C)

Liquid solenoid 
valve installed 
upstream of 
expansion valve

For R410A, maximum operating pressure 
difference: 3.5 MPa or higher
It is necessary to control the solenoid 
valves in indoor unit using “Operate unit” of 
outdoor unit

Defrost method

Hot gas defrost not possible
After defrosting ends, resume operation of 
the refrigeration-side blower within 3 
minutes or less

Restrictor

Use a thermal expansion valve for R410A

4PWEN74303-1C.book  Page 6  Thursday, March 10, 2016  10:59 AM

Содержание LREQ10B7Y1

Страница 1: ...OPERATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit 4PWEN74303 1C book Page 1 Thursday March 10 2016 10 59 AM...

Страница 2: ...l dealer about installation work Doing the work yourself may result in water leakage electric shocks or fire hazards Consult your local dealer regarding modification repair and maintenance of the cond...

Страница 3: ...a danger of flammable gas leakage In the event of a gas leakage build up of gas near the condensing unit may result in fire hazards Perform drain piping to ensure perfect drainage Imperfect drainage m...

Страница 4: ...6 hours before resuming the operation of the unit Note The power consumption of the unit varies with the operating factors such as the condensing unit model 5 2 Install an alarm if operational errors...

Страница 5: ...dealer for the replacement of the power supply fuse Is the power circuit breaker not turned off Turn on the power if the knob of the power circuit breaker is set to the OFF position Do not turn on th...

Страница 6: ...e target evaporating temperature set for the protection of the unit Model LREQ5 LREQ6 LREQ8 LREQ10 LREQ12 LREQ15 LREQ20 Power supply 3 phase 50 Hz 380 415 V Refrigerant R410A Operating condition Evapo...

Страница 7: ...nt Contact your dealer for discarding the system condensing unit since it is required by law to collect transport and discard the refrigerant in accordance with relevant local and national regulations...

Страница 8: ...ion work The use of the unit beyond the operating temperature range as a result of on site modification An accident resulted from the improper handling of the unit under installation work The loosenin...

Страница 9: ...4PWEN74303 1C book Page 1 Thursday March 10 2016 10 59 AM...

Страница 10: ...4PWEN74303 1C book Page 2 Thursday March 10 2016 10 59 AM...

Страница 11: ...4PWEN74303 1C book Page 3 Thursday March 10 2016 10 59 AM...

Страница 12: ...4PW74303 1C 2016 02 Copyright 2012 Daikin 4PW74303 1 C 0000000L 4PWEN74303 1C book Page 1 Thursday March 10 2016 10 59 AM...

Отзывы: