SiBE041025
Control Specification
Function and Control
33
2.13 Forced Operation Mode
Outline
Forced operation mode includes only forced cooling.
Detail
Item
Forced Cooling
Conditions
1) The outdoor unit is not abnormal
and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
The forced operation is allowed when
the above both conditions are met.
Start
Press the forced operation ON/OFF
button (SW1) on the indoor unit for 5
seconds.
Command
frequency
58 Hz
End
1) Press the forced operation
ON/OFF button (SW1) on the indoor
unit again.
2) Press the ON/OFF button on the
remote controller.
3) The operation ends automatically
after 15 minutes.
Others
The protection functions are prior to all
others in the forced operation.