Air cooled refrigeration condensing unit

4P360438-1B – 2014.01

Installation manual

16

Precautions for terminal connections

• Be sure to use ring-type crimp-style terminals provided with 

insulation sleeves.

• Use specified electric wires for the wiring and secure the wiring so 

that external force will not be imposed on the terminal block.

• Use an appropriate screwdriver to tighten the terminal screws.

Small-sized screwdriver will damage the screw heads and cannot 
tighten the screws properly.

• Do not tighten the terminal screws in excess, otherwise the screws 

may be damaged.

• Refer to the following table for the tightening torque values of the 

terminal screws.

• Take out the earth wire from the notch of the cup washer and lay 

the wire carefully so that other wires will not be caught by the 
washer. Otherwise, the earth wire may not contact sufficiently and 
the earthing effect of the wire may be lost.

• Do not finish strand wire with solder.

7-4 Procedure for wiring inside units

• Referring to the following figure, secure and wire the power and 

transmission wiring using the accessory clamp (1), (2).

• Lay the ground wire so that it will not come in contact with the lead 

wires of the compressor. Other equipment will be adversely 
affected if the ground wire comes in contact with the lead wires of 
the compressor.

• Make sure all wiring do not contact to the pipes (hatching parts in 

the figure).

• The transmission wiring must be at least 50 mm away from the 

power wiring.

• After wiring work is completed, check to make sure there are no 

loose connections among the electrical parts in the control box.

LREQ15-20

1

Conduit

2

Perform wiring carefully so that the wiring will not come in contact 
with the port and

 part.

3

When routing high-voltage wiring (power supply wiring, earth 
wires, and warning/caution/run input, operation output wiring) 
from the left side

4

Connecting local piping

5

Power supply terminal block (X1M)

6

X2M terminal block for warning, caution, run input, and operation 
output

7

Earth terminal block

8

When routing high-voltage wiring (power supply wiring, earth 
wires, and warning/caution/run input, operation output wiring) 
from the right side

9

When routing high-voltage wiring (power supply wiring, earth 
wires, and warning/caution/run input, operation output wiring) 
from the front

10

When routing remote operating switch wiring from the front.

11

Remote switch terminal block (X3M)

12

When routing remote switch wiring through a wiring opening

13

Separate by at least 50 mm

14

Fixed to the rear side of the support with the provided clamp (2)

15

Perform wiring carefully so that the sound insulation of the 
compressor will not come off

16

Support

CAUTION

On completion of electrical work, check that there are no disconnected 
connectors or terminals of any electrical parts in the control box.

8. INSPECTION AND PIPE INSULATION

For piping work contractor, electrical work contractor, 
and trial run workers

• Never open the shutoff valve until the insulation measurement of 

the main power supply circuit is finished. The measured insulation 
value will become lower if the measurement is made with the 
shutoff valve opened.

• On completion of inspection and refrigerant charging, open the 

shutoff valve. The compressor will malfunction if the condensing 
unit is operated with the shutoff valve closed.

8-1 Airtight test/refrigerant oil charging/vacuum 

drying

Refrigerant is enclosed in the unit.
Be sure to keep both liquid and gas shutoff valves 
closed at the time of an airtight test or vacuum drying of 
the local piping.

[For piping work contractor]

On completion of piping work, make the following inspection precisely.

• To ensure that the condensing unit withstand pressure properly 

and prevent the penetration of foreign substances, be sure to use 
R410A-dedicated tools.

Screw size

Tightening torque (N•m)

M8 (Power supply terminal block)

5.5 - 7.3

M8 (Earth)
M4 (X2M)

2.39 - 2.91

M3.5 (X3M)

0.79 - 0.97

Crimp-style terminal

Insulating sleeve

Power wire

Crimp-style terminal

Cup washer

Cut out section 

8

11

12

13

15

16

9

6

X1M

X1M

X3M

A5P

A1P

X2M

14

3

1

2

10

5

4

7

13

14

Gauge manifold
Charge hose

• To ensure that the condensing unit withstand 

pressure properly and prevent the 
penetration of foreign substances (water, 
dirt, and dust), use an R410A-dedicated 
gage manifold and charge hose. 
R410A-dedicated tools and 
R407C-dedicated tools are different in screw 
specification.

Vacuum pump

• Pay the utmost attention so that the pump oil 

will not flow backward into the system while 
the pump is not in operation.

• Use a vacuum pump that can vacuum down 

to –100.7kPa (5 Torr or –755 mmHg).

Gas for airtight 
test use

• Nitrogen gas

Refrigerant oil

Daphne FVC68D
Only use the refrigerant oil listed in the Daikin 
sevice parts list.

Содержание LREQ-BY1R

Страница 1: ...INSTALLATION MANUAL LREQ15B7Y1R LREQ20B7Y1R Air cooled refrigeration condensing unit ...

Страница 2: ...ifikatet C i enlighet med den Tekniska Konstruktionsfilen D som positivt intygats av E Fastsatt modul F G Riskkategori H Se även nästa sida 12 som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bedømmelse av E Anvendt modul F G Risikokategori H Se også neste side 13 jotka on esitetty asiakirjassa A...

Страница 3: ... bar Минимално максимално допустима температура TS TSmin Минимална температура от страната на ниското налягане L C TSmax Температура на насищане съответстваща на максимално допустимото налягане PS M C Охладител N Настройка на предпазното устройство за налягане P bar Фабричен номер и година на производство вижте табелката на модела 22 Maksimalus leistinas slėgis PS K bar Minimali maksimali leistina...

Страница 4: ...n accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer for further information If the refrigerant leaks and exceeds the limiting concentratio...

Страница 5: ...h containing less than 95 kg refrigerant charge CAUTION This unit is already filled with a certain amount of R410A Never open liquid and gas shutoff valve until the step specified in 9 CHECKS AFTER WORK COMPLETION on page 18 The refrigerant R410A requires that strict precautions be observed for keeping the system clean dry and tightly sealed Read the chapter 6 REFRIGERANT PIPING on page 6 carefull...

Страница 6: ...mber of indoor units be sure to install them at the same level Use either off cycle defrosting or electric heater defrosting as the defrosting type Hot gas defrosting models cannot be used Make sure the total internal volume of indoor units connected to the condensing units is 80 l or lower Starting from an outdoor temperature of 32 C the total indoor unit capacity needs to be 50 or more of the to...

Страница 7: ... for front side no higher than 1500 mm Wall height on the suction side no higher than 500 mm Wall height for sides no limit Make sure each unit is installed level Install the slave unit adjacent to the master unit Make sure the slave unit faces the same direction as the master unit Provide enough space for maintaining and servicing the units Provide adequate space for the air in and outlets Make s...

Страница 8: ... See Engineering Data for details 5 If the outdoor units are installed in areas with heavy snowfall the installation of a snowbreak hood is required This is available as an optional accessory If the units are installed in a location where the ambient temperature can drop below 10 C install a windbreak board or a snowbreak hood 1 Snowbreak hood installation Required parts 2 Windbreak board installa...

Страница 9: ...When installing on a roof make sure the roof floor is strong enough and be sure to water proof all work Make sure the area around the machine drains properly by setting up drainage grooves around the foundation Drain water is sometimes discharged from the outdoor unit when it is running If the condensing unit is of brine damage resistant or heavy brine damage resistant type use nuts provided with ...

Страница 10: ...sed is clean and free of contaminants such as sulphur oxide dust chips oil and fat and water It is desirable that the maximum oil adhesion in the piping is 30 mg per 10 m Use the following type of refrigerant piping Material Seamless phosphorus deoxidized copper tube C1220T O for a maximum outer diameter of 15 9 mm and C1220T 1 2H for a minimum outer diameter of 19 1 mm Refrigerant piping size and...

Страница 11: ...or units connected downstream Total capacity of indoor units after branching Liquid pipe size less than 4 0 kW Ø6 4 x 0 8 O type 4 0 kW over and less than 14 0 kW Ø9 5 x 0 8 O type 14 0 kW over and less than 30 0 kW Ø12 7 x 0 8 O type 30 0 kW over and less than 50 0 kW Ø15 9 x 1 0 O type 50 0 kW or over Ø19 1 x 1 0 O type Total capacity of indoor units after branching Gas pipe size Medium temperat...

Страница 12: ...mplete Wait until all oil is dripped out 7 Cut the pinched piping off with a pipe cutter just above the brazing point or just above the marking in case there is no brazing point 8 Wait until all oil is dripped out in case the recovery was not complete and only then proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above mark...

Страница 13: ... to the valve cover mount and the screw thread of the service port Otherwise dew condensation water will intrude inside and freeze Therefore refrigerant gas leakage or a compressor malfunction may result from the cap deformation or damage 3 Connecting refrigerant piping to outdoor units Use the outdoor unit multi connection piping kit EKHRQZM to split up the gas piping and connect it to the differ...

Страница 14: ...onnected at the lateral side bottom CAUTION Only use the dedictated outdoor unit multi connection piping kit EKHRQZM When brazing make sure there are no flammable materials around 1 Connect gas side accessory pipes 1 to field supplied branch pipes Gas side accessory pipes 1 are supplied with the outdoor units 2 Connect gas side accessory pipes 1 to the gas side shutoff valves 1 Gas side accessory ...

Страница 15: ...moisture Follow instructions in the dryer instruction manual concerning dryer brazing Repair any burning of dryer paint that occurs during dryer brazing Contact the manufacturer for more information about paint for repair use Flow direction is specified for some type of the dryer Set the flow direction according to the operation manual of the dryer Install the dryer on the main liquid pipe Sight g...

Страница 16: ... to install an earth leakage circuit breaker This unit uses an inverter so install the earth leakage circuit breaker that be capable of handling high harmonics in order to prevent malfunctioning of the earth leakage circuit breaker itself Earth leakage circuit breaker which are especially for protecting ground faults should be used in conjunction with main switch or fuse for use with wiring Electr...

Страница 17: ...l field supply 7 3 Procedure for power supply wiring Procedure for Power Supply Wiring 1 Power supply 3 phase 50 Hz 380 415 2 Overcurrent circuit breaker earth leakage circuit breaker all pole disconnection switch 3 Earth wire 4 Power supply terminal block 5 Mount insulation sleeves 6 Fix the power supply wiring for phases L1 L2 L3 and N respectively with the provided clamp 1 to the resin clamp 7 ...

Страница 18: ...stem on page 13 by all means when connecting the operation output wiring A compressor failure may result if the operating output wiring is not connected Remote switch wiring connections When installing a remote switch clamp as indicated by the following diagram This connection is only required for the master unit X3M wire specifications Wiring connection for low noise mode Wiring connection for lo...

Страница 19: ...put operation output wiring from the front 10 When routing remote operating switch wiring from the front 11 Remote switch terminal block X3M 12 When routing remote switch wiring through a wiring opening 13 Separate by at least 50 mm 14 Fixed to the rear side of the support with the provided clamp 2 15 Perform wiring carefully so that the sound insulation of the compressor will not come off 16 Supp...

Страница 20: ...unit for one hour and then check that the reading on the vacuum gauge is not rising If the reading on the vacuum gauge is rising water may be remaining in the system or leakage may be occurring In that case perform necessary repair and then conduct the air tightness test again 1The design pressure of the indoor unit locally procured needs to be 2 5 MPa or more Contact the manufacturer in advance f...

Страница 21: ... page 19 see the illustrations below Use the piping outlet for jobs required during the steps of 10 REFRIGERANT REPLENISHMENT on page 19 e g a job of taking in the charge hose Note After knocking out the holes we recommend you remove burrs in the knock holes and paint the edges and areas around the edges using the repair paint Make sure there is no gap in the Y joint 8 3 Checking of device and ins...

Страница 22: ...operation d Turn off the operation switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly Otherwise a piping explosion may result from liquid sealing Label pasting position z 1 Master unit 2 Additional refrigerant charge label 3 Additional refrigerant oil label 4...

Страница 23: ...sin ballpoint or another non conducting object Close the inspection door after the work is finished A Inspection hole upper left B Inspection hole upper right 1 Inspection door left 2 Lift to open 3 Operation switch S1S 4 Electric component box cover 5 LED H1P H7P 6 Push button switch BS1 BS5 7 DIP switch DS1 DS2 8 Inspection door right Making field settings Settings are made on the master unit on...

Страница 24: ... malfunction code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking 3 Press the RETURN button BS3 to display the first digit of the malfunction code on the LED 4 Press the SET button BS2 to display the second digit of the malfunction code on the LED 5 Press t...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...4P360438 1B 2014 01 Copyright 2013 Daikin 4P360438 1 B 0000000_ ...

Отзывы: