background image

IOM 1322-1 • WATER-COOLED SCROLL COMPRESSOR 68 www.DaikinApplied.com

Unit Maintenance 

System Maintenance

To provide smooth operation at peak capacity and to avoid 

damage to package components, a program of periodic 

inspections should be set up and followed. The following items 

are intended as a guide to be used during inspection and must 

be combined with sound refrigeration and electrical practices to 

provide trouble-free performance.
The liquid line sight glass/moisture indicator on all circuits must 

be checked to be sure that the glass is full and clear and that 

the moisture indicator indicates a dry condition. If the indicator 

shows that a wet condition exists or if bubbles show in the 

glass, even with a full refrigerant charge, the filter-drier element 

must be changed.
Water supplies in some areas can tend to foul the water-cooled 

condenser to the point where cleaning is necessary. The fouled 

condenser will be indicated by an abnormally high condenser 

approach temperature (saturated discharge temperature 

minus leaving condenser water temperature) and can result 

in nuisance trip-outs. To clean the condenser, mechanical 

cleaning or a chemical descaling solution should be used 

according to the manufacturer’s directions. The condenser flow 

sensor should be cleaned anytime the condenser is opened. 

This should typically be performed at the annual inspection; 

however, more frequent cleaning may be required depending 

on the conditions of the jobsite.

Recommended condenser flow sensor maintenance includes 

the following:

•  Check the sensor tip for buildup.
•  Clean the tip using a soft cloth. Stubborn buildup - such 

as lime - can be removed using a common vinegar 

cleaning agent.

The compressor oil level must be checked periodically to be 

sure that the level is at the center of the oil sightglass located 

in the compressor’s equalizing line or on the compressor itself 

Low oil level can cause inadequate lubrication and if oil must 

be added, use oils referred to in the following Compressor 

Lubrication section.
A pressure tap has been provided on the liquid line 

downstream of the filter-drier and solenoid valve but before the 

expansion valve. An accurate subcooled liquid pressure and 

temperature can be taken here. The pressure read here could 

also provide an indication of excessive pressure drop through 

the filter-drier and solenoid valve due to a clogging filter-drier. 

Note: A normal pressure drop through the solenoid valve is 

approximately 3 psig (20.7 kPa) at full load condition.

 DANGER

LOCKOUT/TAGOUT

 all power sources prior to servicing the unit. 

Disconnect all power before doing any service inside the unit or serious 

personal injury or death can occur. The panel is always energized to ground 

even when the system switch is off. To de-energize the complete panel 

including crankcase heaters, pull the main unit disconnect. Be sure to read 

and understand the installation, operation, and service instructions within 

this manual.

 CAUTION

Warranty may be affected if wiring is not in accordance with specifications. 

A blown fuse or tripped protector indicates a short ground or overload. 

Before replacing fuse or restarting compressor, the trouble must be found 

and corrected. It is important to have a qualified control panel electrician 

service  this  panel.  Unqualified  tampering  with  the  controls  can  cause 

serious damage to equipment and void the warranty. If motor or compressor 

damage is suspected, do not restart until qualified service personnel have 

checked the unit.

All power electrical terminals should be checked for proper 

torque every six months, as they tend to loosen due to normal 

heating and cooling of the wire.

Compressor Lubrication

The oil level should be watched carefully upon initial start-up 

and regularly thereafter.
All tandem and trio compressors on WGZ units come equipped 

with oil equalization lines connecting the crankcase of each 

set of compressors in each refrigerant circuit. This allows 

the oil to move from one compressor crankcase to the other 

during normal operation, and balance between the two when 

the compressors are off. The oil sight glass is located in the 

equalization line on or on the compressor body depending on 

model size. In either case, the oil level should be 1/4 to 1/3 of 

the glass.
POE type oil is used for compressor lubrication. This type of 

oil is extremely hygroscopic, which means it will quickly absorb 

moisture if exposed to air and may form acids that can be 

harmful to the chiller. Avoid prolonged exposure of POE oil 

to the atmosphere to prevent this problem. For more details 

on acceptable oil types, contact your Daikin Applied service 

representative.
The units are factory-charged with lubricant. It is important that 

only the manufacturer’s recommended oils be used Acceptable 

POE oil types are:

•  CPI/Lubrizol Emkarate RL32-3 MAF
•  Copeland Ultra 32-3 MAF
•  Parker Emkarate RL32-3MAF
•  Virginia LE323MAF
•  Nu Calgon 4314-66
•  Exxon/Mobil EAL Arctic 22 CC*
• 

Hatcol 22CC*

•  Everest 22CC*

NOTE: 

These types of oils can only be used as “Top Off” oils. 

Oil can be added to the compressor through the oil fill 

hole in the crankcase. Special equipment is required 

to add oil and the work should be done by qualified 

refrigeration technicians with the proper training and 

equipment.

 WARNING

POE oil must be handled carefully using proper protective equipment 

(gloves, eye protection, etc.) The oil must not come in contact with certain 

polymers (e.g. PVC), as it may absorb moisture from this material. Also, do 

not use oil or refrigerant additives in the system.

Unit Maintenance 

Содержание IOM 1322-1

Страница 1: ...ion and Maintenance Manual Water Cooled Scroll Compressor Chillers WGZ030DW WGZ200DW Packaged Water Cooled Chillers 30 200 Tons 105 700 kW R 410A 50 60 Hz IOM 1322 1 Group Chiller Part Number IOM1322...

Страница 2: ...iderations 8 Condenser Water Piping 10 Packaged Unit Refrigerant Piping 11 Relief Valve Piping 12 Water Pressure Drop 12 Dimensions and Weights Packaged Units 16 Isolator Information 21 Physical Data...

Страница 3: ...artup Oil heaters energized at least 12 hours before startup Chiller components EXV Sensors Transducers installed and wired properly Wiring complies with National Electrical Code and local codes See N...

Страница 4: ......

Страница 5: ...trical charge builds when halo carbon refrigerant travels in a rubber hose A grounding strap must be used between the auxiliary refrigerant tank and the chiller s end sheet earth ground which will saf...

Страница 6: ...is not the responsibility of Daikin Applied Refrigerant Charge Every model WGZ DW water chiller with water cooled condensers is shipped with a full refrigerant charge For shipment the charge is contai...

Страница 7: ...oving always apply pressure to the base on the skids only and not to the piping or other components A long bar will help move the unit Avoid dropping the unit at the end of the roll If the unit must b...

Страница 8: ...d insulation thickness for accessibility It is recommended that the field installed water piping to the chiller include Some means of maintaining adequate system water pressure e g expansion tank or r...

Страница 9: ...hot metal is dipped into the water tank Then the load would increase drastically Since there are many other factors that can influence performance systems can successfully operate below these suggesti...

Страница 10: ...temperature from 15 F 9 4 C to 60 F 16 C Leaving chilled fluid temperatures below 40 F 4 6 C result in suction temperatures at or below the freezing point of water and a glycol anti freeze solution i...

Страница 11: ...rature cannot be maintained at a 60 F minimum or when pond lake or well water that can fall below 60 F 15 C is used as the condensing medium special discharge pressure control must be used A water rec...

Страница 12: ...discharge pipe from the pressure relief valve should not be less than the size of the pressure relief outlet 5 8 in flare See Figure 8 for pipe size when combining low side relief on compressor sucti...

Страница 13: ...Application Considerations www DaikinApplied com 13 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR Figure 9 WGZ D Condenser Pressure Drop Curves...

Страница 14: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 14 www DaikinApplied com Application Considerations Table 2 WGZ D Evaporator Pressure Drop Curves...

Страница 15: ...Application Considerations www DaikinApplied com 15 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR Table 3 WGZ D Condenser Pressure Drop Data Table 4 WGZ D Evaporator Pressure Drop Data...

Страница 16: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 16 www DaikinApplied com Dimensions and Weights Packaged Units Figure 10 WGZ030DW 060DW Packaged Dimensions and Weights Packaged Units...

Страница 17: ...Dimensions and Weights Packaged Units www DaikinApplied com 17 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR Figure 11 WGZ070DW Packaged...

Страница 18: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 18 www DaikinApplied com Dimensions and Weights Packaged Units Figure 12 WGZ080DW 130DW Packaged...

Страница 19: ...Dimensions and Weights Packaged Units www DaikinApplied com 19 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR Figure 13 WGZ150DW 200DW Packaged...

Страница 20: ...ww DaikinApplied com Dimensions and Weights Packaged Units Figure 14 Lifting Locations WGZ030 060D Packaged Table 5 Lifting Weights WGZ030 060D Packaged Figure 15 Lifting Locations WGZ070 130D Package...

Страница 21: ...ngs running under the main unit supports The unit should be set initially on shims or blocks at the listed spring free height When all piping wiring flushing charging etc is completed the springs are...

Страница 22: ...00 ID 900 ID 900 ID 900 RP 3 RP 3 RP 3 RP 3 Green Green Green Green Gray Gray Gray Gray WGZ070DW ID 1350 ID 1350 ID 1350 ID 1350 RP 4 RP 4 RP 4 RP 4 Purple Purple Purple Purple Brown Brown Brown Brown...

Страница 23: ...hysical Data Packaged Units www DaikinApplied com 23 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR Table 10 Physical Data WGZ030D WGZ040D Table 11 Physical Data WGZ045D WGZ055D Physical Data Packaged Unit...

Страница 24: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 24 www DaikinApplied com Physical Data Packaged Units Table 12 Physical Data WGZ060D WGZ070D Table 13 Physical Data WGZ080D WGZ090D...

Страница 25: ...Physical Data Packaged Units www DaikinApplied com 25 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR Table 14 Physical Data WGZ100D WGZ130D Table 15 Physical Data WGZ150D WGZ200D...

Страница 26: ...ns and can only be used if the condenser leaving water temperature is 105 F or less Circuit Breakers The circuit breaker used in the High Short Circuit panel option may have a higher trip rating than...

Страница 27: ...l Data www DaikinApplied com 27 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR Figure 18 Field Wiring Diagram Packaged Units NOTE Points 904 910 908 and 909 are only provided if dual pump output option is...

Страница 28: ...door Motor Protection Module The motor protection system consists of an external control module located on each compressor motor terminal box connected to a series of thermistors located in the motor...

Страница 29: ...for troubleshooting In addition to displaying alarm diagnostics the MicroTech II chiller controller also provides the operator with a warning of pre alarm conditions Staging The four scroll or six com...

Страница 30: ...ircuit 2 UT Unit n Refrig Dependent NOTE 1 If Water Cooled Y then Entering Condenser If Water Cooled N then Outside Ambient NOTE 2 Selection of R134a in unit set point screen will modify unit operatio...

Страница 31: ...No Fault 16 Open 16 Motor Protection 2 R134a R410A C2 0 VAC Fault 24 VAC No Fault 17 Ice Mode Switch UT 0 VAC Normal 24 VAC Ice 18 Heat Mode Switch UT 0 VAC Normal 24 VAC Heat NOTE 1 Units with singl...

Страница 32: ...roller Digital Outputs The following parameters are digital outputs from this controller Types C1 Refrigerant Circuit 1 C2 Refrigerant Circuit 2 UT Unit Description Type Output Off Output On 1 Evap Wa...

Страница 33: ...can be adjusted to any value in the Range column The unit controller is also used for TGZ Templifier R 134a in HEAT mode see IOM 1319 on www DaikinApplied com for further information The PW password c...

Страница 34: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 34 www DaikinApplied com Unit Controller NOTE Temperature sensor SO 5 is Condenser Entering water sensor when Water Cooled ON...

Страница 35: ...en cleared Evaporator Flow Loss Alarm description Evaporator Flow Loss Trigger 1 Evaporator Pump State Run AND Evaporator Flow Digital Input No Flow for time Evap Flow Proof Set Point AND at least one...

Страница 36: ...point or higher and the freeze time has not been exceeded the timer will reset Action Taken Rapid stop circuit Reset This alarm can be cleared manually via the keypad if the evaporator pressure is ab...

Страница 37: ...s of compressor operation Action Taken Rapid stop circuit Reset This alarm can be cleared manually via the keypad EXB Comm Failure on CP1 Alarm description No EXB comm CP1 Trigger CP1 does not have co...

Страница 38: ...nt and number of High Condenser Pressure Unload occurrences since the circuit has cycled off or since midnight See table below Failed Pumpdown Event description Pumpdown Fail Cir N Trigger Circuit sta...

Страница 39: ...point is set equal to the current LWT set point IN cool mode this will be Evap LWT and in heat mode this will be Heat LWT Reset Type 4 20 mA The Active Leaving Water set point is adjusted by the 4 to...

Страница 40: ...is calculated for each circuit using the following equation Suction superheat Suction Temperature Evaporator Saturated Temperature Pump Down Pressure The pressure to which a circuit will pump down is...

Страница 41: ...rotect inputs are ignored during this time so as to avoid tripping a false alarm Ice Mode Start Delay An adjustable start to start ice delay timer will limit the frequency with which the chiller may s...

Страница 42: ...the Unit to shutdown compressors on a loss of flow up to two times every twenty four hours before locking the unit out on a Evaporator Flow Loss Alarm If there are no compressors running when Evapora...

Страница 43: ...hutdown The Alarm indicators are turned On and the Circuit Status for any circuit with running compressors becomes Off Ready the Unit Status becomes Auto Wait For Flow and the condenser water pump sta...

Страница 44: ...n the Valve Control Range Min set point and the Valve Control Range Max set point A valve increment shall be computed once every 5 seconds according to the following equation Increment Error Error Gai...

Страница 45: ...rmal as well allowing multiple compressor restart attempts before locking out the circuit Low Ambient Start Procedure A low OAT start is initiated if the condenser refrigerant saturated temperature is...

Страница 46: ...gerant 2 Number of compressors 3 Condenser configuration 4 How many high pressure unload occurrences since the previous midnight See below for initial offset value and step increase for each additiona...

Страница 47: ...the network limit value received from the BAS and is determined as shown in the following graph NOTE In order to allow all stages to run a signal of 100 0 is required Maximum LWT Rate The maximum rat...

Страница 48: ...The output should be off at all other times including the delay time described below The hot gas bypass valve opening will be delayed for Hot Gas Bypass Time set point seconds the default is 30 secon...

Страница 49: ...al setting UP Increment increases the value of the setting DOWN Decrement decreases the value of a setting These four edit functions are indicated by one character abbreviation on the right side of th...

Страница 50: ...keys on the controller are used to navigate through the menus The keys are also used to change numerical set point values contained in certain menus Figure 25 Menu Matrix Selection can be made within...

Страница 51: ...Enable OFF Unit Mode COOL Source KEYPAD Unit Enable settings can be OFF and ON as determined from the Unit Enable set point Unit Enable is an external signal or a keypad setting that keeps the unit of...

Страница 52: ...ompressor can stage off normally not by an alarm Default is 30 sec It is recommended that these settings not be changed of Compressors 4 SET COMP SPs 3 Comp 1 Enable Comp 3 Enable of Compressors 6 SET...

Страница 53: ...ettings below 60 F are not recommended Water cooled On SET TOWER SPs 3 StageDiff XX X F Stage Up Tmr XX min StageDn Tmr XX min StageDiff is the number of degrees below the Stage ON that will turn off...

Страница 54: ...fied by the Valve VFD Control set point The controlled parameter shall be the condenser entering water temperature When the desired output signal varies from 0 to 100 the output voltage shall vary as...

Страница 55: ...place is the shutoff of all compressors running when the LowEvPrStop setting is reached default is 58 psi Reducing these time intervals will increase detrimental compressor cycling It is recommended t...

Страница 56: ...Details Units of Measure Parameters will be expressed in different units dependant on the protocol selected Parameter Type Modbus Units BACnet Units LONworks Units Temperature F X 10 F X 10 C X 100 P...

Страница 57: ...Unit Controller Operation www DaikinApplied com 57 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...

Страница 58: ...0 to 59 Network Defaults The network set point default values are used only for the LONworks protocol Digital index 10 determines whether the network defaults should be loaded at startup The startup p...

Страница 59: ...t command will be required for the lockout to be cleared Code 2 Open Shorted Motor Thermistor The module will flash the red Alert LED two times indicating the motor PTC thermistor circuit has a resist...

Страница 60: ...If the relay does not close perform the following tests 1 1 Check the voltages between L1 L2 L1 L3 and L2 L3 These voltages should be approximately equal and within 10 of the rated three phase line to...

Страница 61: ...hours before starting the unit 8 Check compressor oil level Prior to start up the oil level should cover at least one third of the oil sight glass located in the equalizing line between the compresso...

Страница 62: ...s Do not leave the vessels or piping open to the atmosphere over the shutdown period Start up after Extended Shutdown 1 Inspect all equipment to see that it is in satisfactory operating condition 2 Re...

Страница 63: ...rel If installation on the inlet pipe is necessary contact Chiller Technical Response at TechResponse DaikinApplied com to review the jobsite details NOTE DO NOT alter or relocate factory installed fl...

Страница 64: ...tomatic Teach of Set point Table 26 Flow Volume Calculation Step 3 After the Teach function is completed and the outer LEDs flashed the flow switch will indicate a new set point based upon the current...

Страница 65: ...ure is performed to toggle to unlocked NOTE 18 The LED window display on flow switch represents a velocity range of 50 cm s The window centers on the set point SP For example if the SP was set to 200...

Страница 66: ...out additional compressors will stage off The last compressor will stage off when the LWT falls below the LWT Set point minus the Dead Band minus the Stop Delta T The stop Delta T is in effect for on...

Страница 67: ...the compressors on a circuit are disabled then the circuit will be disabled If both circuits have all of their compressors disabled then the Unit State will remain Off Automatic Pump Down WGZ units ar...

Страница 68: ...ath can occur The panel is always energized to ground even when the system switch is off To de energize the complete panel including crankcase heaters pull the main unit disconnect Be sure to read and...

Страница 69: ...not running Phase Voltage Monitor Optional The phase voltage monitor is a device that provides protection against three phase electrical motor loss due to power failure conditions phase loss under ov...

Страница 70: ...be slipped off its mounting stud for replacement Be sure to replace the coil on its mounting stud before returning the pumpdown switch to the auto pumpdown position To replace the entire solenoid valv...

Страница 71: ...Unit Maintenance www DaikinApplied com 71 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...

Страница 72: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 72 www DaikinApplied com Troubleshooting Chart Troubleshooting Chart...

Страница 73: ...Warranty Registration Form Scroll www DaikinApplied com 73 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll...

Страница 74: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 74 www DaikinApplied com Troubleshooting Chart...

Страница 75: ...Troubleshooting Chart www DaikinApplied com 75 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...

Страница 76: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Troubleshooting Chart...

Страница 77: ...Troubleshooting Chart www DaikinApplied com 77 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...

Страница 78: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 78 www DaikinApplied com Troubleshooting Chart...

Страница 79: ...Limited Product Warranty www DaikinApplied com 79 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR Limited Product Warranty...

Страница 80: ...uant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representat...

Отзывы: