Daikin IOM 1177-1 Скачать руководство пользователя страница 6

Page 6 of 8 / IOM 1177-1 / LIAF184

Sensor Functions

Figure 4: Sensor switches and functions

Status LED

Occupancy Switch

Override Reset 

Button 

System Switch

Fan Switch

Room Temperature

 

Adjustment

This sensor is used for water source heat pump 
applications requiring the following functionality:

 

Cool/Warm Room Temperature Adjustment

 – 

This slide adjustment is used to set the desired room 

temperature. To increase the desired room temperature, 

move the slide to the right toward “Warm”. To decrease 

the desired room temperature, move the slide to the left 

toward “Cool”.

• 

Occupancy Switch

 – Move the switch to the “Occ” to 

allow the unit to operate in the occupied mode. Move 

the switch to the “Unoc” to allow the unit to operate in 

the unoccupied mode. Move the switch to the “Off” so 

heating, cooling and the fan remain off. 

• 

System Switch

 – Set to “Heat” for heating only operation. 

Set to “Auto” for operation of heating or cooling as 

needed to satisfy the room setpoint conditions. Set to 

“Cool” for cooling only operation. The output voltage 

on Terminal 2 will change based on the system mode 

selection.

• 

Fan Switch

 – Set to “Auto” to allow the fan to cycle with 

all requests for heating or cooling capacity. Set to “On” 

to allow the fan to operate continuously as long as the 

MicroTech III control is not in an alarm condition.

• 

Status LED

 – This green LED will light to indicate the 

system status. See 

Table 8

 for unit status LED definitions.

• 

Override Button

 – When the “Override” button is 

pressed, the thermistor sensor across terminal 4 is shorted. 

If held for more than 5 seconds but less than 11 seconds, 

it puts the water source heat pump controller into a timed 

Occupied Override. If the unit is in alarm, then holding 

the “Override” Button for more than 11 seconds will clear 

all alarms in the water source heat pump controller but 

only if the cause of the alarm has already returned to its 

non-alarm condition. Some alarms will not reset from the 

room sensor.

In this case, power to the unit must be cycled off for 5 sec

-

onds to clear the alarm. Continuously resetting alarms from 

the room sensor could damage the controller. Please call a 

service technician when repeated alarm resets are required to 

keep the unit operational.

Table 8: WSHP unit status LED definition

Status LED

Unit Status

Unit Operation

ON

OFF

0.5 seconds

0.5 seconds

Controller Off  

(or Network “Wink” 

operation active)

“Alarm”

0.0 seconds

Continuous

Unit running in Night 

Setback Override 

Mode or no power to 

the sensor

“Override”

0.5 seconds

5.5 seconds

Unoccupied Mode

“Unoccupied”

5.5 seconds

0.5 seconds

Standby Mode

“Energy Save” or 

“Load Shed” com

-

mand from Energy 

Management System

Continuous

0.0 seconds

Occupied Mode

“Occupied”

Содержание IOM 1177-1

Страница 1: ...ith Occupancy Switch Sensor Part No 910121753 Used With Water Source Heat Pumps SmartSource Units with MicroTech III Controls Models GS GT Enfinity Units with MicroTech III Controls Models CCH CCW VFC VFW LVC LVW MHC MHW VHC VHF IMPORTANT Operator save these instructions for future use 2013 Daikin Applied www DaikinApplied com 800 432 1342 LIAF184 ...

Страница 2: ...ent and should be handled carefully Rough handling or distorting components could cause the control to malfunction The remote sensors cannot be used with systems where power interruptions are part of normal system operation NOTICE MERCURY NOTICE This product does not contain mercury However this product may replace a product that contains mercury Mercury and products containing mercury must not be...

Страница 3: ...Supple mental Primary 3 Way Valve Control Water Source Heat Pumps Hori zontal Enfinity W CCH CCW 1 1 No No No No No No No No No Vertical W VFC VFW 1 1 No Yes No No No Yes1 Yes No No Vertical Stacked W VHC 1 1 No No No No No No No No No Console W MHC MHW 1 1 No No No No No Yes1 Yes No No Hori zontal Vertical Smart Source 1 Stage W GSH GSV 3 4 Yes Yes Yes Yes Yes Yes Yes Yes Yes Hori zontal Vertical...

Страница 4: ...e and snapping the bottom into position Figure 1 Junction box mounting Junction box Field provided thermostat wiring 6 32 1 2 mountings screws Drywall Mounting 1 Place the base plate against the wall where you want to mount the sensor 2 Mark out the two mounting holes where the unit will be attached to the wall Drill a 3 16 hole in the center of each mounting hole and insert a drywall anchor into ...

Страница 5: ...tpoint Adjustment Room Temperature Sensor Tenant Override DC Signal Common Emergency Shutdown Unoccupied Adjustable Cool Warm Room Temperature Sensor with Occupancy Switch Part No 910121753 Maintenance Wipe the thermostat case as needed with a damp water only cotton cloth Do not use any type of cleaner as it may damage the buttons or labeling Do not paint Terminal Descriptions 1 Unit Status Indica...

Страница 6: ...as long as the MicroTech III control is not in an alarm condition Status LED This green LED will light to indicate the system status See Table 8 for unit status LED definitions Override Button When the Override button is pressed the thermistor sensor across terminal 4 is shorted If held for more than 5 seconds but less than 11 seconds it puts the water source heat pump controller into a timed Occu...

Страница 7: ...IOM 1177 1 LIAF184 Page 7 of 8 This page left blank intentionally ...

Страница 8: ... 2013 Daikin Applied www DaikinApplied com 800 432 1342 IOM 1177 1 LIAF184 Page 8 of 8 ...

Отзывы: